CHAPTER 31
1962 Guide And Data Book
relief from coil to suction line, to permit a build-up of coil
pressure and melting of the ice coating by transfer of beat out of
the air flowing across the coils. Refrigeration therefore continues
during the defrosting period, but at a drastically reduced rate.
Room air defrost is alow; the
required may vary from 30
minutes to several hours if the coils are undersued for dry coil
operation.
Unit coolers may be defrosted by any one or combinations
of the three methods. Ail methods involve a reduction in
chilling capacity varying with the time loss and the heat in
put. Hot gas and coil spray defrost interrupt the chilling only
for short periods but introduce some heat into the space.
Room sir defrost severely reduces the chilling rate for long
periods, but the heat required to vaporize the ice is obtained
entirely from the room air. This method is generally consid
ered impractical in air temperatures below 40 F, because of
the long defrosting periods encountered. However, it is prac
ticable in air temperatures as low as 35 F if the coils are large
enough to avoid excessive icing.
Evaporator control customarily employed in carcass chilling
and holding rooms include (1) refrigerant feed controls,
(2) evaporator pressure controls, and (3) air circulation control.
1. Refrigerantfeedcontrol* are designed to maintain under varying load as high a liquid level in the coil as can be carried without excessive liquid spill-over into the suction line. This is accom plished by the use of an expansion valve that throttles the liquid from supply pressure (typically 150 psig) to evaporating pressure (usually 20 psig or higher). The throttling of the liquid flashes some erf it to gas, which chills the remaining liquid to saturation temperature at the lower pressure. The flashed gas, if it does not bypass the coil, tends to reduce flooding of the interior coil sur face and thus lower coil efficiency.
The valve used may be a hand expansion valve controlled
manually by operator judgment aJoae, a thermal expansion
valve governed by the degree of superheat of the suction gas, or
a float valve (or solenoid valve operated by a float switch)
governed by the level of feed liquid in a surge arum placed in the
coil suction tine. This surge drum-suction trap permits the
ammonia flashed to gas in the throttling process to now directly
to the suction line, bypassing the eoiL It may be small and placed
just high enough so that its level governs that in the coils by
gravity transfer. Or, as in the ammonia recirculation system,
it may be placed below coil level so that the liquid is pumped
mechanically through the coils in much greater quantity than
required for evaporation. In the Utter caseIt is sired Urge enough
to carry its normal operating level plus all the liquid flowing
through the coils, thus effectively preventing liquid spill-over
to the compressors. Nevertheless, it is necessary in all cases to
rovide further protection at the compressors against return of
quid.
Manual and thermal expansion valves do not provide good
coil flooding under varying loads, and do not bypass the ftmfuwi
feed gas around the coils, hence evaporators so controlled are-
usually rated 10 to IS percent lees in capacity than those con
trolled by.float valve or ammnni% recirculation.
2. Evaporator pressure controls provide a nwun of regulating
coil temperature, and thereby the rate of refrigeration, by vary
ing evaporating pressure within the eoiL This is accomplished by
the use of a throttling valve in the evaporator suction line
downstream from the surge drum suction trap. All such valves
impose a definite loss on the refrigeration system, and the amount
of the kiss varies directly with the pressure drop through the
valve. This increases the work of compression for a given re
frigeration effect.
The valve used to control evaporating pressure may be a man
ual suction valve set solely by operator judgment, a back pressure
valve actuated by coil pressure or temperature, or a back pres
sure valve actuated by a temperature searing element
at
some point in the room. Manual suction valves require excessive
attention when loads fluctuate. The coil-controlledhack pressure
valve seeks to hold a constant coil temperature, but this does not
control room temperature unless the bad is constant Only the
room-controlled compensated back pressure valve responds to
room temperature.
3. Air circulation control is frequently used when an evapora
tor must handle separate load conditions that differ greatly in
magnitude, such as the load in chilling rooms that are used
as holding rooms or the negligible bad for week-ends. Control can be accomplished to a degree by the use of two-speed fan motors (operated at reduced speed during the periods of light bad) or by turning the fans off and on.
BEEF CARCASS CHILLING AND HOLDING COOLERS
The Chilling and Holding Function
The /unction of the chilling and holding coolers is to chill the freshly slaughtered and dressed carcass halves or sides to storage temperature in minimum time, with controlled dry ing of the surfaces, and to provide storage under optimum conditions of temperature, humidity, and air motion. Exces sive shrinkage, bone taint or sour rounds, surface- slime or mold, discoloration, and freezing must be avoided. The carcass must be delivered with the bright, fresh appearance demanded by the trade.
Although the basic principles involved are identical, in cer tain aspects, beef and hog carcass chilling differ substantially. The massive beef carcass is only partially chilled (although shippable) at the end. of the standard overnight period-- whereas the average hog carcass may be fully chilled (but not ready for cutting) in 5 to 6 hr while the balance of the period accomplishes temperature equalization only. The beef carcass retains on its surface a large amount of wash and shroud water, which provides much evaporative .cooling in addition to that derived from actual shrinkage; but evapora tive cooling of the hog carcass, which retains very little wash water and is not shrouded, occurs only through actual shrink age. Although it must subsequently be tempered well for cutting, the hog carcass, including the skin, and scheduled for in-plant processing, can tolerate a certain amount of surface freezing; but the beef carcass, without skin and destined largely for sale as fresh cuts, must be chilled in air tempera tures sufficiently high to avoid freezing and damage to ap pearance. Nevertheless, as a result of the retained surface water, shrouded beef carcasses can be chilled with an actual overnight shrink of # to 1 percent, whereas equally good prac tice on hog carcasses will result in 1>{ to iyi percent shrink.
The bulk of the beef chilling is done overnight (18 to 24 hr) in chilling rooms having large refrigeration and air circu lation capacity. The balance of the chilling, and tempera ture equalization, occur during a subsequent holding or storage period that averages perhaps one day, but frequently extends to two or three, usually in a separate holding room having low refrigeration and air circulation capacity.
Cooler Layout and Capacity
The carcass halves or sides are supported by hooks sus pended from one-wheel trolleys running on overhead rails. These are generally pushed from the dressing floor to the chill ing rooms by powered conveyor chains equipped with fingers that engage the trolleys, then distributed manually over the chilling and holding room rail system. Chilling and holding room rails are commonly placed on 3H to 4 ft centers, with pull-out or sorting rails between in the holding rooms. The rails must be placed a minimum of two feet from the nearest obstructions such as a wall or building column, and the tops of the-rails must be at least 11 ft above the floor. The sup porting beams should be placed 2J^ ft (or more if ceilingsuspended refrigeration units are to be used) below the ceiling, for optimum air distribution. Regulations applying to some of these dimensions, applicable to new construction in plants engaged in inter-state'commerce, are issued by the the Meat Inspection Division of the USDA.
Carcass sides should be so placed on the rails in both chilling and holding coolers that they do not touch each other, to
I # 'T" Med* onc* ^res*1 n*
assure effective air circulation. Required spacing varies with the size of the carcass, averaging 2M feet per two sides of beef. In practice, however, sides are often crowded more closely together.
The chilling room should be of such size that the last carcass loaded into it does not materially retard the chilling of the gret c*T*aq- While size is not as critical as in the case of the bog carcass chill room, because of the slower chill, a capacity ezCeeding four hours' kill will result in unnecessary shrink. Holding coolers may be as large as desired, because of the more uniform temperature and humidity that can be main tained in them.
While overall plant chilling and holding room capacities Vary widely, chilling coolers generally require a capacity equal - to the daily kill, and holding coolers twice the daily kill. The Beef Carcass
The dressed beef carcasses, split into two sides, range in (Peight from approximately 300 to 1000 pounds, averaging about 550 pounds per head. Specific heats of carcass com ponents range from 0.50 for fat to 0.80 or more for lean muscle, averaging'about 0.75 Btu per (lb) (F deg) for the carcass as a whole.
The body temperature of tbe beef animal at slaughter is about 102 F. After slaughter, and continuing for 30 hours or more, changes occur that generate heat and tend to increase carcass temperature, while heat loss from the surface tends ito lower it. ' The most massive part of the carcass is the round, and at any given stage of the chilling cycle its center will show the highest temperature of all carcass parts. This deep round temperature (about 105 F when the carcass enters the chill ing cooler) is therefore universally used as a measure of chilling progress. The temperature must be taken accurately if it is to be significant. Incorrect techniques in common use will show temperatures as much as 10 F deg lower than actual deep round temperature. An accurate technique that yields con sistent results with ordinary care is shown in Fig. 1. This em ploys a fast-reacting easily-read 8-inch stem dial thermome ter, calibrated before and after tests, inserted upward to the full 8-inch depth through the hole in the aitch bone.
Fig. 1 .... Deep Round Temperature Measurement in Beef Carcass
339
fig. 2 .... Typical Beef Carcass Chilling-Holding Temperature Curves
At the time of slaughter, the water content of the beef muscle is approximately 300 percent of dry weight (75 percent of total weight). Thereafter a gradual drying of the surface takes place, resulting in weight loss or shrinkage. Shrinkage and its measurement are greatly affected by the final opera tions in the dressing process: weighing, washing, and shroud ing. Weighing must be done prior to washing arid shrouding if the weights are to reflect actual product shrinkage. The beef carcass retains on its surface and carries into the cooler a large amount of wash and shroud water, loss of which does not constitute actual product loss.
The amount of wash water retained by the carcass depends on its condition and on washing techniques. A typical amount retained per carcass is81b, part of which is lost bydrip and part by evaporation. Water pressures used in washing vary from 50 to 300 psig, and tempreatures from 60 to 100 F.
The shrouds which are cloths saturated in warm (120 to 130 F) weak (under 20 Salometer) brine and applied to outer surfaces of better grades of beef in an attempt to enhance appearance, remain in place throughout the chill period but are removed before the carcasses are transferred to the hold ing rooms. The cloths used weigh about 10 lb wet and 4 lb dry per carcass (two sides.) These lose about 6 lb of water per car cass in the chilling cooler, partially by drip but largely by evaporation.
To minimize spoilage, the carcass should be reduced to a uni form temperature of about 35 F as rapidly as possible. In practice, deep round temperatures of 60 F (accurately meas ured as in fig. 1), with surface temperatures of 35 to 45 F, are common at the end of a 20-hour chill. A certain dryness of the carcass surface is necessary during storage to prevent formation of surface slime. Exposed beef muscle chilled to an actual temperature of 36 F will not slime readily if dried at the surface to a water content of 90 percent of dry weight (47.4 percent of total weight). Such a surface is in vapor pressure equilibrium with a surrounding atmosphere at the same temperature (36 F) and 96 percent relative humid ity. In practice, a room atmosphere at 32 to 34 F and 90-95 percent relative humidity will maintain a well-chilled carcass in non-sliming condition.1
The Chilling-Drying Process The chilling of the shrouded beef carcass occurs to some
extent by sensible transfer of heat to the surrounding air, but primarily by evaporation of water from its surface. Curves of carcass temperature during a typical chilling-holding cycle are shown in Fig. 2. Note that some heat loss occurs before the carcass enters the chilling cooler.
Sensible transfer of heat from the warm carcass to the cool