square *heat type
^series
12 sizes--243,000 to 1,350,000 Btuh
mm'H
i'*
versatility . ability
to burn any fuel... ability to deliver effi ciently far beyond rated capacity... makes this boiler ideal for any medium size building. Kewanee Type R Boilers are giving economical, trouble-free service in thousands of office and store buildings, schools, motels, hospitals, small factories, etc.
It operates at top efficiency with oil, gas, or coal. Coal may be hand or stoker fired. Change from one fuel to another, or from mechanical to hand firing, or back again, can be made quickly, inexpensively.
Teamed with radiant baseboards, wall, floor or ceiling coils or panels, convectors or conventional radiators, Kewanee Square Heat Type R provides a sturdy steel heart for the system. It can be pushed far beyond rated capacity yet operate at full efficiency.
The result of nearly a century of experience, this boiler offers the medium size building all the heating dependability and economy for which Kewanee Boilers have always been famous.
A.S.M.E. and S.B.I. Code requirements have been followed to the last detail. But more than that, Kewanee guarantees per formance well beyond any code requirements.
three pass design
Kewanee 3 pass design assures maximum heat transfer from fuel to water. The large firebox provides complete mixing of fuel and air. Combustion is complete--all fuel burns-before the hot gases enter the fire tubes. In the first pass gases travel from front to rear in the firebox. The second pass is from rear to front in the bottom bank or direct tubes. The third pass is from front to rear in the return tubes. This longer gas travel transfers maximum BTU's to water.
Copyright 1961 by American Radiator & Standard Sanitary Corporation
2
28508
take a
at a
Note these features.
The husky shell tells of extra sturdiness, insideyou see the many features that pack so much efficiency into compar atively small space.
At every level of rated capac ity ... even at loads far above nominal ratings . . . Kewanee Square Heat Type R operates at full efficiency.
Hydrostatically tested at 60 psi, it operates up to 15 psi steam or 30 psi hot water.
The smoke hood has two cleanout openings and a cir cular rear outlet that fits standard size smoke pipe.
Coil opening provides for in stallation of either tank type or instantaneous water heat ing coil.
Steel flue access cover with insulation securely keyed in place. (Stoker and hand fired boilers have cast iron flue doors and frames).
Spinner blades in oil-gas boilers 3R1 to 3R8 inclusive . . . swirl hot gases against tube walls assuring maximum heat transfer.
Shell is extra heavy, quality steel plate for strength and dependability.
Insulated cast iron fire door. Stoker and hand fired boilers have cast iron fire doors with liners and door slides for sec ondary a ir.
Cleanout openings with hollow brass plugs and rubber gaskets located at each corner.
150 lb. American Standard flange on Nos. 3R9 thru 3R12.
High and abundant steam space assures ample reserve of dry steam.
Disengaging area at the water surface is unbroken, and large enough to prevent prim ing.
Longer gas travel through two passes of heavy gauge tubes is a plus value in secondary heating surface that assures greater fuel savings.
Optional--wrap-around steel jacket with mineral fiber in sulation.
Rapid circulation m wide, free waterways sweeps steam bubbles up without turbu lence to the unbroken disen gaging area at the water line.
Large, high firebox provides plenty of space for complete, economical combustion.
Exceptionally sturdy steel base is reversible for front or rear firing.
Crown sheet arched upward affords greater height for bet ter combustion. Also it is self draining and cleaning.
$
REAR VIEW SHOWING
SMOKE OUTLET AND
OBSERVATION OPENING
Round rear smoke outlet, in standard pipe size, provided tor ease in making breeching connection. (Top outlet optional.) Cleanout furnished on side of smoke hood.
Two inch capped tube welded in rear water leg to provide observation opening. A oneeighth inch plugged opening is located in the tube for draft gauge connection.
FRONT VIEW
SHOWING DOORS
FOR STOKER
OR HAND FIRING
Designed for top efficiency when stoker or hand fired. Type R Boilers for solid fuel firing are provided with a cast iron, iatchtype flue door... cast iron fire door with liner and secondary air slides.
28509
3
square *heat type
series
.-rs rs-vy " - -in*, o!';'
red-
CJ s 0 ? stokH-;
BOILER NUMBER
SBI Net Rating--Steam Steam or Water
Sq. Ft. MBtuh
Gross Output
MBtuh
*Firing Rate--Oil. . --Gas. --Stoker
Gph MBtuh Lb. per hr.
Heating Surface (SBI min)
Sq. Ft.
Furnace Volume (SBI min)
Cu. Ft.
Firebox Volume above Mudring
Cu. Ft.
Safety Valve Capacity Lb. Steam per hr.
3R1 3R2
1010 U240 243 297
324 396
2.9
405 3b
3.5 495
44
53 8.2 8.8
324
65 10.0 10.4 396
3R3
1460 351
468
4.2 585
52
77 11.8 12.0 468
3R4
1690 405
540
4.8 675
60
88 13.6 13.5 540
3R5
2020 486
648
5.8 810
72
106 16.4 17.2
648
3R6
2480 594
792
7.1 990
88
129 20.0 20.1 792
Firing rates calculated to develop gross outpul based on 140,000 Btu Oil; 12,000 Btu Coal.
3R7
2930 702
936
8.4 1170 104
153 23.6 23.0 936
3R8
3380 810
1080
9.6 1350 120
177 27.3 26.3 1080
3R9
3940 945
1260
11.2 1575
140
206 31.8 32 6
1260
3R10
4500 1080
1440
12 9 1800
160
236 36 3 37 n
1440
3R11
SOfiO 1215
1620
14 5 2025
180
266 40 Q 41 i 1620
3RX2
1350 1800
1* 1 2250 266
1800
it M'vi,"7 H;-i Oft /\
^ >el,.'S
BOILER NUMBER
A --Boiler Width Overall B --Boiler Length . . C --Boiler Height
D --Boiler Length Overall
E --Water Line Height
F --Steam or Water Supply Height G --Smoke Outlet Height H --Steam or Water Supply J --Floor to bottom of smokebox K --Coil Connection Height
L --Firebox --Length
M--
--Width
N--
--Height
P --Opened Firedoor to Boiler
Q --Floor to bottom of Firedoor
R --Return Height
S --Smoke Outlet Diameter
T --Steam Supply Size U -- Return Size
V --Smokebox Depth--Front .
W--
--Rear
AA --Base--Width
BB--
--Length
CC--Tube Replacement Space Front & Rear
Chimney--Diameter -- Height
Ft.
Outside Surface to Cover
Sq. Ft.
Approximate Weight. Unjacketed
Lb
3R1
30% 30% 65% 48% 55 %
66% 48 10 34% 57%
25% 24 21% 21% 19% 17%
12
4 3
8 8
32% 34%
31%
10 30
38 1500
3R2
30% 36% 65% 54% 55%
66% 48 12 34% 57%
31% 24 21% 21% 19% 17%
12
4 3
8 8
32% 40%
37%
11 35
43 1650
3R3
30% 42% 65% 60% 55%
66% 48 14 34% 57%
37% 24 21% 21% 19% 17%
12
4 3
8 8
32% 46%
43%
12 35
48 1800
3R4
30% 48% 65% 66% 55%
66% 48 16 34% 57%
43% 24 21% 21% 19% 17%
12
4 3
8 8
32% 52%
49%
12 40
53 1950
3R5 3R6 3R7
35 42% 73 61% 62%
35 50% 73 69% 62%
35 58 73 77 62%
73% 54 14 39 64% 1
73% 54 17
39 64%
73% 54 19 39
64%
37% 28 26 21% 21 18 .
15 ;
45 28 26 . 21% 21 18
15
53 28 26 21% 21 18
15
444 444
91 9! 9 8 88
36% 46%
36%, 36% 54% 62
43% 51% 59
13 14 15 35 40 40
58 . '65
73
2250 2475 2725
3R8 3R9 3R10 3R11 3R12 i
35 67
73 86 62%
41l/2 56% 82 77% 70%
41% 64 y2 82 85l/2 70%
411/2 41 V->' 72 " 791/21 82 g? 93 iooy2: 70% 70%
73% 1 54 1 22 j 39 i 64% '
62 28 26
21% 21
18 ,
15
86 60 16 44y2 72%
51 35 31 27 21% 18 ,
18
86 60 18 441/2 72%
59 35 31 27 2IV2 18
18
86 60 20 441/2 I 72% !
66 35 1 31 ' 27 2iy2 18 :
18
86 fin
441/-. 72%
74 35 i 31 ! 27 ! 2iy/ 18 ;
18
4 6** 6** 6** 6** 44444
9 : 10
10
8 9, 9
10 i 10 99
36% 71
44 44 44 , 44
60 : 68
75% 83
68 57 65 73 80 .
16 16 17 18 18 45 35 40 45 50
82 3000
82 3375
90 3650
99 3850
107 4200
*150 Lb. American Standard Flange. Eight % in. bolts. 9V2 m. bolt circle 'For other base heights add to vertical dimensions F, K, J, E, Q, R and G.
Bases of 20. 24 and 30 in height available for mechanical firing at additional cost
28510
ALL 3R SERIES BOILERS
1. 14" high steel base
1. Extra base heights--20", 24" and 30"
2. Rear smokebox with circular rear outlet
2. Wrap-around insulating jacket
3. Rear observation opening
3. Water heating coils
4. Flue cleaner with handle
4. Water heater tappings
5. Washout plugs
5. Wing induced draft fan
6. Washout plug wrench
6. Rear smokebox with top outlet
OIL AND GAS FIRED BOILERS
1. Steel access flue cover with insulation
2. Cast iron firedoor with insulation
3. Spinner blades for 3R1 thru 3R7-- Direct tubes only for 3R8
STOKER AND HAND FIRED BOILERS
1. Cast iron flue door with insulation 2. Cast iron firedoor witlT liner and slides 3. Shaking grates and ash door (hand fired only)
1. Safety valve
2. Compound steam and vacuum gauge 3. Water gauge and glass
STEAM BOILERS
1. n0. 767MM low water cut off
1. Relief valve(s) 2. Combination altitude gauge and thermometer
WATER BOILERS
1. No. 63BMM low water cut off
The contactor shall furnish and install
No. 3R
Kewanee Square-Heat Type R Boilers) for roil) (gas) fstoker)
(hand fired ) firing. Boiler(s) shall contain not less than
sq. ft. of heating surface and have a net SBI rating of.
sq. ft. Not less than
cu. ft. firebox volume above mud ring.
Boiler shall be of three pass firebox design and constructed in accordance with the A.S.M.E. Code for (15 lb. steam; (30 lb. water). Boiler shall be inspected during construction by-an authorized inspector and after completion shall be subjected to a 60 lb. hydrostatic test and stamped with all identifying markings and symbols as required by the latest edition of the A.S.M.E. Code.
Boiler to be furnished with
in. high steel base. Front
flue access cover with refractory securely keyed in place and of
size permitting easy access to all firetubes. Rear smokebox
shall have a cleanout opening on the side and be provided with a circular rear outlet. Observation opening to be provided in rear of boiler.
Boiler trimmings shall consist of the following:
For steam: Safety valve, compound steam and vac uum gauge, water gauge glass assembly.
For water: Relief valvets) as required by A.S.M.E. Code for low pressure boilers, combina tion altitude gauge and thermometer.
Optional: Boiler to be provided with wrap-around steel jacket with 1" mineral fiber insulation. Jacket designed so as to permit either installation or removal without disconnecting supply or return piping.
28511
5
SQUAREHEAT BOILERS --horizontal right or left discharge (dimensions in inches)
BOILER NUMBER
3R1 3R2
Inducer Number* Oil or Gas Boiler
Stoker Boiler Fan Motor Size
--60 Cycle--1 Phase 110V 110/220V .
.
lODI-'/s lODI-'/s lODI-'/e lODI-'/s
. hp hp
Ye
Ve
A--Outlet Size
...
B--Bottom Boiler to Center of Outlet.
C--Boiler Head to Center of Outlet .
D--Overall Space Requirement.
E--Barometric Damper.
..
10 Dia. 32 y2 16 24 9%
10 Oia. 32`/2 16 24 9%
F--Boiler CL to Outlet.................................
G--Boiler CL to Motor End
............
H--Fan Removal Clearance ....................
9% 15%
14
9% 15 %
14
3R3
lODI-% lODI-%
Ye
10 Dia. 32>/2 16 24 9%
9% 15%
14
3R4
lODI-'/e lODI-%
Ye
10 Dia. 32% 16 24 9% 9% 15% 14
3R5
lODI-'/e lODI-%
a
10 Dia. 37% 16 24 9%
9% 15%
14
3R6
lODI-% lODI-'/s
Ye
10 Dia. 37% 16 24 9%
9% 15%
14
3R7
10DI-`/6 IODI.%
Ye
10 Dia. 37% 16 24 9%
9% 15%
14
3R8
3R9 3R10
14DL-y4 14DL-*4 140L-% i4D-y4 14D-1/4 UD-Va
'A
14 37% 20% 31% 9
10% 23 19%
'A
14 44 21% 32% 9
10% 23 19%
1A
14 44 21% 32% 9
10% 23 19%
3R11
14D-!4 14D-%
'A 14 44 21% 32% 9 10% 23 19%
3R12
14D-% i4D-y4
% 14 44 21% 32% 9
10% 23 19%
horizontal right or left discharge
T 'O A
i-;'' A
Wing Draft Inducers for Kewanee Square-Heat Type "R" boilers provide precise draft control... eliminate need for tall stacks. Air Cooled Bearings--pre-sealed and pre-lubricated require no lubrication. Spring Mounted Motor--dustproof, multispeed, brushless . . . maintains correct fan belt tension. Note: 10 DI-V6 fan is equipped with constant speed motor and adjustable pitch sheave for speed regulation--no spring loaded base. Permanent Mounting--furnished for either hori zontal right or left, or vertical discharge as specified. Barometric dampers at extra cost.
Inducers listed are based on sea level elevation, sized for firing up to and including 141.5% of SBI rating with oil, gas or stoker. Controls other than multispeed controller, not furnished as standard equipment. Orders must specify operating line voltage, cycle and phase. Stack and breeching weights must be supported in dependently.
vertical dischargemounted on smokebox
SQUARE*HEAT BOILERS--vertical discharge (dimensions in inches)
BOILER NUMBER
3R1
3R2
3R3
3R4
3RS
3R6
3R7
3R8
3R9 3R10 3R11 3R12
Inducer Number* Oil or Gas Boiler Stoker Boiler
Fan Motor Size
--60 Cycle 110V 110/220V
lODI-'/s 10DI-% lODI-'/s lODI-'/s lODI-% 10DI-'/6 lODI-% 14DL-y4 14DL-% 14DL-y4 i4D-yd 14D- % 10DI-Ye lODL-'/e lODL-% lODL-'/s 10DL`/s 10DL-% 10DL-`/6 14D-y4 14D->/4 14D-% 14D-% i4D-yd
hp Vs Ye Ye Ye Ye Ye Ye hp % `A Va `A 'A
A--Outlet Size B -- 8ottom Boiler to Outlet C--Boiler Head to Center of Outlet D--Overall Space Requirement E--Barometric Damper
10 Dia.
41% 16 24 9>/2
10 Dia.
41% 16 24
9%
10 Dia.
41% 16 24 9%
10 Dia. 41% 16 24
9%
10 Dia. 46% 16 24
9%
10 Dia. 46% 16 24
9%
10 Dia. 46% 16 24
9'/2
14 48 20 y? 31% 9
14 54%
21% 32%
9
14 54%
21% 32%
9
14 54%
2 V/2 32%
9
14 54%
21% 32%
9
Fan sizes based on sea level elevation for firing up to and including gross output rating with oil, gas or stoker.
28512
6
square'heat type
coil selection chart
FAMILIES OR BATHS
40 to 140F BW 180aF Gal|'n>n'' 40 to 140F BW 212"F
..
40 to 180F BW 210F
Inlet & Outlet Diameter--Inches Overall Length--Inches
3R1, 3R2. ... 3R3 ... 3R4 3R5 . . 3R6. . . 3R7 3R8 3R9 3R10. . 3R11 3R12
'2 3 ;4
: 60 90 : 120
100 150 200
48 j 72 > 96
` KT- ! KT- ; KT; 60 ; 90 i 120
j
b
i
L1*
30 i 30 ; 24
:1 :1
1
1 :1
1
' 1 j 1 , 1
1 11
:1 1
1
;i ii ;i
;i 11
i
!i 11 .i
i1 :11i
!1 1 i
i1 1 1
1
<. 1 1 , 1
6 ! 8 10 12 14 180 i 240 ! 300 360 , 420
300 i 400 500 600 700
144.j 192 ; 240 288 336
KT- j KT- ; KT- KT- KT180 [ 240 ! 300 360 420
V/2 2 ; 2 30 1 29 32
2 ;2 38 41
1 !1
111 ; 1 i !i ;i 1 1
1 .1 ;i 1 1 i ii i1 1 1
1 '1 I1
1
b
ii
1
1 1
i i i1
1 !1
1
1 1 !1
ii i .i 11
1 :1 |1 i i 1 .1 1 1 1
16 J 19 22 24
480 ; 560 i 640 720
800 933 ' 1067 1200
384 : 448 i 512 576
KT- , KT- j KT- KT480 i 560 640 720
2 i2 44 | 50
2 2>/z 56 ' 45
, ' 11
i: i1 ij1 ij1 11 1 i1 1 ;1
1 1i1 il
1 11 11 ii1
" 28 840 1400 672 KT840
2'/2 51
32
960 1600 768 KT960
2'/2 57
36 1080 1800 864 KT1080 2'/z 63
40 1200 2000
960 KT1200
2'/z 69
44 1320 2200 1096 KT1320 2'/z 75
--
1 1!
ij
1i
i
1 l 11 1 j
___ i___
11
domestic hot water ... all year 'round!
Every Kewanee Square-Heat Boiler is arranged for easy installation of Indirect Water Heating Coils (either tankless or storage tank type) which can be fitted at any time by simply removing coil opening cover plate and bolting coil in place.
For Gravity Circulation with storage tank, check the table above. For instantan eous Flow, see table below.
RESIDENTIAL RATINGS--Based on intermittent draw of hot water with short peak demands
FAMILIES OR BATHS
1 1-2
4
6 15 25 35 45 52 65 78 92 105 120 130 140 150 160 170 180 190
Gallons Per Hour 40 to 140F BW 180aF.
240 300 380 480 600 720 840 920 1080 1240 1400 1560 1740 1860 1980 2100 2220 2340 2460 2580
COMMERCIAL RATINGS--Based on continuous draw of hot water with long peak demands
INSTRUCTIONS: Read across top section of table to find desired coil capacity. Read down column until you reach correct boiler size. If number appears m that box, coil will fit The number represents the maximum quantity of coils boiler will accommodate
28513
V
Did you know...
American-Standard Industrial Division offers all the major components for air handling, heating, and air conditioning? You can look to one company for your total requirements for systems of any size or degree of complexity . . . whether you need roof ventilators, package units, multi-zone air conditioners, fans, centrifugal refrigerating machines, water chillers, boilers, or dust collectors. You'd be surprised at the con venience. You talk to product specialists who speak your language. You have one source responsible for quality and performance in equipment designed and manufactured to work together.
SALES OFFICES IN ALL PRINCIPAL CITIES
Executive offices: Detroit 32, Michigan
!n Canada American-Standard Products (Canada) Ltd
Toronto 4. Ontario Canadian Sirocco Products
AMERICAN RADIATOR A STANDARD SANITARY CORPORATION