Cooling Load
321-:
8, Table 3. Assume that the outside doors will be used at the rate of 10 persons per hour and the inside doors at the rate of 30 persons per hour. Total infiltration will then be 40 X 100 = 4000 cfh or 67 efm.
The.design rate of entry of outside air is then:
Q = 1275 + 67 = 1342 cfm.
The sensible, latent and total loads are determined from Equations 13, 14 and 15 respectively at 3:00 P.M. (Table 13) t, = 95, <i = 80, W,, = 0.0169, W, = 0.0098. AH the air entering the room as infiltration becomes a part of the space.load.
Infiltration:
q. = 67 X 1.08 (95- 80) = 1085 Btuh sensible.
q. = 67 X 4840 (0.0169- 0.0098) = 2300 Btuh latent.
2t =* 2 + 9e = 1085 + 2300 = 3385 Btuh total.
Ventilation Air Taken Through Cooling Unit Which Does Not Become a Part of the Space Load:
r q. = 1275 X 1.08 (95-80) = 20,700 Btuh, sensible.
2,, = 1275 X 4840 (0.0169- 0.0098) = 43,800 Btuh, latent.
2t = 2. + 2. = 20,700 + 43,800 = 64,500 Btuh, total.
Heat Gain from Sources within the Conditioned Space: For the occupants, use the data of Table 24 for moderately active office work.
-.. Sensible heat gain = 85 X 200 = 17,000 Btu per hr. Latent heat gain = 85 X 250 = 21,250 Btu per hr. Total = 38,250 Btu per hr.-
For the gain from lighting, use Equation 16 with a use factor of unity, and a special allowance factor of 1.20 for the fiuorescents and of unity for the tungsten globes.
9.1 = (12,000 X 1.20 + 4000) X 3.41 = 62,700 Btu per hr. For the fan motor, use Equation 17 with a load factor of unity and omit term Motor Efficiency because the motor is not within the space.
9a = 7.5 X 2544' = 19,100 Btu per hr.
' Moisture Permeation, Miscellaneous Allowance, and the Load-Lag Estimate-
1 Moisture permeation will be negligible, since this is a comfort job" with a good
building construction.
. ..
There would be some heat gain in the ductwork, but this would not be great be cause of the short run'involved. Practical judgment for this job would'suggest that no adjustment for load-lag need be made to the load as computed. (Refer to Fig. 6).
While it is true.that inside radiation forms an important part of the total heat gain,
it is advisable to be conservative in recognizing the effect of the large,.flat, hot roof on the comfort sensations of the occupants. Radiation from the relatively low ceiling,
augmented by heat absorption from the lighting fixtures, would produce a sensation
of warmth in excess of the nominal effective temperature (see Chapter 12)-'estab
lished by the wet bulb and dry bulb temperatures. Hencej it is not desirable to take advantage of every small decrease possible in the peak design load-, especially since-
the peak occurs in mid-afternoon when everything would be rather well warmed.
Total Loads arid Required Air Quantity through Conditioning Equipment:
I ... .The total loads are summarized in Table 26.
' .
"* -Compute the specific enthalpy of' the water difference room-air andl supply air, from Equation 19.
(184,765 + 23,550) ____
,,...
9". T
o2o3,5cc5n0
x 1076 ~ S520-,
Table 26. Summary of Total Loads--Example 11
Load Component
Sensible Btu/hr'
LatentBtu/hr
78,500 6,380 1,085 17,000
62,700 19,100.
184,765
20,700 . 205,465 -.
2'300 21,250'
.... 23,550 43,800
i 67,350 .272,815
From the Goff diagram, determine that the apparatus dew-point is 54.3 F (refer to
Chapters 3 and 43) #
>1
In computing the effective air quantity, assume a coil efficiencyi of 85 per cent.
Then,
'-
e
=
184,765 1.08 (80 - 54.3)
X
0.85
=
7850. cfm.
(Refer to Chapter 25 for coil selection and efficiency.)
From note under Equation 20 the dry-bulb range will be (80-- 54.3) X 0.85 = 21.8 deg and the dry bulb temperature of air leaving the coil will be 80 -- 21.8 = 58.2 F. The dry-bulb temperature leaving the fan (including the heat supplied by the fan motor), or delivered into the room, will be (from Equation 22):
184,765 - 19,100 80 - 19.5 = 60:5F.. 1.08 X 7850
With good distribution and diffusion, this temperature should not produce objec tionable drafts.
Example 11: Summary
Outdoor Conditions........ ........ 95 DB Space Conditions.,....................80 DB
78 WB . 0.0169 Humidity Ratio
.65 WB
0.0098 Humidity Ratio
Difference,.......... ............ 15
0.0071
-
Sensible Load Transmission '
' Btu/Hr
Roof 4000 sq ft X 53 X 0.34. =............................. -
72,000 -...
S. Wall 405 sq ft X 6" X 0.41 =..................................................
995
E. Wall 765 sq ft X 11 X 0.52 =......................................
4,380
N. Wall Ex. 170 sq ft X 3 X 0.52 =.............
- 265.- .
N. & W. Party Wall 1065 sq ft X 2 X 0.26 =..............
. 550
Floor None
Door 35 sq ft X 15 X 0.59 =........................... .............
........... 310
All Glass 160 sq ft X 15 X 1.04 =..................... ................................... 2,510 -
Solar Radiation S. Glass 60 sq ft X 0.90 X 0.74 X 42 =......................
S. Glass (Doors) 35 sq ft X 1.0 X 42 =.............................................
E. Glass (Doors) 18 sq ft X 15 =............. ....... ................ ............ ' N. Glass 30 sq ft X 15 =......... ................................................. . . . .
1,680
1,470 .
270 45Q-. ,.. '
Internal Load
'
Infiltration 67.cfm X 1-08 X.15 = .'....... ......... ............................. 1,085
Lights'(12,000 X 1.20 + '4000) 3.41 =............................. ........... 62,700
People 85 X 200 =............... ........... ......... ........................-17,000-
Motor, Fan 7.5 hp X 2544 =....................................... .............. ........ 19,100
Total Sensible Space Load. .............................. ..................
184,765