43--Fire Protection
crease the clearance up to 36 in over large, closely packed piles of combustible cases, bales, cartons, or similar stock
6 Conosion of sprinklers in such locations as bleachenes, dye houses, oi chemical operations Use sprinklers specially pro tected for use in such locations
7 Inadequate supplv of water because of faultv design oi poor maintenance Verify that water conditions have not changed since original plant installation It is im portant that the system be sturdily installed and anchored because explosions can jolt the piping and render the system ineffec tive
Water spray systems
Watei spray is effective on all types of flies wheie there is no hazardous chemical leacbon between the water and the matenal that is burning These systems are independent of, and supplemental to, other forms of piotection --not a replacement for automatic sprinklers
Fixed watei sprav systems are similar to the standard deluge system except that the open spunklers are teplaced with spray-type nozzles The water supply to the system can be conti oiled automatically or manually They are geneially used to protect flammable liquid and gas tankage, piping and equipment, cool ing towers, and electrical equipment, such as transfoimers, oil switches, and motors (Fig 43-32) Because of its low electrical conduc tivity, water spiav applied thiough fixed piping systems on electncal equipment with voltages as high as 345,000 volts has pioved piactical When applied on some tvpes of electrical equipment, water spiav may cause shoit circuits bv foiming a continuous path of watei between energized parts In such cases, means should be piovided foi cutting off the electnc cunent befoie the watei spray is ap plied (See NFPA Standard No 15, Water Spray Fixed Systems )
The tvpe of watei spiay lequned depends upon the natuie of the hazatd and the puipose foi which the piotection is provided The basic pnnciple of water spraying is to give a complete surface wetting with a pre-selected water density, taking into consideiation nozzle tvpes, sizes, spacing, and watei supplv
Watei sprav systems can be designed effec-
1368
Fig 43-32 --A water spray system for oil-filled electric power transformers A thick layer of crushed stone and subsurface drainage is provided around the base of the transformer installation to prevent burning oil from flowing beyond the area protected by the spray
Courtesy National Fire Protection Association
tivelv foi any one oi any combination of the following
1 Extinguishment of fiie
2 Control of fire wheie extinguishment is not desirable, such as gas leaks
3 Exposure piotection, that is, absorb the ladiant heat bv evaporation of the sprav
4 Pievention of fire
Since the passages m a watei spiay nozzle aie small in comparison with those in the oidinaiv sprinkler, they can easily be clogged bv foreign mattei m water Therefoie, strameis aie ordinallly lequired m the supply lines of fixed-piping spiay systems The strainer basket should have holes small enough to piotect the smallest orifices of the nozzles used In cases where the nozzles have ex tremely small water passages, they may have their own internal stiainei in addition to the supply-line strainei