EXHAUST SYSTEMS, GENERAL 6 COMFORT VENTILATION general ventilation are obtained This dis tribution also provides closer control of the ambient working temperature Makeup air temperatures are usually maintained at approximately the same as the desired room temperature Since this air is being used for ventilation and re placement purposes and is not relied on for heating the building, the usual temperature range will be 65-80 P However, in modem high-speed machining areas where equip ment heat load is a factor, lower air tem peratures can be used Makeup air is also used for spot cooling applications at very high heat stress operations In these cases the final air temperature and air motion depend on the workers' requirements Makeup air equipment There are three basic equipment types (1) beat exchangers using steam or hot water, (2) direct-fired heat exchangers using oil or gas, and (3) open flame heaters. 1 Steam and hot water units should be pro vided with distnbuhng-tube coils (non freeze) and automatic controls to mini mize the possibility of freezing the heat ing coils during subzero conditions. Controls will include modulating valves, thermostats and motor-operated outside louvers. Multiple coil units with preheat and reheat cods usually give closer con trol of discharge air temperature than single cod units. Condensate return pip ing must be sized for the large volumes of returned water and coils must be vent ed properly to assure proper flow at various positions of the mam valve 2 Direct-fired units must he vented to the outside and must be provided with ade quate safety controls as specified by the American Gas Association and various underwriting firms Attention must be given to proper location horn the stand point of air distribution and restrictions for hazardous locations 3 Open-flame beaters are those units in which the fuel is burned directly in the makeup air stream with no outside vent ing These units are usually gas fired and the combustion safety controls must be of the approved type Care must be taken in their location also, especially where hazardous materials are involved. Since these units present a potential dan ger of carbon monoxide gas, additional requirements must be met a The makeup air volume must be suffi cient to dilute any possible carbon monoxide to less than 25 ppm. b Controls must stop the supply fan and close the mam gas valve in case of any flame failure C. Controls should be arranged to inter lock the makeup air unit with exhaust fans (or the mam exhaust fan) to prevent the unit from being operated without sufficient exhaust ventilation Heating of process makeup air The material in this section is taken from Amencan Gas Association's A Complete Guide to Direct Gas-Fired Heating of Process Makeup Air, published in Actual Specifying Engineer Magazine (Dec 1061, Feb and March 1962). The three most common heating media for low-temperature industrial beating proc esses are oil, gas, and steam, and all have some application in heating makeup air Makeup au heating should not be confused with space heating, which heats the build ing whether or not processing lines are func tioning within it However, makeup air can be supplied to an entire building area as well as directly compensating for air be ing exhausted at one point or being lost through loading dock doors. General factors which must be considered are 1. Proper location, size, and construction of air intakes 2. Filtering of makeup au if necessary 3. Au handling equipment must be ade quate to keep au in the building under positive pressure, even with exhaust systems in use This will reduce drafts and minimize dispersal of contaminants in the work area. 4 Automatic controls must be provided to assure delivery of makeup au at ac ceptable temperatures to persons work ing in the area They should be located in a place as clean and free of vibration as possible 5 Proper startup and shutdown procedures must be enforced 6 Controls and safety devices should be 28-65