Start-up Procedure
(follow these instructions any time
a system has been shut down long enough for the Aroclor to cool
below 180F.).
Start circulation numo and check expansion tank (should be
"i/TfulD --^
----------------------------------
pj|Start burner on lowest heat and maintain full circulation until return fluid temperature reaches 180F.
0Set burner for full heat. Resume normal operation when fluid reaches proper temperature.
Shut-down Procedure (follow these instructions to prevent localized over-heating when system is being shut down).
Q Shut burner off but maintain full circulation for at least 1/2 hour to dissipate high residual heat in combustion chamber.
Qif air temperature is under 50F., keep fluid circulating constantly at 200F.
Precautions in Case of Power Failure
Power failure automatically interrupts the burner operation. When power resumes, start the circulation pump to get rid of any vapor pockets that may have formed in the heater tubes. If fluid is still hot (above 180 F.), full heat may be resumed when pipe knocking (if any) has stopped.
If returning fluid has cooled below 180F. during power failure and initial circulation, follow Start-up Procedure above.
For more details, consult Monsanto's booklet on "Aroclor 1248 Heat Transfer Data**, or contact