Document aBepqbzzLnkoLr58gQG2R6qGR

680 CHAPTER 38_________________ 1948 .Guide change of the air being processed is.determined by the cooling water tem perature and the amount of moisture removed in the equipment. Control of leaving air temperature may be obtained by precooling the absorbent solution in a suitable surface cooler, by tap, well, or chilled water, . The excess water of condensation,.which dilutes the brine, is.removed in the solution concentrator. This is a low.pressure steam.heat exchanger which over-concentrates a portion of the weak liquor and returns it to the main brine reservoir for re-cycling. The concentrator operates in the mariner of an evaporative condenser, whereby moisture is evaporated from the brine by the heating coils into a stream of regeneration air taken 'from and rejected to the outside atmosphere. Low pressure steam is normally used for heating the brine. When it is desirable or necessary to use gas or electricity, an auxiliary low pressure steam-boiler'is usually Fig. 5. Liquid Absorbent Equipments Which Solution Cooler and Contactor are Combined . ........... added to the equipment. Concentrators operating on a simple, boiler principle have not as yet beeri commercially practical.. It should be noted that the solution concentration phase is the reverse of: the absorption process. During concentration the aqueous vapor pressure of the solution is greater than that of the surrounding,air, while during dehumidification, the reverse is the case Utilization of this principle permits winter humidification by heating (instead of cooling) the solution pumped, to. the contactor. Water is thereby evaporated into; instead of being condensed out of, the conditioned air stream. This requires dilution of the brine externally .to the contactor, rather than concentration. / ;. CALCULATION OF MOISTURE LOAD Calculation of the. dehumidification required to maintain lower than normal moisture content in a given room begins with determination of the rate of moisture gain in the .room from all sources. It is common practice when maintaining a low humidity ratio to. recirculate a large percentage of the air in the room through the dehumidifier, and to add only enough outside air to meet the needs of the problem. The humidity ratio of the. rnixture of outside; and recirculated air and the dehumidifier performance data can be used to calculate the humidity ratio of the air leaving the dehumidifier. The difference between the humidity'ratio of the air in the room and that, of .the . dehumidified air entering the room Dehumidification by Sorbent Materials 681 represents the effective dehumidification per-pound of air. The rate of internal moisture gain in grains per minute divided by the effective dehumidification in, grains per pound of air equals the air quantity required in pounds per minute. The following typical example usmg arbitrary values shows a general method of determining the dehumidifying requirements. Sensible heat determination considerations are discussed in other chapters and are purposely omitted here. Example 1. A solid adsorbent dehumidifier having performance characteristics as shown in Fig..6 is to be used to maintain inside conditions of 73 F and 20 per cent relative humidity, 24.1 grains per pound of dry air, 30 F dew-point, in a room, 20 ft x 30 ft x 10 ft high, having a total wall, ceiling, and floor surface area of 2200 sq ft. Outside design conditions are 72 F dew-point (118.4 grains per pound). Internal sources of moisture are: 4 occupants; an open natural gas burner using15 cu ft of natural gas per hour; an open top water tank, having an area of 2 sq ft ex posed surface, in which water is maintained at 87 F, with air movement over the water surface being 100 fpm. Determine the quantity and condition of the dehumidified air to be supplied to the room. Solution. The internal moisture gain consists of items 1 to 5. Grains Per Minute - 1. From occupants: 4 X 1800/60 = 120 1800 grains per person per hour is obtained from Fig. 7, . Chapter 12,-by interpolation between curves C and D. 2. From burned gas: 15 X 650/60 = 1 cu ft natural gas produces approximately 650 grains of moisture. 162 3. From exposed water surface: 2 X 20 = Evaporation from water surface is assumed to be 20 grains per (minute) (square foot) at 87 F water with air movement of 100 fpm. 40 4. From infiltration: 60 *^13 56 ^ U18.4 -- 24.1) = 696 One air change, 6000 cu ft, assumed per hour (see Chapter 8). 5. Moisture transmitted through room surface: oU X 3 X (0.783 - 0.176) = Permeability assumed to be 3 grains per (square foot) (hour) (inch Hg vapor pressure difference on two sides of wall). Total moisture gain from internal sources 67 _____ 1085 Let q be the air delivered to the room, pounds per minute. Let it be assumed for this problem that 85 per cent of the air is recirculated and 15 per cent is outside air. Enough air must be supplied to replace leakage from the system or to satisfy normal ventilating requirements for the occupants of the room as given in Chapter 12, whichever is greater. The amount is estimated from experience or obtained by test. The humidity ratio of the mixture of recirculated and outside air entering the dehu midifier is then: 0.85g (24.1) + 0.15g (118.4) = 3g 3 gra;ns per pound entering dehumidifier. 0.85g + 0.15g For the dehumidifier shown in Fig. 6, for 38.3 grains per pound in entering air, the leaving humidity ratio will be 6.5 grains per pound. Effective dehumidification in the room is 24.1 -- 6.5 or 17.6 grains per pound of supply air. ' Then a = 1055 per minu*g = 61.6 lb air per minute minimum that mtist be * 17.6 grains per pound * supplied to the room to maintain 30 F dew-point. . Note that this figure represents the.minimum requirement for the arbitrary conditions set forth and that in practice safety margins should be added to the outside air per centage figure and to the calculated internal moisture gain.