American Society of Heating and Ventilating Engineers Guide, 1936
analysis of this section is predicated on the assumption of constant gas temperature and no air infiltration throughout the height of the chimney.
5. The coefficient of friction between the chimney gases and a sooted surface has been taken by many workers in this field as a.constant value of 0.016 for the conditions in volved. This value, of course, would be less for a new unlined steel stack than for a brick or brick-lined chimney, but in time the inside surface of all chimneys regardless of the materials of construction becomes covered with a layer of soot, and thus the coef ficient of friction has been taken the same for all types of chimneys and in general constant for all conditions of operation. For reasons of simplicity and convenience to
Fig. 5. Chimney Performance Chart 2o solve a typical example: Proceed horizontally from a Weight Flow Rate point .to intersection with diameter line; from this intersection follow vertically to chimney height line; from this intersection follow horizontally to the right to Available Draft scale. Starting from a point of Available Draft, take steps in reverse order. the reader, this constant value of 0.016 has been employed in the development of the various special equations and charts shown in this chapter. ! However, much to be recommended as an alternate method is the practise of .separ ately determining duct friction factors as a function of the flow conditions, specifically as a function of the Reynolds number and the relative duct roughness. The Reynolds criterion is based on the physical properties of the gas, the duct dimensions, and the gas velocity. The gas velocity for a chimney is usually well above the critical velocity. It is likely that this procedure of using a separately determined variable friction factor for chimney flow will give results that are to be preferred over those based on a set constant. . 6. The length of the friction duct is the vertical distance between the bottom of the breeching opening and the top of the chimney. Ordinarily this distance is approximately equal to the height of the chimney above the grate level.
456
Chapter 26--Chimneys and Draft Calculations
7. Assuming no air infiltration the amount of gases flowing and being discharged is, of course, equal , to the amount of gases generated in the combustion chamber of the boiler. The total products of combustion in pounds per second for a grate fired boiler may be computed from the equation:
where
w = C*g^tp. 3600
(4)
Cg = pounds of fuel burned per-square foot of grate surface per hour. G = total grate surface of boilers, square feet. Cg X G = total weight of fuel burned per hour. . Wtp .= total weight of products of combustion per pound of fuel.
A similar computation may be made in the case of gas, oil, or stoker-fired fuel.
Fig. 5 is a typical chimney performance chart giving the available draft intensities for various amounts of gases flowing and sizes of chimney. This chart is based on an atmospheric temperature of 62 F, a chimney gas temperature of 500 F, a unit chimney gas weight of 0.09 lb per cubic foot, 'sea level atmospheric pressure, a coefficient of friction of 0.016, and a friction duct length equal to the height of the chimney above the grate level. These curves may be used for general operating conditions. For specific operating conditions, a new chart should be constructed from Equation 1.
It has been.the usual custom, and still- is to a lamentably greatextent, to select the required size of a nat'ural draft chimney from a table of chimney sizes based only on boiler horsepowers. After the ultimate horsepower of the projected plant had been determined, the chimney size in The table corresponding to this figure Was then selected as the proper size required. Generally, no further attempt was, made to determine if the height thus selected.was sufficient to help create the required draft demanded by the entire installation, or the diameter sufficiently large to enable the chimney quickly, efficiently, and economically to dispose of the gases. Since the operating characteristics of a natural draft chimqey are similar in,all respects to those of a centrifugal pump, or a centrifugal fan, it'is no more possible to select a proper size chimney from such a table, even with correction factors appended, than it is to: select the proper size pump from tables based only on the amount of water to be delivered. .
DETERMINING CHIMNEY SIZES
The required diameter and height of a natural draft chimney are given by the following equations:
H
=
Dr
20g.|)J;>wv
TCD
. (5)
where
D = 0.288 J WTc
" BoWcV
(6)
H = required height of chimney above grate bar level, feet. D = required minimum diameter of chimney, feet (constant for entire height).