Document bBppDxNaoX9zp92LLrRD8L5kZ
162
CHAPTER 12
1965 Guide And Data Boole
Odor Detection and Measurement
While odor sensing is not fully understood, what is known should be discussed insofar as it gives understanding of what constitutes an odor problem and yields some insight into cer tain odor control methods. Sensing involves the dissolving of odor molecules in the fluids bathing a small area high in the nasal cavity. As this occurs, some unknown interaction stimu lates the generation of electrical impulses which pass along the olfactory nerve to the brain's olfactory bulb. The brain then correlates the information in terms of its past experiences. There is no reason to believe that the mechanism differs from person to person, since most people will qualify the am odors similarly. There is ample evidence, however, that the sensitivity to and reaction to an odor will vary from person to person and from time to time. For example, most people will describe acrolien as a burnt odor, and benzaldehyde as a floral or fruity one. In general, the women, the young, the non drinker, and the non-smoker have more acute senses of smell than their opposites. High temperatures and high humidities: reduce acuity. The former presumably dessicates the nasal., mucosa, and the latter presumably floods or dilutes the con centration at the sensor. Sensitivity varies from day to day or hour to hour, depending upon the state of health, traumatic offense to the olfactory system, or recent odor exposures.
Odor detection and measurement must rely ultimately upon olfactory observations and human appraisal. A trained organ oleptic panel is presently the best means of evaluating odor intensities because the nose is still the best instrument for odor perception.
An arbitrary preference scale of increasing odor values is usually selected. For instance, the.sensory scale utilised by Yaglou7 for cigarette smoke classifies odor as: 0--imper ceptible, 1--not objectionable, 2--acceptable, 3--objection able, 4--endurable, and 5--intolerable. This scale has been found convenient for use in air-conditioning odor investiga tions. As discrimination develops with experience, the ob^ jective sensory scale can be divided into more classifications.
Another method, employed by Hopper,* bases odor in tensities on multiples of threshold concentrations. In this method a source of odorless air and a method of miring it, in easily variable proportions, with the odor sample is used. The mixture is adjusted until the odor is barely discernible. The result, expressed as the ratio of mixture volume to' sam ple volume, is called the number of thresholds; At threshold, or barely discernible intensity, the nose is operating at its most sensitive point. The number of thresholds has a useful meaning. For instance, 10 thresholds has the implication that 1 cu ft of odorous gas can taint 10 cu ft of air to a recognizable level*
Zn the ADL concept of odor intensity, a five-point scale has been developed.1* The intensity scale is simple and con stant, and is described as follows:
0--not present )(--threshold or just recognisable 1--slight 2--moderate 3--strong
pied spaces. In the past, the application of proposed stand ards has not been feasible, owing to the difficulty of identify, ing and measuring the odor-producing vapors present in agiven space. However, a method using the threshold approach has recently been suggested. Once standards have been agreed upon, the number of thresholds in a given space can be meas ured with the aid of various air-dilution devices. It would then be possible to rate odor-control systems for their effec tiveness in reducing the number of thresholds in a given time and in maintaining a reasonable odor level. That approach could be used for different types of systems using dilution with odor-free air, whether the air were brought in from outdoors, or recirculated and purified by sorption equipment.
Various chemical analytical techniques have been proposed ' and evaluated in an effort to standardize odor measurement methods. Detection and identification of a complex odor mixture at threshold levels is generally beyond the sensitivity of presently available analytical instruments. Concentration of the odor molecules may be achieved by adsorption on acti vated carbon or by absorption in a liquid. The sorbed odors may be desorbed and identified by infrared or ultraviolet spectroscopy. Alternatively, the concentrated odorants in the liquid system may be determined by standard chemical reactions.1*
Odor Sources
When'the concentration of odorous vapors in the air is in sufficient.to permit odor perception, the air is commonly to be odor-free. Therefore, to eliminate or abate an odor con dition, it is necessary either to remove the offending gaww 0r vapors or adequately reduce their concentration or intensity by odor modification to create an environment of greater comfort.
The sources of odors that cause discomfort to individuals in occupancy areas are many. They may be introduced from the outdoor atmosphere and contain a high percentage of hydrogen sulfide, industrial effluents, or snog. In industrial spaces they may contain odors from ftHaminal products such as printing ink, dyes, synthetics, and odors from manufac tured rubber products. In offices, arenas, and other enclosed spaces, obnoxious odors may consist of body odors and to-' bacco smoke odors. Cigarette smoking may produce objec tionable pyridine, ammonia odors, and irritants, anH alan impair visibility.7 Odors may also result from wetted air-
The three levels of intensity, slight, moderate, and strong, can be related to three segments of intensity on a scale of 29 levels or just noticeable differences. Regardless of the used, the Weber-Fechner law for detectable low intensities of odors is generally applicable. This law states that the per ceived intensity is proportional to the logarithm of the ex ternal concentration, or that the ratio, in concentrations, which produces a detectable difference, is a constant.11
It should be possible to establish odor standards for occu
fig. 1 .... Adaptation to Smoke Odor and Irritation Caused by Ggaretto Smoke Generated in Room -
Qdp,
^itinnms coils as they become dirty. The metals and . con^V_ qjj materially affect the possibility of ""SL objectionable odors.1* Odors may be contributed by
paint, upholstery, rugs, drapes,-or other household rLjohmw- Food, cooking, and putrefaction of animal and Ugetable matter are also frequent contributors.
Humidity and Temperature Effects
Research conducted at the ASHRAE Research Laboea-
HY
elsewhere has indicated that odor perception of
cigarette smoke (suspension of tobacco tar droplets plus
vapor), and pure vapors is affected by temperature and
humidity. An increase in humidity, at constant dry-bulb tem
perature, has the definite effect of lowering the intensity
level of cigarette smoke odor as well as that of pure vapors.14
This effect is more pronounced for some odorants than for
others. An increase of temperature at oonstant specific hu
midity lowers the odor level of cigarette smoke slightly.
Adaptation to odors takes place more rapidly during the
initial stages of exposure. While the perceptible odor level of
cigarette gmV decreases with time of exposure, irritation
to the eyes and nose generally increases. The irritation is
greatest at low relative humidities.
In order to keep odor perception and irritation at a mini
mum,' the air-conditioned space should be operated at'about
45 to 60 percent relative humidity (see Fig. I). Since tempera
ture has only a slight effect on odor level at constant specific
humidity, it generally can be ignored and the temperature
maintained at conditions desired for comfort or economy.
Adsorption and Release of Odors
Tests have been made on the odor adsorption and release of cotton, wool, nylon, rayon, and fir wood.' It was deter mined, by using iso-amyl acetate as the odor agent, that the odor adsorption of rayon was negligible. The odor adsorption at tiie end of a 24-hour charging period was about the' same for nylon and cotton at the same temperature and humidity. The odor adsorption of wool under the un<> test conditions was less. Adsorption of the wood samples was less than nylon and cotton, but more than wool
Odor retention or release as a function of airing time is affected by temperature and humidity. For the fabrics tested and at 75 F, 50 percent relative humidity conditions, odor retention after 1000 min.was reduced to 6.8 percent for cotton, 12.3 percent for nylon, and 25.8 percent for wool In the latter case the initial wool retention was only about 25 percent of that of cotton or nylon. After 1000 min the
163
odor retention of wool was comparable, to that of cotton. Wood lost its odor after 300 min.
These data are meager, but indicate a trend useful for /Ipgjgn Application of the quantitive values should not be made without due consideration of the finish, weight, weave, anH thrpftH count of the fabrics. Further research.is needed relative to these items.
- While it has been shown that smoke, cooking, and body odor perception is decreased with humidity increase, where the odor source is intrinsic with the materials, as in the case of linoleum, paint, rubber, and upholstery, a reduction of relative humidity would be beneficial,1* and would decrease the rate of odor release.
ODOR REMOVAL
Odor removal may be accomplished by physical or chemical means. Ventilation with dean outdoor air, dr washing or scrubbing, charcoal adsorption, chemical reaction and odor modification are physical methods available to the engineer. Chemical adsorption or destruction of odor sources, vapor neutralization, and catalytic combustion are other means. Air washing or scrubbing and combustion are of considerable value to process industries. Washing and scrubbing, like filtering, are applicable to the removal of particulates and in some cases are means of recovery of valuable product. Odors associated with the particulates are removed indirectly in such processes. Combustion of obnoxious gases is quite effec tive and' practicable where indicated by economy.- These methods are employed to alleviate the effects of harmful ex haust gases and particulates on people, vegetation, and property.
Ventilation, charcoal adsorption, and odor modification are effectively utilized in air conditioning for odor removal Hie removal of'odorous gases or vapors by water sprays in airconditioning systems is most' practicable for water-soluble odors such as Ammonia, but not for water-insoluable odors.
Ventilation
Ventilation is an effective means of removing the con taminated air in an enclosed space by dilution. In this process, the vitiated air containing objectionable gaseous odors, ir ritants, particulates that obscure vision, and toxic matter are
* ^ rotftbod to provide oocewary oxygen coafeof.
K y to1 'Wnd to prevent COt content)ufioo from rfcog above 0j6 petetf. fydrerf resaove objectionable body odara from tedtitary odufh. from tvrve C too-owed by 50 percent (and projected) to eOow for defoto pfcydcaf ocb'vOy and odors.
fig. 2 .... Minimum Ventilation Requirements to Avoid Vitiation and Obnoxious Body and Smoking Odors
Rg. 3.... Physiological Effect of Various Concentrations of Carbon Dioxide