from .name location> p. q# Benignus - St. Louis
DATE = September 8, 1970
subject : Therminol 55 Type Fluid as possible Dielectric
ftEFCRENCE
?
TO : DR. R. H. MUNCH QUEENY
cc W. R. Richard - WRICH J. G. Bryant - JBRYA D. A. Olson - DOLSO H. S. Bergen - HBERG R. Davis - RDAVI M. F. Baber - MBABE
For your convenience and as Bill Richard requested this data, I am pleased to enclose the properties and ASTM test methods for uninhibited transformer mineral oil. In general, this is also used for circuit breakers. However, for circuit breakers a somewhat lower viscosity is sought. The exact value at zero centigrade sought is 300-320 SUS. It has been indicated to
me that the viscosity of Therminol 55 is 215 SUS at 37.8C.
Accordingly the viscosity of Therminol 55 as given is higher than desired by dielectric use. The same thinking pertains relative to the published minus 20F pour point for Therminol 55 versus minus 40F or lower sought for dielectrics used in transformers, circuit breakers, and cables.
However, Don Roush and others indicate that various fractions from the Chocolate Bayou stream may be available with lower viscosity and pour point than for Therminol 55.
Your results show that these fluids can be cleaned up to ex
cellent, electrical values.
Costs are indicated to be quite low, indicating orderly econo mics possibly for use as dielectrics.
We are aware of industry interest in dodecyl benzene materials for cables, etc. Doble win evaluate a 100 gallon sample at .
a stipend of something like $1500. This would encompass the more costly arc testing which is a requirement relative to possible use for circuit breakers and cables. Doble*s evalua tion including oxidation stability tests as related to trans former applications -have carried a much lower stipend.
*5 'S'%.
(VO
o 'O
O*. VnTv
Y
This area of dodecylbenzene related materials appears as one
'of the very few new ventures open to us at the moment. I am
sure that we are all interested in pursuing it. Possibly
Jim Bryant may well be assigned to exploring availability and
general physical properties of the various streams of this
type material at Chocolate Bayou. You earlier pointed out
and we certainly agree with your thoughts that it is highly im
portant for us to learn what materials in this area are avail
able to us. I think that Jim Bryant could develop-this for us
if he were given it as a project.
.
DSW 201859
P. G. Benignus cr
STLCOPCB4059926
UNINHIBITED TRANSFORMER OIL PURCHASE . SPECIFICATION TESTS*
TYPE OF TEST
Acidity, mg KOH/g** Aniline Point, C Color ASTM ' Corrosive Sulphur Dielectric Strength, kv Dielectric Strength, kv Flash Point, C Interfacial Tension, dynes/cm Pour Point, C Ferrer Factor at 100C, % Power Fcctor at 25 C, % Specific Gravity, 60/60 Viscosity at 37. 8C
Kinematic, cs or Saybolt Sludge-Free Life, measured at 8-hour periods
-
PFVO Rating ***
TEST LIMITS
.025 max. 78 - max.
0.5 max. Passes
26 - min. 20 - min. (.04" gap) 130 - min. 40 - min. -40 - max.
0.3 max. 0.05 max.
.865 - .910
11 - max. 62 - max.
64-hr. min.
See attached graph
ASTM METHOD
D974 (Modified) D611 D1500 D1275 DS77 D1816 . D92 D971 (unfiltered) D97 D924 D924 D1298
D445, D446 . D88, D446
D1904-6IT (Modifled)
* These specification tests were developed after several years of study and research sponsored by a representative group of the utilities in the United States
** Acidity to be measured by ASTM proposed modification to D974, using 1/100 normal solution and a micro-burette.
*** Any oil for which the power factor curve lies within the acceptable area and
does not cross the graph until 72 hours or later, is considered an acceptable oil. The
time (Hours) that the power-factor curve of an oil crosses the limiting graph is indicative
of the cpjalify of the oil.
.