_ 1004 CHAPTER 40 1957 Guide ' Sound Control 1005 PWL, = PWL - 10 logiols-p1) dbe (18) ranging in size from 0.01 hp to 100 hp show that the sound power level in where : 1; iMplll g = quantity of air discharged, cfm. p = pressure, inches of water. a duct either upstream or downstream from the fan can be found within 4 db from the simple relation: PWL = 100 + 10 logioWis + 10 log,op dbe (19) PWL = sound power level actually measured. where Since static pressure p, is more frequently measured for fans than total pressure pt, p, may be used under most normal operations conditions We = nameplate electrical horsepower of the motor driving fan (assuming that the motor is operating near rated hp). (when the difference between p, and pt is less than 20 percent) and the error will then be less than 1 db. Near free discharge, p, becomes zero and p = pressure head, inches of water, dbe = number of decibels re 10~13 watt. pt must be used. In other words, PWL, is the sound power level that a (See discussion following Equation 18). 'I i |j similar (although hypothetical) fan would produce when operating at 1 The assumption is made that the fan is being operated near the "knee" ! i I;s on its operating characteristics, i.e., near maximum efficiency or near the minimum in the curve of specific sound power (upper curve oh Fig. 5). it: - fTi i i hU'irt {! 1 I!, III \ !i 1 1t Fig. 5. Specific Fan Characteristic Curves, Including Specific Sound Power Level These data are for a particular fan. The quantities 4, , 4, and PWL, are discussed in the text. Such curves apply to all fans in a mmilar series. cfm and a total pressure of 1 in. of water. As an example, the specific power level for one fan tested is shown on Fig. 5. Although few data are available to confirm the conclusion, it is indicated that such a plot also holds throughout a series of fans for all eight of the frequency bands provided rotor or blade passage frequencies are not pre dominant. Approximate Overall Sound Power Level In practice, data of the type shown in Fig. 5 are usually not available. Hence, in design an estimate has to be made of the overall sound power level and of the shape of the noise spectrum. Tests on centrifugal fans FREQUENCY BAND IN CYCLES PER SECOND Fig. 6. Chart, fob Determining the Sound Power Band Levels fob Ventilating Fans of Two Types TTie over-all power level is first determined from Equation 19 or 20 and is added algebraically to the or* mate m Fig. 6. Acoustics by L. L. Beranek (McGraw-Hill, 1954 Second Printing). Used by permission. By assuming a fan mechanical efficiency of 50 percent, Equation 19 can be put in the form of Equation 18 with PWLS = 65 dbe, i.e., where PWL = 65+10 logiog + 20 logiop dbe (20) 9 = air quantity, cfm. P -- pressure head, inches of water. (See discussion after Equation 18.) It should be emphasized that Equations 19 and 20 are intended to be used only when actual noise data are not available. All fans of the same Power input are not equally noisy. The example illustrated in Fig. 5 demonstrates this fact since the minimum value of PWL, for this particular