Document b522RjxBXnpkmB3pEbzw8E64Z

INSTRUMENT FUNCTION OUTLINE #1 Absorber Steam Tracing TITLE Temperature Control ____ DEPARTMENT246 . . ' LOOP NUMBER036 SHEET . 4 OF 4 CLASSIFICATION TIC-36 WRITTEN BY 'DATE ~ " '_____________ REV, BY __ .DATE "------ REVTN07 3.0 OPERATION OF THE LOOP ' "' ' . 3.1 NORMAL OPERATION : . . Activate steam heating system for absorber and set control point at a temperature corresponding to the surge tank . temperature. . . 3*1*1 Start Up Instructions ' A. Open Manual valves in steam line to absorber . B. Check air pressures to controller and control . valves . . . C, Set controller as per Instructions 3*1*2 Shut Down Instructions A. Close manual valves in steam line B. Set controller to lowest point. 3*1.3 Manual Control : . . . None ' ' 3.2. INTERLOCK . . - . There are no interlocks in this system. . 3.3 ABNORMAL OPERATIONS . ' - 3*3*1 Air Failure Air.failure to this loop will cause loss of temperature control due`to the control valve closing. 3*3*2 Power Failure Power failure to this loop will have no effect on this loop, 'r% t \ \itB R M 13 1If4~*TM \h A t[i fl %!/ fijf L2VZZ f o. , A/ / / ' 1) .1 / \ t / ^ HilWioh' I 1 j;'LhpMACjLJLrs s i J .-*** & / . s t ( }/ &~) f.s/f V ///Wk? / _ .f , i'SA/(Sf? ' PCB-ARCH-EXT0374009 INSTRUMENT FUNCTION OUTLINE DEPARTMENT_________ ____________ , #2~ and #3 Absorters Inlet TITLE-' Flow Control & AlarmLOOP NUMBER 032 SHEET 1 OF 4 ' WRITTEN BY^. DATE 6/69 REV, BY CLASSIFICATION ' _ DATE REV. NO, PICA-32 1.0 NEED FOR LOOP This loop is needed to insure proper flow of g,roclor to the absorber. . 1.1 DESCRIPTION OF LOOP . . . 1.1.1 Function . . The function of this loop is to control the flow of material into the absorbers and to sound an alarm, if flow is too low. : 1.1.2 System Performance Required . ' . The flow rate should be maintained + \ GPM of set. point. 1.1-3 Accomplishment of Function ' ' . ' . . The flow rate is sensed by a flow transmitter with integral orifice plate. The transmitter sends a 3-15 psig air signa.l to a flow indicating controller. The controller compares this signal to a set point and sends a 3 - 15 psig air signal to a control valve to compensate for variation from set point. The transmitter also sends an air'signal to a pressure switch which activates an alarm on low flow. PCB-ARCH-EXT0374010 INSTRUMENT FUNCTION OUTLINE -- fTPTfliiM |W TtMl > II * ^ . I< '^^1 -- ,"*'* 1 ' -- -- TITLE#2 and #3 Absorbers Inlet Flow Contro1 SHEET 2 OF 4 i, & Alarm DEPARTMENT LOOP NUMBER CLASSIFICATION 2 46 032 2.0 COMPONENT AND CALIBRATION DATA OPERATING DATA MECHANICAL DATA A. FT-32 Differential Press. TranS. Supply: 20 psig Output: 3-15 psig Flow: 0-10 GPM Span: 0 - 400" W.C. Location: l4' Levels NE of . Tank 530 B. FIC-32 Flow Indicating Controller Input: 3-15 psig Output: 3-15 psig Action: Inc. Input Dec. Output Supply: 20 psig Location: Panel C. FV-32 Control Valve Input: 3 - 15 psig Action: Air to open Fails Close Location: l4' levels, NE of Tank 530 D. FSA-32 Pressure Switch Input: 3 - 15 Psig Set Point: 33% FCT: Lo Flow alarm at 3*3 0PM SPDT contact/115 V., 10A Location: Panel A. Foxhoro Integral Orifice Diff. Press. Trans. W/Piped & Mt'd. Air Set W/Gage_______________ Model #: 13A-HS2 - Range: 0 - 200 to 0 - 850" W.C. Calibrated range 0 - 400" W.C. 316 SS Body Process Conn: j?" NPT Orifice: .350" Bore 316 S.S. Accuracy: \a/o . . Serial #: IPMO: 1947915 001 . B. Fischer & Porter Flow Ind. Controller Model#: 51-1351 ABEC Range: 3-15 psig sq.ft. Scale: 0 - 100 sq. rt. Prop._ Band: 2 - 500/ Reset Rate: .02 to 5 min. Accuracy: -|/ IMO: IPMO: 165 C. Fisher Gov. Control Valve #66?-BF Actuator Size 30 Travel 3/4" 1" 150# Fig. 316 SS Body Packing Set 1U2546-0101 . 3/4" 315 SS Trim^ Micro-Flute Valve Plug 2J7335-3507 Valve Ring 1R1262-3507 Teflon Packing, Skirt-Top Guiding Spare valve S.C. 07-75671 IMO: ' 45 IPMO: 126 Serial: 4435034 D. Barksdale Pressure Switch #DIT-Hl8 Range: 0 - 18 psig Bronze Diaphragm, IPS Conduit Conn: NPS Setting trips at 4.08# on drop Stores Code: 44-73246 PCB-ARCH-EXT0374011 PCB-ARCH-EXT0374012 INSTRUMENT FUNCTION OUTLINE -~.jj-2 'and #3 Absorbers Inlet TITLE Flow Control & Alarm DEPARTMENT 246 LOOP NUMBER 032 SHEET 4 WRITTEN BY OF 4 DATE CLASSIFICATION FICA-32 REV.BY . DATE ' REV. NO. 3.0 OPERATION OF LOOP . ` '.' . 3.1 NORMAL OPERATION . . , . Set the flow control to absorbers to correspond to the flow ' . from the still condensers. Normally this will be 4 to 6 . gallons per minute. ' / Note: Scale of the flov,r indicator is 0 to 100. A reading of 100 is equal to 10 Gal. per minute. 3.1.1 .Start Up Instructions . . A. Align manual valves from surge tank to absorbers. B. Check all air supply pressures. C. Align valves from absorber *to filter and return to surge tank. . . D. Start transfer pump. ' E. Adjust flow controller to. correspond with ' Operating Instructions. If there is no flow. an alarm will sounds or if flow drops below 3-3 GPM. ' 3.1.2 Shut Down Instructions . ' . A. Close manual valves. - . B. Shut off feed transfer pump to absorbers. 3-1.3 Manual Operations . . A. Place flow controller on "Manual" and regulate air pressure to control valve to achieve desired flow rate. 3.2 =INTERLOCKS i $ | IsTM \ L iwy iEl a -- There are no interlocks in this system. hi %s U w 3.3 ABNORMAL OPERATIONS 3-3-1 Air Failure Y/b a- u e \ /AV! Air failure to this loop will cause loss of flow, due to the control valve closing, and 3.3.2 Power Failure r 4$ Power failure to this loop and flow if failure is to feed pump. PCB-ARCH-EXT0374013