Document aJwX7qMzN0Y0obYrRgXa42EDM
496
CHAPTER 34
1959
for example, connection to an effective flue is mandatory. Furthermore, ail such heating equipment must incorporate an automatic ignition pilot that will shut off gas supply to the main burner or burners in the event of pilot outage. If liquefied petroleum gas is used, the automatic pilot must cut off all gas supply to the appliance, including the pilot burner, in case the pilot flame becomes extinguished.
Rating and Sizing Gas Appliances
Input rating for a gas appliance is established by demon strating that the appliance can meet the Approval Require ments of the ASA. The tests are conducted at the A.GA. Testing Laboratories. Output rating is determined from the approved input and a minimum required efficiency stated in the Approval Requirements, and is the heat available at the outlet.
Although gas-burning equipment usually is completely automatic, maintaining the temperature of rooms at a pre determined figure, there are some manually controlled in stallations. In order to overcome effectively the starting load and losses in piping, a manually-controlled gas boiler should have an output as much as 100 percent greater than the equivalent standard radiation which it is expected to serve. .. Boilers under thermostatic control, however, are not sub ject to such severe pick-up loads and consequently, it is pos sible to use a lower selection factor. For a gas-fired boiler or furnace under thermostatic control, a factor of 20 to 25 per cent is usually sufficient for pick-up allowance.
In those installations, in mild climates where 100 percent outdoor air is used, furnaces should be of larger size in order to provide adequate capacity and quick pickup under in termittent heating conditions.
The factor to be allowed for loss of heat from piping will vary somewhat, the proportionate amount of piping in stalled being greater for small installations than for large ones. For selection factors to be added to installed radiation under thermostatic control, see Chapter 35.
Appliances used for heating with gas should bear the ap
proval seal of the A.GA. Testing Laboratories on the manu facturer's nameplate; together with the official input and output ratings. It is not permissible-to operate a gas beating unit above its stated rating. It may be necessary to operate below this rating at elevations above 2000 ft. Installations should be made in accordance with recommendations of the American Gas Association, as shown in current American Standard for Installation of Gas Piping and Appliances in Buildings, ASA Z21.30, and in accordance with local regu lations.
Sizing of Gas Piping
Piping for gas appliances should be of adequate size, and so installed as to provide a supply of gas sufficient to meet the maximum demand without undue loss of pressure be tween the point of supply (the meter) and the burner. The size of gas pipe required depends upon the following:
1. Maximum gas consumption to be provided. 2. Length of pipe and number of fittings. 3. Allowable loss in pressure from the outlet of the meter to the burner. 4. Specific gravity of the gas.
To obtain the cubic feet per hour of gas required by the burner, divide the Btu input rate at which the. burner will be adjusted, by the average Btu heating value per cubic foot of the gas.
Capacities of different sizes and lengths of pipe, in cubic feet per hour, with a pressure drop of 03 in. of water column for a gas of 0.60 specific gravity, are shown in Table 3. In adopting a 03 in. pressure drop, due allowance for an ordi nary number of fittings was made.
To convert the values given in Table 3 to capacities for another gas of different specific gravity, multiply the tabular values by the multipliers shown-in Table 4.
Pipe capacities for gas flow up to 100,000 cfh for various lengths of pipe are given in Fig. 16 whichis based on a spe cific gravity of 0.60. The capacity at a given pressure loss for a different specific gravity may be obtained by multiply ing Fig. 6 capacities by a multiplier obtained from Table 4.
Table 3 .... Capacity of Gas Piping--Cu Ft Per Hr. (A/ pressure drop of 0.3 fn. wafer. Spedfn gravity = 0.60)
length of Pipe H
Xl
Iron Pipe Size (fPS) Inches 23
4
15 30 45 60
75 90 105 120
150 180 210 240
270 300 450 600
76 52 43 38
172 345 120 241
99 199 86 ' 173
77 155 70 141 ' 65 131
120
109 100
92
750 535 435 380
345 310 285 270
242 225 205 190
178 170 140 119
1220 850 700 610
545 490 450 420
380 350 320 300
285 270 226 192
2480 1780 1475 1290
1120 1000
920 > 860
780 720 660 620
580 545 450 390
6500 4700 3900 3450
3000 .2700 2450 2300
. 2090 ' 1950 1780 1680
1580 1490 1230 1030
13880 9700 7900 6800
6000 5500 5100 4800
4350 4000 3700 3490
3250 3000 2500 2130
From America Standard Inttgllation <tf Go* Piping and Oar AppUaneu in BtttUingt, ASA ZSlJC-lBSt.
6
38700 27370 23350 19330
17310 15800 14620 13680
12240 11160 10330
9600
9000 8500 7000 6000
8
79000 55850 45600 39500
35300 32250 29850 -27920
25000 22800 21100 19740
18610 17660 14420 12480
Length ot Pipe Ft
15 30 45 60
75 90 105 120
150 180 210 240
270 300 450 600
.
Automatic Fuel Burning Equipment
Table A.... Multiplier* for Various Specific Gravities (For Uro Wirt) Table 3 and Fig. 16)
Specific Gravity
Multiplier
Specific Gravity
MMptier
0.35 0.40 0.45 0.60
0.55 0.60 0.65 0.70
0.75 0.80 0.85 O.90
1.31 1.23. 1.16 1.10
1.04 1.00 0.962 0.926
' 0.895 0.867 0.841 0.817
1.00 1.10 1.20 1.30
1.40 1.50 1.60 1.70
1.80 1.90 2.00 2.10
0.775 0.740 0.707 0.680
0.655 0.633 0.612 0.594
0.577 0.565 0.547 0.535
COMMERCIAL AND INDUSTRIAL GAS EQUIPMENT
No attempt can be made, due to space limitation, to de scribe or classify the varied types of equipment used for commercial and industrial applications. Much of the equip ment utilized is custom built to suit a particular process. Certain standard parts such as venturi and burner head sets, ring burners, proportional mixers, or compressors, are pur chased for assembly in existing equipment, usually by the installer. Furnaces to provide particular atmospheres or for annealing, soaking pits, metal melting, etc. are usually en gineered by industrial gas-equipment manufacturers.
Burners utilized in industrial equipment often operate at gas pressures higher than encountered in domestic usage. High-pressure gas provides flexibility of control required
497
in the production of constant temperatures^ In addition, airgas ratios can be closely maintained under throttling con ditions, and heat liberation per cubic foot ' of combustion space is considerably greater than can be achieved with lower pressures.
A few of the many basic types of burners used are as follows: single-pipe high-pressure, proportional mixing, premix, two-pipe high-pressure, and atmospheric.
The single-pipe high-pressure burner system utilizes gas delivered to the orifice of a venturi at pressures from TO to 50 psig. A constant pressure compressor, sometimes remotely placed, is occasionally used to increase the gas pressure. The velocity of the gas issuing from the orifice entrains primary air which is controlled by an air shutter on the venturi tube. An advantage of this system is that when the gas pressure is reduced (lowering the input) the air-gas ratio will remain constant, over a fairly wide range.
In the proportioned miring burner, an enclosed type ven turi is used and high-pressure air is delivered through an ori fice. The resulting partial vacuum entrains the gas which is supplied through a zero pressure governor. When the air pressure is reduced, the amount of gas entrained is similarly reduced, thus maintaining a constant air-gas ratio over a wide fuel capacity range.
The pre-mix burner system embodies a compressor which mixes air and gas intimately and discharges the mixture through pipes to the burners where it is discharged through orifices and burned. The pre-mix compressor can be re motely installed and the mixture can be closely controlled.
The tu>o-pipe high-pressure burner system utilizes both air and gas under pressure, both being delivered through orifices and mixed prior to delivery to the burner.
The atmospheric burner system is not commonly used. It consists of a burner supplied with gas at a pressure of 2
QrfLOW.JN CUBIC FEET PER HOUR
1
tr
Bated on Spffzgfon Friction factor and 0A0 Specific Gravity. To convert tor other ipedfic gravity tee Table 4. fig. 16 .... Flow vs. Pressure Drop for Low Pressure Natural Gas