CHAPTER 38_________________
1948 .Guide
change of the air being processed is.determined by the cooling water tem perature and the amount of moisture removed in the equipment. Control of leaving air temperature may be obtained by precooling the absorbent solution in a suitable surface cooler, by tap, well, or chilled water, .
The excess water of condensation,.which dilutes the brine, is.removed in the solution concentrator. This is a low.pressure steam.heat exchanger which over-concentrates a portion of the weak liquor and returns it to the main brine reservoir for re-cycling. The concentrator operates in the mariner of an evaporative condenser, whereby moisture is evaporated from the brine by the heating coils into a stream of regeneration air taken 'from and rejected to the outside atmosphere. Low pressure steam is normally used for heating the brine. When it is desirable or necessary to use gas or electricity, an auxiliary low pressure steam-boiler'is usually
Fig. 5. Liquid Absorbent Equipments Which Solution Cooler and
Contactor are Combined
. ...........
added to the equipment. Concentrators operating on a simple, boiler principle have not as yet beeri commercially practical..
It should be noted that the solution concentration phase is the reverse
of: the absorption process. During concentration the aqueous vapor
pressure of the solution is greater than that of the surrounding,air, while
during dehumidification, the reverse is the case Utilization of this
principle permits winter humidification by heating (instead of cooling)
the solution pumped, to. the contactor. Water is thereby evaporated
into; instead of being condensed out of, the conditioned air stream. This
requires dilution of the brine externally .to the contactor, rather than
concentration. /
;.
CALCULATION OF MOISTURE LOAD
Calculation of the. dehumidification required to maintain lower than normal moisture content in a given room begins with determination of the rate of moisture gain in the .room from all sources. It is common
practice when maintaining a low humidity ratio to. recirculate a large percentage of the air in the room through the dehumidifier, and to add only enough outside air to meet the needs of the problem. The humidity ratio of the. rnixture of outside; and recirculated air and the dehumidifier performance data can be used to calculate the humidity ratio of the air leaving the dehumidifier. The difference between the humidity'ratio of the air in the room and that, of .the . dehumidified air entering the room
Dehumidification by Sorbent Materials
681
represents the effective dehumidification per-pound of air. The rate of
internal moisture gain in grains per minute divided by the effective dehumidification in, grains per pound of air equals the air quantity required in pounds per minute. The following typical example usmg arbitrary values shows a general method of determining the dehumidifying requirements. Sensible heat determination considerations are
discussed in other chapters and are purposely omitted here.
Example 1. A solid adsorbent dehumidifier having performance characteristics as shown in Fig..6 is to be used to maintain inside conditions of 73 F and 20 per cent relative humidity, 24.1 grains per pound of dry air, 30 F dew-point, in a room, 20 ft x 30 ft x 10 ft high, having a total wall, ceiling, and floor surface area of 2200 sq ft. Outside design conditions are 72 F dew-point (118.4 grains per pound).
Internal sources of moisture are: 4 occupants; an open natural gas burner using15 cu ft of natural gas per hour; an open top water tank, having an area of 2 sq ft ex posed surface, in which water is maintained at 87 F, with air movement over the water surface being 100 fpm. Determine the quantity and condition of the dehumidified air
to be supplied to the room.
Solution. The internal moisture gain consists of items 1 to 5.
Grains Per Minute
- 1. From occupants:
4 X 1800/60 =
120
1800 grains per person per hour is obtained from Fig. 7, . Chapter 12,-by interpolation between curves C and D.
2. From burned gas:
15 X 650/60 =
1 cu ft natural gas produces approximately 650 grains of
moisture.
162
3. From exposed water surface:
2 X 20 =
Evaporation from water surface is assumed to be 20 grains per (minute) (square foot) at 87 F water with air movement
of 100 fpm.
40
4. From infiltration:
60 *^13 56 ^ U18.4 -- 24.1) =
696
One air change, 6000 cu ft, assumed per hour (see Chapter 8).
5. Moisture transmitted through room surface:
oU X 3 X (0.783 - 0.176) = Permeability assumed to be 3 grains per (square foot) (hour) (inch Hg vapor pressure difference on two sides of wall).
Total moisture gain from internal sources
67
_____ 1085
Let q be the air delivered to the room, pounds per minute. Let it be assumed for this problem that 85 per cent of the air is recirculated and 15 per cent is outside air. Enough air must be supplied to replace leakage from the system or to satisfy normal ventilating requirements for the occupants of the room as given in Chapter 12, whichever is greater. The amount is estimated from experience or obtained by test.
The humidity ratio of the mixture of recirculated and outside air entering the dehu
midifier is then:
0.85g (24.1) + 0.15g (118.4) = 3g 3 gra;ns per pound entering dehumidifier.
0.85g + 0.15g
For the dehumidifier shown in Fig. 6, for 38.3 grains per pound in entering air, the
leaving humidity ratio will be 6.5 grains per pound.
Effective dehumidification in the room is 24.1 -- 6.5 or 17.6 grains per pound of
supply air.
'
Then a = 1055
per minu*g = 61.6 lb air per minute minimum that mtist be
* 17.6 grains per pound
*
supplied to the room to maintain 30 F dew-point.
. Note that this figure represents the.minimum requirement for the arbitrary conditions
set forth and that in practice safety margins should be added to the outside air per
centage figure and to the calculated internal moisture gain.