American Society of Heating and Ventilating Engineers Guide, 1937
.Table 5. Friction Heads (in Milinches) of Central Circular Diaphragm Orifices in Unions
Duheteb
Velocitt or Water at Pipe in Inches pee Second
1 8 I 10, (Inches)
32 .
4
6
12 IS 24
14-in. Pipe
0.25 0.30 0.35 0.40 0.45 0.50 0.55
1300 650 330 170
2900 1450 740 380
185
5000 2500 1300
660 330 155
75
11,300 5700 2900 1500 740 350 170
20,800 10,400
5200 2600 1300
620 300
32,000 16,000
8000 4000 2000
970 480
45.000 23,000 12,000
6800 2900 1400
700
57,000 26,000 13,000
6500 3200 1600
47,000 24,000 53.000 12,000 27.000
5700 13.000 2800 6400
1-in. Pipe
0.35 0.40 0.45 0.50 0.55 0.60 0.65
900 2000 3500 460 1000 1800 270 570 1000 160 330 580
190 330
200
120
7800 4000 2300 1400
750 440 260
14,000 7200 4100 2300 1300 800 460
22,000 12,000
6400 3700 2200 1300
720
32,000 17,000
9300 5400 3000 1800 1100
37,000 21,000 12,000
7000 4200 2400
65,000 37,000 22,000 50.000 13,000 128.000
7400 17.000 4300 10.000
0.45 0.50 0.55 0.60 0.65 0.70 0.75
1000 660 430 280 190
2250 1450 950 630 420 285 190
4000 2600 1700 1100
750 510 330
114-in. Pipe
8900 5800 3800 2500 1700 1150
750
16,000 10,400
6800 4400 3000 2000 1300
25,000 16,400 10,500
6900 4700 3100 2100
,36,000 23,000 15,000 10,000
6700 '4500 3000
53,000 34,000 22,000 15,000 10,000
6700
60,000
40,000 27,000 60,000 18,000 [40,000 12,000 26,000
0.55 0.60 0.65 0.70 0.75 0.80 0.85
850 1900 3300 600 1300 2300 400 850 1500 260 -600 1100 180 400 760
300 540
200 380
114-in. Pipe
7400 5400 3600 2600 1800 1200 860
13,000 8600 7200 4400 3000 2200 1600
21,000 16,800 10,400
7000 5000 3200 2300
30,000 21,000 14,000 10,000
7000 5000 3000
50,000 30,000 21,000 14,000 10,200
7800
53,000 39,000 28,000 19,000 45,000 13,000 30,000
S-in. Pipe
0.70
0.80
0.90 1.00 1.10 1.20 1.30
890 1850 3500 470 975 1800 255 560 1000 160 340 610
214 375
195
7400 3900 2200 1320
850 460 . 275
14,000 7400 4200 2520 1600 950 . 525
22,300 11,700
6500 4000 2500 1360
980
33,000 17,000
9500 5800 3700 1910 1375
37,000 20,500 12,500
7900 4200 3100
38,000
23,000 49,000
14,000 30,000 8100 16,800 4400 8850
Note.--The losses of head for the orifices in the 1%-ta. and 2-in. pipe were calculated from those.in the smaller pipes, the calculations being based on the assumption that, for any given velocity, the loss of bead is a function of the ratio of the diameter of the pipe to that of the orifice. This had been found to he practically true in the tests to determine the losses of head in orifices in K*in., 1-in., and I>J-in. pipe, con ducted by the Texas Engineering Experiment Station, and also in the tests to determine the losses of head in orifices in 4-in.. 6-in., and 12-in. pipe, conducted by the Engineering Experiment Station of the University of Illinois.(/iullelin 109. Table 6. p. 38. Davis and Jordan).
612
T
Chapter 33--Hot Water Heating Systems and Piping
large as those through the other radiators. The result would be that the water, in flowing through the radiator, would cool 5 F instead of 10 F. The `mean water temperature in the radiator would then be 21734 F in stead of 215 F, and the mean temperature difference, water to air, would be 14734 F instead of 145 F. The heat dissipated by the radiator would therefore be about 2 per cent more than calculated. It is evident that this difference in heat dissipation is smaller, than the difference between
Fig. 6. A One-Pipe Gravity Circulation System
Fig. 7. A Two-Pipe Direct Return Gravity Circulation System
the calculated heat losses and the actual heat losses, and also smaller than the average difference between the calculated radiator sizes and the nearest stock sizes selected.
GRAVITY CIRCULATION For gravity circulation, the one-pipe system shown in Fig. 6 and the two-pipe direct return system shown in Fig. 7 are probably in most common use. ; The one-pipe system has the disadvantage that the radiator nearest the boiler is the only one which receives water at approximately the tem perature at which it leaves the boiler. All other radiators receive cooler water and must be proportionally increased in size, so the total heating
613