Document b52MbN1vGr78kZ8DpLbVeNxrg
Intra-Company Communication
Ihy 22, 1961
Mr. 3* Vanasnt Safety Engineer Tpeilanti Plant
Bt: Air-bome Particulate Matter - Solvent Vapor* - Mixing Hoorn tor the Heater Core Operation - Ipsilantl Plant
The writer took eaaples of air-borne particulate setter and toluene solvent vapor at the above ad ring roan. the zaaults vena aa follows:
location
Sisal conveyer Clay hopper Calclw hopper Mix tank
Air-borne Particulate Matter
8olvent Vest
Besuits to MPPCT*
$.$ 5.2 1.7 1.3
location
Gunk cutoff Ejection end of extruder
Results In Fftt--
0-70 $32
MPPCF Million particles per cubic foot of air.
PPM a parts of solvent vapor per Billion parts of air.
fbe asixiawn allowable oonoentratlona for the air-borne particulate mtter and toluene solvent vapors are $0 aqppef and 200 ppau these auxlaat are based on an eight hour day continuous exposure.
the results obtained Indicate that no excessive concentration* art present at this tine.
J. C. Stadcllffe, Supervisor
industrial Safety Section
hyi C. X. Masters Mb
OTA
HFM -014454
5007 C1P5
' PRODUCED BY FORD
SCF-FORD-0325