INSTRUMENT FUNCTION OUTLINE
#1 Absorber Steam Tracing
TITLE Temperature Control
____
DEPARTMENT246
.
. '
LOOP NUMBER036
SHEET
. 4 OF
4
CLASSIFICATION TIC-36
WRITTEN BY 'DATE ~ " '_____________ REV, BY
__ .DATE "------ REVTN07
3.0 OPERATION OF THE LOOP
'
"' ' .
3.1 NORMAL OPERATION
:
.
.
Activate steam heating system for absorber and set control
point at a temperature corresponding to the surge tank .
temperature.
.
.
3*1*1 Start Up Instructions
' A. Open Manual valves in steam line to absorber
.
B. Check air pressures to controller and control
. valves
.
.
.
C, Set controller as per Instructions
3*1*2 Shut Down Instructions
A. Close manual valves in steam line B. Set controller to lowest point.
3*1.3 Manual Control
:
.
.
. None
'
'
3.2. INTERLOCK .
. -
.
There are no interlocks in this system.
.
3.3 ABNORMAL OPERATIONS
.
'
-
3*3*1 Air Failure
Air.failure to this loop will cause loss of temperature control due`to the control valve closing.
3*3*2 Power Failure
Power failure to this loop will have no effect on this loop,
'r% t \
\itB R
M
13
1If4~*TM \h A t[i
fl
%!/ fijf
L2VZZ
f o. ,
A/ /
/ ' 1) .1 / \ t
/
^ HilWioh'
I
1
j;'LhpMACjLJLrs
s i J .-*** & / . s t ( }/ &~) f.s/f
V
///Wk?
/ _ .f , i'SA/(Sf? '
PCB-ARCH-EXT0374009
INSTRUMENT FUNCTION OUTLINE
DEPARTMENT_________ ____________
, #2~ and #3 Absorters Inlet
TITLE-' Flow Control & AlarmLOOP NUMBER
032
SHEET
1 OF
4 '
WRITTEN BY^. DATE 6/69 REV, BY
CLASSIFICATION ' _ DATE REV. NO,
PICA-32
1.0 NEED FOR LOOP
This loop is needed to insure proper flow of g,roclor to
the absorber.
.
1.1 DESCRIPTION OF LOOP
.
. .
1.1.1 Function
. .
The function of this loop is to control the flow
of material into the absorbers and to sound an
alarm, if flow is too low.
:
1.1.2 System Performance Required
.
'
. The flow rate should be maintained + \ GPM of set.
point.
1.1-3 Accomplishment of Function
'
'
. ' . .
The flow rate is sensed by a flow transmitter with integral orifice plate. The transmitter sends a 3-15 psig air signa.l to a flow indicating controller. The controller compares this signal to a set point and sends a 3 - 15 psig air signal to a control valve to compensate for variation from set point. The transmitter also sends an air'signal to a pressure switch which activates an alarm on low flow.
PCB-ARCH-EXT0374010
INSTRUMENT FUNCTION OUTLINE
-- fTPTfliiM |W
TtMl >
II *
^ . I< '^^1 -- ,"*'* 1 ' --
--
TITLE#2 and #3 Absorbers Inlet Flow Contro1
SHEET
2 OF
4
i,
& Alarm
DEPARTMENT LOOP NUMBER CLASSIFICATION
2 46 032
2.0
COMPONENT AND CALIBRATION DATA
OPERATING DATA
MECHANICAL DATA
A. FT-32 Differential Press. TranS.
Supply: 20 psig Output: 3-15 psig Flow: 0-10 GPM Span: 0 - 400" W.C. Location: l4' Levels NE of
. Tank 530
B. FIC-32 Flow Indicating Controller
Input: 3-15 psig Output: 3-15 psig Action: Inc. Input
Dec. Output Supply: 20 psig Location: Panel
C. FV-32 Control Valve
Input: 3 - 15 psig Action: Air to open
Fails Close Location: l4' levels, NE of
Tank 530
D. FSA-32 Pressure Switch
Input: 3 - 15 Psig Set Point: 33% FCT: Lo Flow alarm at 3*3 0PM SPDT contact/115 V., 10A Location: Panel
A. Foxhoro Integral Orifice Diff. Press. Trans. W/Piped & Mt'd. Air Set W/Gage_______________
Model #: 13A-HS2
-
Range: 0 - 200 to 0 - 850" W.C.
Calibrated range 0 - 400" W.C.
316 SS Body
Process Conn: j?" NPT
Orifice: .350" Bore
316 S.S.
Accuracy: \a/o
.
.
Serial #: IPMO:
1947915 001
.
B. Fischer & Porter Flow Ind. Controller
Model#: 51-1351 ABEC
Range: 3-15 psig sq.ft.
Scale: 0 - 100 sq. rt.
Prop._ Band: 2 - 500/
Reset Rate: .02 to 5 min.
Accuracy: -|/
IMO:
IPMO:
165
C. Fisher Gov. Control Valve #66?-BF
Actuator Size 30 Travel 3/4"
1" 150# Fig. 316 SS Body
Packing Set 1U2546-0101
.
3/4" 315 SS Trim^ Micro-Flute
Valve Plug 2J7335-3507
Valve Ring 1R1262-3507
Teflon Packing, Skirt-Top Guiding
Spare valve S.C. 07-75671
IMO: '
45
IPMO: 126
Serial: 4435034
D. Barksdale Pressure Switch #DIT-Hl8
Range: 0 - 18 psig
Bronze Diaphragm,
IPS
Conduit Conn:
NPS
Setting trips at 4.08# on drop
Stores Code: 44-73246
PCB-ARCH-EXT0374011
PCB-ARCH-EXT0374012
INSTRUMENT FUNCTION OUTLINE -~.jj-2 'and #3 Absorbers Inlet
TITLE Flow Control & Alarm
DEPARTMENT
246
LOOP NUMBER
032
SHEET
4
WRITTEN BY
OF
4
DATE
CLASSIFICATION FICA-32
REV.BY
. DATE '
REV. NO.
3.0 OPERATION OF LOOP
.
`
'.' .
3.1 NORMAL OPERATION
.
.
,
. Set the flow control to absorbers to correspond to the flow
' . from the still condensers. Normally this will be 4 to 6 .
gallons per minute.
'
/
Note: Scale of the flov,r indicator is 0 to 100. A reading of 100 is equal to 10 Gal. per minute.
3.1.1 .Start Up Instructions
. .
A. Align manual valves from surge tank to absorbers.
B. Check all air supply pressures.
C. Align valves from absorber *to filter and return
to surge tank.
.
.
D. Start transfer pump.
' E. Adjust flow controller to. correspond with
'
Operating Instructions. If there is no flow.
an alarm will sounds or if flow drops below
3-3 GPM.
'
3.1.2 Shut Down Instructions
.
'
.
A. Close manual valves. - .
B. Shut off feed transfer pump to absorbers.
3-1.3 Manual Operations
.
.
A. Place flow controller on "Manual" and regulate
air pressure to control valve to achieve desired
flow rate.
3.2 =INTERLOCKS
i $ | IsTM \ L iwy iEl a --
There are no interlocks in this system.
hi
%s U w
3.3
ABNORMAL OPERATIONS 3-3-1 Air Failure
Y/b a-
u
e \
/AV!
Air failure to this loop will cause loss of flow, due to the control valve closing, and
3.3.2 Power Failure
r 4$
Power failure to this loop and flow if failure is to feed pump.