Document bB0omX02Yy4r5GVjMm2ywqYB0
426
Chapter 17
1954 Guide-;
temperature drop and friction loss in the flue pipe cannot be calculated^ accurately,7 and the resistance of various chimney connection^ is uncertain^ the minimum calculated heights should have a generous factor of safety applied to allow for these and other uncertainties. Where ample height' cannot be provided, forced or induced draft should be provided. Extreme care should be used in the application of forced draft to avoid producing a pressure in the combustion chambers, because they are not usually de signed to avoid the leakage of toxic gases which might result.
Induced draft by means of motor-driven fans or blowers will solve lowdraft problems, but would usually be employed for residential systems only as a last resort. Operation of a blower entails some cost, introduces main tenance requirements, and may be dangerous, in event of power failure unless suitab'e protective devices are used. Induced draft fans designed
Table 3. Drafts Required by Typical Residential Heating Devices or Appliances
Device
Draft, Inches Water
Stack Tempera ture0 F Deo
0.06 to 0.08 0.06 0.06b 0.06 0.03"
0.05* or less 0.04b 0.06b
ft Draft in firebox. ** For chestnut sized anthracite. c 18 in. from heater.
1000 860 900 860
___
400 900
.
to resist effects of high temperature and corrosion are available. Fans not carefully designed or modified to meet these conditions should not be ap
plied to this service.
CHIMNEYS FOR GAS HEATING
Since a gas-designed appliance must be able to operate at rated input
(plus 10 or 15 percent) without chimney connection, and without produc ing carbon monoxide, the only function of the chimney is to remove the
products of combustion from the room. The chimney provides draft to
overcome the friction in the flue pipe and chimney, but does not draw air
into the appliance.
Chimneys for venting appliances designed for burning gas, can therefore
be low in height, but must have adequate area. The height is usually
established by the building height. Chimney sizes are usually selected
on the basis of heat input of the appliance. The chimney sizes adopted by
the American Standards Association and the National Board of Fire Un
derwriters in 1950 for gas appliances13 are shown in Fig. 10.
'
Additional provisions of ASA Standard Z21.30-1950 relating to chimney
size are:
1. In no ease shall the vent area be less than the area of a 3-in. diameter P*P-'
2. When more than one appliance vents into a flue or vent, the flue or vent area
shall be not less than the area of the largest flue or vent connector plus...
per cent of the areas of the additional flue or vent connectors.
. .;>>
3. An elliptical flue or vent may be used provided its flue gas venting capac?.;
is equal to the capacity of the round pipe for which it is substituted.
Chimneys and Draft Calculations
427
Since Fig. 10 has been prepared for circular flues, relative capacities for rectangular and semi-elliptical flues14 are shown in Fig. 11.
Heating appliances designed to burn gas, as well as appliances converted to gas burning, except those equipped with power type burners and ex cepting conversion burner installations in excess of 400,000 Btu per hour input in large steel boilers, are always equipped with a draft hood attached to the flue outlet of the appliance. This draft hood is required if the appliance is to meet the approval requirements of the American Gas-As sociation and the American Standards Association, and is essential for safe
Fig. 10. Capacity in Btu per Hour for Gas Appliance Flues or Vents
operation. It- is designed to prevent excessive chimney draft which would ewer appliance efficiency, to prevent a blocked flue or a down-draft in the chimney from impairing combustion, to provide a relief opening for the Products of combustion during down-draft or blocked flue conditions, and o prevent spillage of the products of combustion to the space surrounding _he appliance, if there is a chimney draft equivalent to that provided by a ~jt chimney. As the draft hood is designed without moving parts, the ehef opening is always open, and consequently some air is drawn into the hiinney. This air lowers the gas temperature in the chimney, but it so lowers the dew-point of the gases and tends to prevent condensation.
'nsta^atl0n of conversion burner equipment in large boilers is UaHy made in accordance with regulations of the local gas company.