Document a4o7qRMrdex2eR111GQxZnL4R
American Society of Heating and Ventilating Engineers Guide, 1935-
Using the prices shown in Table 5, the cost of the 1,600 ft. of shown in Fig. 11, is S3,193. Assuming the life of the main to be 20 and the interest rate 6 per cent, the cost of the main is $278 per
Table 5. Approximate Cost of Covered Pipe Installed in Tunned
Sizes--Inches
2 2M 3 3M 4
568
Cost per Foot ... $0.75 $1.00 $1.25 $1.50 $1.75 $2.00 $2.25 $2.75 $4.50
The power required to circulate the water through the main is 150,000 X 15.9, or 2,385,000 ft. pounds per hour, or 1.2 hp. Assuming that'the power required to circulate the water through the central plant is 15, per cent of the amount stated, that the efficiency of the pump is 75 pjr cent, and that the cost of current is 2^ cents per kilowatt-hour, the cost of circulating the water is 3.44 cents per hour, or $144 per year if the: pump is to be operated 20 X 30 X 7, or 4,200 hours a year.
After completing two additional calculations similar to the one just1 described, for the system in which the largest pipes in the main are 4 in. and 6 in. respectively, the following results are obtained:
Largest Main, Inches
Velocity in Same Total Friction
Inches per Second
In Feet
4 93 34.8 5 58 15.9 6 40 6.47
Annual Cost
$221 278 340
Annual Cost of Circulation
$316 144 59
Combined Cost
$S37^~
422
399
This comparison assumes that the cost of the pump is practically the same in the three cases and that the cost of forcing the water through the six buildings remains constant.
Optimum Velocity of Water in Forced Circulation Systems
Based upon these assumptions, the system having the 6-in. main with a velocity of 40 in. per second in that main is the most economical to install.
For this installation the cost o circulating the water-would be about 2 per cent of the cost of the heat, if. the latter is estimated at 50 cents per 1.000. 000 B.t.u., and if it is further assumed that the average heat demand will be one-half of the maximum, i.e., that the average will be 1,500,000 for the plant which was designed for a maximum demand of 3.000. 000 B.t.u. per hour.
In a manner similar to that described before, every forced circulation system should be analyzed before definite pipe sizes are adopted.
In large installations it may be found advantageous to transport the heat from the central plant to the central point of a group of buildings by means of high-pressure steam and to install at this central point a heat exchanger and a circulating pump.
200
Chapter 11--Hot Water Heating
Mfeci of. location of Expansion Tank on Pressure in Forced System .Inmost centra heating systems it is necessary to use an expansion g&ZSuch a tank is generally msta led near the circulating pump and pits suction side; the pump being located in the return line near the heater. With such an arrangement, the pressure in the main remains
_____ ,
`sfcfcii*"
1_____ h"-*
~ .<--------- .
12 Two-Pipe, Direct-Return, Forced Circulation System for Six Buildings
^-Heater ''flump
Fic. 13. Influence of the Circulati<nTg" Pump upon the Pressure in the Flow Main
constant at the suction side of the pump; it rises sharply in the pump and then decreases gradually along the main/ as indicated in Fig. 13. In this figure, the line 1, 2, 3, 4, is a base line; the line 5, 6, 7, 8, is a line parallel to the base line drawn so that the distance 1 to 5 represents the pressure
----. .v in ooerarion. This pressure is deter* - flisif-