Document b51mq4Qk08zx0yNRaxpmNMqR0
984
CHAPTER 39
1957 Guide
winding circuit. The relay then keeps these contacts open because there is sufficient voltage induced in the starting winding, when the motor is running, to hold the relay in the open contact position.
CONTROL-FOR ALTERNATING CURRENT MOTORS
Squirrel-Cage motors are usually linestarted where power company limitations permit. In sizes up to 5 hp at 220 volts, or hp at 440 volts, polyphase motors may be started by means of manual switches having overload current elements for motor protection. In larger ratings a linestarter is usually provided with either an additional safety switch or circuit breaker for disconnecting and short circuit protection. Reduced voltage starting may be used when the current inrush on full voltage ex ceeds the limitations set by the power company. The magnitude of this inrush current is entirely independent of the load on the motor, and is the same whether the motor is lightly loaded or heavily loaded.
Table 7. Compabison op Squirrel Cage and Synchronous Motor Starting Methods
Type op Starter
Full Voltage Starter
Percent of Motor Rated Values
line Voltage
Starting Torque
Line Current
100 100 100
Autotrahsformer 80 percent tap 65 percent tap 50 percent tap
Resistor, single step
80 64 68 65 42 46
50 25 30
80
64 ,
80
Reactor SO percent' tap 45 percent tap 37.5 percent tap
Part Winding
50 45 37.5
60
25 20 14
50
50 45 37.5
60
Restrictions on starting current may limit the maximum current inrush
or may limit the increments of current inrush which may be drawn on
each step. Table 7 shows a comparison of the various methods of reduced
voltage starting. The choice may depend upon the limitation to be met.
Fig. 5 shows examples for maximum current limitations. Fig. 6 shows
examples for increment limitations. The increment starters would not be
satisfactory" for meeting maximum current limitations as they exceed the
maiitnnm value before the motor reaches full speed. Both Curves B and
C of Fig. 6 would be satisfactory if the increment limitation were 400 per
cent but only the starter illustrated by Curve C would meet a limitation
of 200 percent increments.
,
When increment starters are used the motor may not develop enougn
torque to start until the last step. Fig. 6 shows that with the resistor step
starter the motor does not start until step 3 or after 2 seconds on Curve O.
Part-winding motors may start and then stall at about half speed unti
the second step which applies full torque.
: The load inertia (WK!) may also affect the selection of reduced current
starting method since the reduced torques may not be sufficient to accel
erate the load without overheating the motor or in the case of synchronous
motors, may not reach sufficient speed to pull into synchronous speed.
Motors and Motor Controls
985
CubvbA Full Voltage
Stabteb
Cubvb B Reactor 60 Percent Tap
Cubvb C Aut otranbfobmeb
65 Percent Tap
0
Fig. 5.
12 3 4 5 0 TIME ---- ; SECONDS
Starters for Maximum Current Limitations
In these cases the solution may be to use the wound-rotor induction motor or some means of reducing the load such as suction dampers on compres sors. Fig. 7 illustrates recommended control practice for squirrel-cage motors.
Wound Rotor motors require control of both primary and secondary circuits. The primary* control may be the same as for squirrel-cage motors, manual or magnetic, at full voltage. Secondary* control pro vides means of varying secondary resistance for starting and speed control. The secondary controller should be specified for starting duty only, or for speed regulating duty. If the secondary controller is to be used for speed regulating duty, the percent speed reduction, the number of speed control points, and the type of load (variable or constant torque) should be speci fied. Fig. 8 illustrates recommended control practice for wound rotor motors.
Synchronous motor starters should provide pull-out protection, auto matic synchronization or automatic stopping of the motor after pull-out, and insurance of complete starting sequence, as well as overload and low voltage protection. The control may be either magnetic or semi-magnetic at full or reduced voltage. Semi-magnetic starters provide automatic field control, but require hand operation for closing the line contactors to start and transfer to full voltage.
Curve A Full Voltage
Stabteb Curve B Part Winding Stabteb Curve C 4-Step Resisteb Increment Stabteb
TIME --SECONOS
Fig. 6. Starters for Increment Limitations
Refer to Glossary at end of chapter.