Document bOLNjdoBZb8mJzQGqy9DGpqjg
American Society of Heating and Ventilating Engineers GuiDe
Combined Systems. There are various central fan systems which, used for both heating and ventilating. They are usually arranged tempering heating units, automatically controlled to provide a mini, temperature for ventilating only, and additional heating units to su the heating requirements. Fig. 6 shows a type of system which reheating units located in the fan room. Tempered air at about 7q supplied to the fan. It may be further heated by the reheating unitSi may pass into the tempered air chamber. A room thermostat control* gradual-acting damper operator on the double mixing damper in the wari and tempered air chambers. When the thermostat calls for heat,
jf^3^GHAPtER l4--Automatic Control
HllrtPK^rlbnuaildlinSygstsemtshe heating plant may be controlled by a single located in a key room in the building, instead of each room
conmcmonontroclo. ntrol for a hand-fired furnace or boiler consists of IP^--ostat and a furnace regulator of some type. The thermostat mm?* located in a representative room; never, of course, near the
or heat flue, too close to a radiator, or in a drafty hallway, and -t-.rtiiiey ^ inside wall. The regulator is attached to the draft and
pampers of the furnace. When the temperature of the air sur-
Fig. 5. Use of Pilot Thermostat on Ventilating System with Air Washer
damper operator moves the dampers so that more air is taken from the warm air chamber. It is essential that the double mixing damper be
moved slowly to prevent alternate blasts of hot and cold air from being supplied to the room.
Outside Air, Recirculating, and Vent Dampers. In all types of plenum systems, the outside air damper is usually opened and closed by a damper 5 operator. This operator may be controlled from a switch in the engi neer's room or it may be operated by a relay in the fan motor circuit. When the ventilating fan is started, the relay causes the damper operator to open the outside air damper.
Recirculating dampers and vent dampers may also be opened and
closed by means of damper operators controlled from remote locations.
Generally these damper operators are positive acting and are either
completely opened or closed. However, in some cases where part out
side air and part recirculated air is used, it is advantageous to use damper
operators which have a certain number of definite positions. With -this
type of operator it would be possible to use 75 per cent outside air and
25 per cent recirculated air, or any other proportions which might be
predetermined. These damper operators are controlled from switches
generally mechanically interlocked so that the total opening of the two
dampers is 100 per cent.
! ,.
246
Fig 6. Control of Mixing Dampers with Intermediate-Acting Thermostat
rounding the thermostat drops, the thermostat causes the furnace regu lator to open the draft and close the check damper. As soon as the room comes up to temperature, the draft is closed and the check damper opened. With this arrangement on hot water heating systems it is advisable to install an immersion thermostat in the boiler. This thermo stat should be connected with the room thermostat so that both must call for heat before the draft is opened, but either one may cause the draft to be dosed. On warm air systems it is advisable to use a bonnet thermostat and on steam heating systems a pressure limiting device, in series in each case with the room thermostat. If the temperature of the heating medium becomes too high, the drafts will be closed even though the room ^
theTrhmeorestahtavceonbteineunessotmoecarellcefonrt himepart.ovements in controls of this type, involving the use of special types of'thermostats and auxiliary apparatus which will give closer control and prevent overheating in mild weather.
CONTROL OF AUTOMATIC FUEL APPLIANCES It is essential that automatic temperature control be used with oil burners, gas burners, and stokers to aid economical operation. There are
247