Document b5LMpJRoLeZNkkwD3e9JeLnzD
310
CHAPTER 13
1953 Guide
/ The magnitude of Qn is substantially the quantity, cfm, of cooled and dehumidified l: air for which the distribution system must be designed.
i: ij> The numerical factor 1.08 is derived from the product 1 cfm X 60 inin X 0.244 X
( 0.00923\ 1-----) = 1 08> assuming an average supply air dew-point of 55 F. Since
standard air density (0.075) includes the weight of the water vapor, it is desirable to reduce it to the basis of dry air by the last factor where 0.00923' = humidity ratio of air at 55 F dew-point, and 0.62 = ratio of density of water vapor to dry air at same temperature and pressure. Refer to Chapter 36 for coil selection.
Note that the product [(space dry-bulb) -- (apparatus dew-point)] X (coil by pass factor) is equal to the dry-bulb range through which the conditioned air is cooled. Hence, in rape instances when the condition line of the process may not intersect the saturation line, any other convenient reference temperature on the condition line may be used instead, provided that the coil by-pass factor is specified accordingly on the proper basis.
MINIMUM ENTERING AIR TEMPERATURE
Due consideration must be given to the temperature of the air entering
\i the conditioned space in order to prevent objectionable drafts. With ceil
ing type diffusers or wall grilles with a high aspect ratio (see Chapter 31),
many engineers consider 20 deg as the maximum difference for good design
under average conditions. This difference can only be exceeded with ex
tremely high ceiling outlets or wall grilles. Thus, if 80 F dry-bulb is to be
.; %?
maintained in a space with average ceiling height, the minimum delivered air temperature would be limited to about 60 F dry-bulb temperature. If
the latent heat load is relatively high, it is often necessary to circulate more
air with a higher delivered dry-bulb temperature in order to produce a
thermodynamic balance. If the dry-bulb temperature of the air supplied
to the space is known, the required air quantity can be calcuated from
the formula,
Qr,
g.
1.08 (Ji - Q
' (20)
or the supply temperature U can be determined as follows,
4
t. U -
g.
1.08 X
(21)
i EXAMPLE--COOLING LOAD CALCULATION
\
An effective means of summarizing the calculation procedure will be the use of an illustrative example. While condensed calculation forms are commonly employed for work of this nature, an outline will be used here in order to facilitate explanatory comments.
Example IS: A one-story office building Fig. 6 is located in an eastern state near 40 deg latitude. The adjoining buildings on the north and west are not conditioned, and the air temperature within them is known to be substantially equal to the outdoor air temperature at any time of the day.
South wall construction: 8 in. concrete block, 4 in. brick veneer, 4 in. plaster on walls. (Table 9, Chapter 9, No. 92B, U = 0.41.)
East wall and outside north wall construction: 8 in. concrete block, painted white, I in. plaster on walls. (Table 8, Chapter 9, No. 82B, U = 0.52.)
. West wall and adjoining north party wall construction: 13 in. solid brick, no plaster:
1 -L + L8 + -2-
V 1.65 5 1.65
or,
U = 0.263. Use U*= 0.26.
Cooling Load
311
Roof construction: 2J in. flat roof deck of 2 in. gypsum fiber concrete on,gypsum board surfaced with built-up roofing. (Table 11, U = 0.34 for summer;) , .
Floor construction: 4 in. concrete on ground. Window: 3 ft x 5 ft, non-opening type, with medium colored Venetian blinds for windows on south wall. Approximately 4 in. reveal on all windows.
Front doors: Two 2 ft-6 in. x 7 ft (glass panels). Side doors: Two 2 ft-6 in. x 7 ft (1 glass panels).
Rear doors: Two 2 ft-6 in. x 7 ft (wood panels). Outside design conditions: Maximum dry-bulb 95 F, wet-bulb 78 F; Wo = 0.0169 lbs vapor per lb dry air; ho = 41.38 Btu per lb dry air. Indoor design conditions: Dry-bulb 80 F, wet-bulb 65 F; Wi = 0.0098 lb vapor per lb dry air; Ai = 29.95 Btu per lb dry air.
Occupancy: 85 office workers. Lights: 12,000 watts, fluorescent; 4000 watts tungsten.
Fan motor: 7f hp.
V
Fio. 6. Plan op One-Stoby Office Building
Assume that cooling coil has a by-pass factor of 0.15, i.c., that 15 percent of the air passes through the coil without contacting the coil surface.
Conditioning equipment to be located in adjoining structure to north. Find: Total, sensible, and latent maximum cooling loads and required air quantity through conditioning equipment. Solution: From Table 3, the recommended ventilation rate is 15 cfm per person. Total necessary = 85 X 15 = 1275 cfm or 76,500 cu ft per hr. As the room volume is 40,000 cu ft, the air changes per hour will be 76,500/40,000 = 1.91 which is more than one air change.
Estimated Time of Maximum Cooling Load:
For this job, judgment indicates that the roof will make the greatest single con tribution to the cooling load. Hence, the time of maximum cooling load probably will be the time of maximum heat gain through the roof. From Table 9 the maxi mum temperature differential for a 2 in. gypsum roof of medium weight construction is 54 deg at 4:00 p.m., and 53 deg at 3:00 p.m. Examination of Table 13 (40 deg N Latitude) shows that solar heat gain through glass on the south wall is 18* Btu per (hr) (sq ft) at 4:00 p.m., and 42 Btu at 3:00 p.m. This indicates that the maximum cooling load occurs at approximately 3:00 p.m. Therefore make load calculations at 3:00 p.m. sun time. (This may be slightly different from 3:00 p.m. local time.)