Document baZG2J3BXNdb7KONjGoq2Gp7g
43--Fire Protection
capable of carrying water under substantial pressures, yet flexible and sufficiently easy to handle Therefore, the fiie hose should be of suitable quality, properly cared for when used, and carefully maintained m storage Yard hose should be stored m standard hose houses for protection from weather (Fig 43-33).
Hose for outside or yard protection ordi narily is IK- or 25-in double-jacketed lined type or single jacket type when weight or bulk is undesirable Hoses made of polyester or other synthetic fibers are lighter, stronger, and mildew resistant (See NFPA Standard No 24, Outside Protection )
Woven-jacket, hned hose with an outer rub ber or plastic covei is chiefly used in industries
kept on a swinging rack or reel of approved type, approximately 5 ft above the floor or high enough so that it will not be a hazard to passers-by or be damaged by trucking opera tions See NFPA Standard No 14, Installa tion of Standpipe and Hose Systems
The hose should be so arranged that it will not kink or tangle when pulled out One end should be kept connected to the stand pipe, and the other end should be equipped with a %- or S-in. nozzle tip or a combination spray-solid stream nozzle To prevent kink ing in use, not more than 75 ft of hose should be placed at a standpipe outlet
Except for unlined linen hose, all fire hose
Fic 43-34 -- Hand-pump assembly for hydrostatic testing of hose
where the hose jacket must be protected against chemicals and abrasions
The lined hose with a rubber or plastic cover is available m X- and 1-in sizes, and is generally used as a booster hose, or as a hose on chemical engines, wheeled extinguish ers, and wall-mounted or vehicle-mounted pressunzed hose reels
For mside use by building occupants (as opposed to standpipe systems designed foi the fire depaitment), lJt-m unlined linen hose is satisfactory to provide small streams for fire protection If kept dry, it will last almost indefinitely It should never be used except in case of fire and should not ordinarily be tested because it will deteriorate if slightly damp However, with the introduction of light-weight, hned fire hose, which has twice the hydraulic efficiency of unlined hose, many firms are replacing the unlined hose on their industrial standpipe installations The unhned hose has its place m such locations as office buildings, where it would be discarded and replaced if ever used The hose should be
1370
should be hydrostatically tested annually, thoroughly inspected, dried and returned to service (Fig 43-34)
Monitor nozzles. Permanent monitoi noz zles are frequently used to protect pulpwood storage piles at paper mills, m lumber yards, in stock yards, and m railway car storage yards Nozzles are often elevated to clear obstructions so that the operator can stand on a shielded platform and direct a high-pressure stream of water over a wide area Such systems aie especially useful in large con gested aieas where it is impractical to lay hose lines in an emergency
Hose nozzles Effective streams for fire fighting aie controlled by the size and type of nozzle The nozzle, in turn, must be sup plied with the correct quantity of water at the discharge pressure for which it is designed Nozzles are designed for solid streams, spray streams (frequently referred to as fog), or combination streams And nozzles for special