VINYL CHLORIDE
RAILROAD TANK CAR LOADING OPERATION
AND
.
/
UN.OADING OPERATION
V
1093J/KP 9/28/87
VMD 720903
HOW MANY LIQUID HOS^S DO YOU ATTACH? SIZE?
LOADING:
ONE - 7 TWO - H
1-1/2" 2" 3"
-1 -6 -4
HOW MANY VAPOR HOSES DO YOU ATTACH? SIZE?
LOADING:
ONE - 10 TWO - 1
1" 1-1/2" 2" 3"
-2 -2 -5 -1
HOW MANY LIQUID HOSES DO YOU ATTACHE? SIZE?
UNLOADING:
ONE - 10 TWO - 11
.
2" - 11 3" - 9 4" - 1
HOW MANY VAPOR HOSES DO YOU ATTACH? SIZE?
UNLOADING:
ONE - 15 TWO - 1
1i .1 - 2 1-1/2" - 2 2" - m 3" - l
1093J/KP 9/28/87
VMD 720905
DO YOU HAVE AN EXCESS FLOW VALVE IN THE PIPING? (NOT THE EXCESS FLOW VALVE IN THE RAILROAD CAR.)
. LOADING:
' YES - 4 NO - 8
UNLOADING:
YES"- 0 NO - 21
IF YES. PLEASE DESCRIBE THE TYPE OF VALVE AND WHERE IT IS LOCATED.
LOADING:
TUFLIN VALVE - 10M FROM OFF-LOADING STATION MASONSILAN VALVE - UPSTREAM OF HOSE FLANGE SPRING-CHARGED EXCESS FLOW VALVE - FIXED PIPING OVERSPEED COUNTER SHUTOFF VALVE - PIPING
1093J/KP 9/28/87
VMD 720906
V
DO YOU HAVE A CHECK VALVE IN THE PIPING OF FAf.H 1INI OADTNG HOSE?
UNLOADING:
YES - 9 NO - 12
.
IF YES, PLEASE DESCRIBE THE TYPE OF VALVE AND WHERE IT IS LOCATED.
CHECK VALVE AT EACH UNLOADING TOWER
SWING CHECK VALVE
FLAPPER CHECK VALVE IN FIXED PIPING
CHECK VALVE AT EACH UNLOADING STATION
CHECK VALVE AT PUMP DISCHARGE
METAL FLAP VALVE AT PUMP DISCHARGE
BALL VALVE 300MM FROM CONNECTING FLANGE
CHECK VALVE IN PIPING
TWO-BEAT VALVE NEXT TO BLOCK VALVE
1093J/KP 9/28/87
VMD 720907
DO YOU RELY ON THE RAILROAD CAR EXCESS FLOW VALVE?
LOADING:
YES - 7 NO - 3
COMMENTS:
'
.
OVERSPEED COUNTER PROVIDES SAFETY
~ - RAILROAD EXCESS FLOW IS DESIGNED FOR DERAILMENT IF VALVES ARE WIPED OFF OR IN CASE AN UNLOADING LINE IS COMPLETELY RUPTURED. THEY WILL NOT SEAT WITH A SMALL LEAK.
UNLOADING:
YES - 13 NO - 6
1093J/KP 9/28/87
VMD 720908
HOW no YOU MEASURE THE VCM LEVEL IN THE RAILROAD TANK CAR? PLEASE DESCRIBE.
LOADING:
:
VOLUMETRICAL MEASUREMENT FIXED NEEDLE VALVE AT MAXIUM ALLOWABLE LOAD MIDLAND MAGNETIC GAUGE MIDLAND MAGNETIC GAUGE MIDLAND MAGNETIC GAUGE - WEIGHED LOAD ON SCALES LOAD ON SCALES LOAD ON SCALES TEMPERATURE AND OUTAGE TABLE
.
UNLOADING:
BAYONET AND ROTOGAUGE
PRESSURE DROP AND SIGHT GLASS
LINE TEMPERATURE AND SIGHT GLASS
SLIP TUBE
WEIGH BEFORE AND AFTER UNLOADING
BAYONET FLOAT GAUGE AND ROTARY LEVEL INDICATOR
BY WEIGHT
BY WEIGHT
ROTARY GAUGE
.
MIDLAND MAGNETIC GAUGE
MIDLAND MAGNETIC GAUGE
MIDLAND MAGNETIC GAUGE
MIDLAND MAGNETIC GAUGE - VAPOR
PRESSURE DROP
RAILROAD CAR SPRINGS AND SIGHT GLASS
OUTAGE GAUGE
1093J/KP 9/28/o7
'
VMD 720909
WHAT TYPE OF SAFETY PROTECTION IS PROVIDED IN YOUR RAILROAD TANK CAR LOADING/UNLOADING OPERATION? PLEASE DESCRIBE.
LOADING:
BONDING AND GROUNDING ON SHUTOFF VALVES
AUTOMATIC
SHUTDOWNS ON HIGH PRESSURE AND OVERWEIGHT
FIRE WATER MONITORS AND AREA MONITORING
FIRE WATER MONITORS
FIRE WATER MONITORS
AREA MONITORING
LOADING AREA VENT/LIQUID ABV'S, REMOTE PUMPS
SHUTOFFS. GROUND INDICATOR. FIRE WATER MONITORS
LEL DETECTORS. HIGH PRESSURE. HIGH LEVEL AND VALVE
POSITIONS ARE INTERLOCKED
EMERGENCY SHUTDOWN VALVES
OVERFILL PROTECTION BY VOLUME AND WEIGHT
EMERGENCY AUTOMATIC SHUTDOWN VALVES. HIGH PRESSURE.
OVERSPEED ON VCM COUNTER
VAPOR DETECTORS WITH AUTOMATIC SHUTDOWN. DELUGE FIRE
SYSTEM
-
I093J/KP 9/28/87
W 720910
DO YOU HAVE A GC MONITORING SYSTEM IN THE LOADING/UNLOADING AREA? YES. NO. OTHER.
LOADING:
YES - 6 NO - 2 OTHER - 2
UNLOADING:
YES - 13 NO - 3 OTHER - 6
1093J/KP 9/28/87
VMD 720911
DO YOU INSTALL A REMOTE OPERATED SHUTOFF VALVE AT THE TANK CAR CONNECTION? IF YES. WHAT ACTIVATES THIS VALVE?
LOADING:
YES - 3 NO - 7
COMMENTS:
SCALE WEIGHT OR MANUAL ACTUATION MANUAL REMOTE SHUTOFF VALVES EMERGENCY STOP. FILLING COUNTER AND OVERFILLING
ALARM
UNLOADING:
YES - 7 NO - 13
COMMENT:
AIR FAILURE, REMOTE SWITCH, LEL RAILROAD CAR MOVEMENT, REMOTE AND LOCAL SWITCH GAS MONITOR OR MANUAL BUTTON FLOW METER. MANUAL OR LOSS OF GROUND LOSS OF GROUND AND LOSS OF AIR RAILROAD CAR WEIGHT OR PUMP STOPPING LOSS OF AIR AND REMOTE SWITCH
1093J/KP 9/28/87
VMD 720912
WHAT TYPE OF HOSE DO YO USE IN THIS SERVICE? PLEASE DESCRIBE.
LOADING:
CHEMIFLEX (LAYERED POLYPROPYLENE) AND BRAIDED SS TEFLON LINED
CHEMIFLEX 0951PP (POLYPROPYLENE REINFORCED WITH GALVANIZED WIRE) t
CHEMIFLEX (POLYPROPYLENE WITH CARBON STEEL WIRE) JOINT ARM PIPES AND FITTING METAL HOSE ANACONDA METAL HOSE #C.T.21-1 STAINLESS STEEL. TEFLON LINED STAINLESS STEEL FLEX STAINLESS STEEL. TFE LINED CONTINENTAL EMSCO SWIVEL JOINTS GATES 45 HW. LIQUID AND GASEOUS HOSES
UNLOADING:
STAINLESS STEEL 304 (FLEXONVE STYLE 461) ARMOURED STAINLESS STEEL STAINLESS STEEL FLEX HOSE STAINLESS STEEL FLEXCARE STAINLESS STEEL FLEXIBLE HOSE WITH RUBBER COVER STAINLESS STEEL BRAIDED STAINLESS STEEL FLEX HOSE STAINLESS STEEL BRAIDED HOSE STAINLESS STEEL FLEX HOSE STAINLESS STEEL FLEX HOSE DOUBLE BRAIDED STAINLESS STEEL
1093J/KP 9/28/87
VMD 720913
BRAIDED STAINLESS STEELiFLEX HOSE
PIPE WITH FLEXIBLE UNIT
LOADING ARMS
-
RIGID ARTICULATED PIPE (PEROLO TYPE)
UNLOADING ARM WITH SWIVELJOINTS
C.S. PIPE WITH SWIVEL
HARD- PIPING WITH SWIVEL
RUBBER TUBE WITH SYNTHETIC WOVEN REINFORCEMENT AND
SYNTHETIC RUBBER COVER
CHEMICAL HOSE - E.P. SHIELD EPTON INDUSTRIES
1093J/KP 9/28/87
VMD 720914
DO YOU HAVE AN INSPECTION OR TESTING PROGRAM FOR THESE HOSES? PLEASE DESCRIBE. '
LOADING:
,
NO
NO COMMENT
MONTHLY VISUAL INSPECT ION
VISUAL INSPECTION
EXTERNAL INSPECTION DAILY WHEN HOOKED UP
ANNUAL EXTERNAL INSPECTION
WATER PRESSURE TEST ANNUALLY, OVA SEMIANNUAL
TWO YEAR BY ASSOC. FOR TECHNICAL INSPECTION
ANNUAL HYDRO TEST AND VISUAL BEFORE EACH USE
ANNUAL ULTRASOUND THICKNESSCHECK
1093J/KP 9/28/87
VMD 720915
V
DO YOU HAVE AN INSPECTION OR TESTING PROGRAM FOR THESE HOSES? PLEASE DESCRIBE.
UNLOADING: .
SOAP TESTED WITH EACH USE
VISUAL, OVA AND PRESSURE TESTED ANNUALLY
ANNUAL HYDRO TEST AND N2 BEFORE EACH USE
VISUAL CHECK DAILY
VISUAL CHECK DAILY
NONE - REPLACE EVERY THREE MONTHS
NO
ANNUAL HYDRO TESTED AND ViSUAL BEFORE EACH USE
PNEUMATIC TESl EVERY THREE MONTHS AND VISUAL BEFORE
EACH OPERATION
VISUAL WITH EACH HOOK-UP
DAILY VISUAL BY UNLOADER
EVERY TWO YEARS
HYDROSTATIC TRIAL EVERY THREE MONTHS, VISUAL EVERY
WEEK AND REPLACE EVERY SIX MONTHS.
NO FORMAL PROGRAM - VISc ,L BEFORE UNLOADING
ONCE PER YEAR BY CONTRACTOR
.
VISUAL INSPECTION
SEMIANNUAL VISUAL AND PRESSURE TEST
ARMS INSPECTED ANNUALLY
MONTHLY INSPECTION - HYDROSTATICALLY PRESSURE TESTED
ANNUAL, BEFORE INSTALLATION AND AFTER MODIFICATION OR
REPAIR
1093J/KP 9/28/87
72091^
WHAT TYPE Of DISCONNECT DO YOU USE IN THIS SERVICE? PLEASE
DESCRIBE.
.
LOADING:
FLANGED
FLANGED
FLANGED
HAMMER UNIONS
SCREWED - ACME THREAD
HAMMER UNION - WECO
HAMMER UNION WITH VITON "0"-RING
HAMMER UNION WITH VITON "0"-RING
FVER-TITE QUICK CONNECTORS
KAMVALOCK - EVALUATING HILLTAP
1093J/KP 9/28/87
VMD 720917
WHAT TYPE OF DISCONNECT DO YOU USE IN THIS SERVICE? PLEASE DESCRIBE.
UNLOADING:
\
FLANGED FLANGED FLANGED "UUOCK ON" COUPLING THREADED PIPE WITH UNION HAMMERLOCK W!TH "0"-RING WECO UNION HAMPER UNION HAMMERLOCK WECO WITH VITON "0"-RING WECO SCREWED FITTING REGO SCREW TYPE WECO UNION HAMMER UNION (BRASS TOOLS) OPG PROPANE FITTING EVER-TITE - KAMLOCK OPW KAMLOCK KAMLOCK OR EVER-TITE BOSSLOCK TYPE FITTING DRY BREAK - KANON
1093J/KP 9/28/87
m 72918
DO YOU REQUIRE CONSTANT ATTENDANCE BY AN OPERATOR DURING LOADING OR UNLOADING?
LOADING:
YES - 8 NO: - 0 OTHER - 2
COMMENTS:
CHECK EVERY HALF HOUR FUTURE BY TV MONITOR HIGHLY VISIBLE FROM CONTROL ROOM
UNLOADING:
YES - 12 NO - 6 OTHER - 1
COMMENTS:
OPERATOR IN GENERAL AREA INSTALLING CC TV
1093J/KP 9/28/87
720919
HOW DO YOU REMOVE THE VCM VAPORS IN THE HOSES FOR DISCONNECT? PLEASE DESCRIBE.'
LOADING: DEPRESSURIZATION TO DRUM WITH CHIMNEY TO ATMOSPHERE VACUUM COMPRESSOR BLOW INTO TANK CAR WITH N2 BLOW INTO TANK CAR WITH N? N2 PRESSURE AND DEPRESSURE PURGE WITH N2 TO INCINERATOR SMALL SPOOL PURGED WITH N2 TO FLARE RINSING WITH N2 N2 PURGE TO GAS HOLDER AND INCINERATOR PURGE WITH N2
1093J/KP 9/28/87
VMD 720920
HOW DO YOU REMOVE THE VCM VAPORS IN THE HOSES FOR DISCONNECT? PLEASE DESCRIBE.
UNLOADING:
COMPRESSORS USED TO BELOW 5 PSIG
VACUUM - COMPRESSION SYSTEM
VENTED TO ATMOSPHERE
RECOVERED TO FLARE
N2 TO GAS HOLDER. CONNECTED TO RECOVERY UNIT
VENT TO FLARE STACK
'
DEGAS TO 12 PSIG WITH COMPRESSOR
BY DRAINING IT. INERTED WITH N2
N2 PURGE TO GAS HOLDER
COMPRESSOR USED TO 10 PSIG - A" SPOOL
PULLED DOWN WITH RECOVERY SYSTEM
DOUBLE BLOCK AND BLEED TO VENT SYSTEM
PULL VACUUM ON HOSES
RECOVERED TO A 30" VACUUM
EVACUATED TO 15" VACUUM
COLD ROOM ROCOVERY SYSTEM
RECOVERED WITH VACUUM SYSTEM
EVACUATION
PRESSURE REDUCED TO 5-10 PSIG
TWO FOOT SPOOL VENTED
1093J/KP 9/28/87
VMD 720921
WHAT ARE YOUR REQUIREMENTS FOR CHOCKING AND SETTING THE BRAKES ON THE -RAILROAD CAR? PLEASE DESCRIBE.
LOADING:
SBOE PLACED ON RAIL
CAR CHOCKED AND HAND BRAKE SET
'
EACH CAR CHOCKED AND HAND BRAKE SET
CHOCKED AND BRAKES SET
BRAKES- SET AND CHOCKS IN PLACE
NO SPECIAL REQUIREMENTS
BRAKES SET AUTOMATICALLY
RAILROAD BLOCK IN FRONT AND BEHIND AND TWO WHEEL
BLOCKERS INSTALLED
BRAKES SET AND RAILROAD CAR IS CHOCKED
BRAKES SET AND PAIR OF CHOCKS
BRAKES SET, WHEELS CHOCKED, GROUND CONNECTED,
CHECKLIST USED
..
1093J/KP 9/28/87
WHAT ARE YOUR REQUIREMENTS FOR CHOCKING AND SETTING THE BRAKES ON THE RAILROAD CAR? PLEASE DESCRIBE.
UNLOADING: `
WHEELS CHOCKED ON BOTH SIDES AND HAND BRAKE SET
DERAIL, ONE WHEEL DOUBLE CHOCKED AND HAND BRAKE SET
WHEELS CHOCKED AND BRAKE SET ON EACH RAILROAD CAR
HAND BRAKE SET AND ONE SET OF WHEEL CHOCKS USED
DOUBLE CHOCK ONE WHEEL AND SET HAND BRAKE
DOUBLE CHOCK WHEELS AND CONNECT GROUND CABLE
SET HAND BRAKE, CHOCK WHEEL AND SET DERAIL
HAND BRAKE SET AND TWO CHOCKS INSTALLED
HAND BRAKE SET AND WHEELS CHOCKED
"MAN WORKING" SIGN POSTED, BRAKE SET AND WHEELS
CHOCKED
- HAND BRAKE SET AND LOCKED, WHEELS CHOCKED AND GROUND
CONNECTED
BRAKES SET AND WHEELS CHOCKED
BRAKES NQI SET, WHEELS CHOCKED AND GROUND CONNECTED
HAND BRAKES APPLIED
SPECIAL WHEEL BLOCKERS
BRAKES FREE AND SPECIAL CHOCKS FIXED ON RAIL
BRAKES APPLIED
BRAKES SET AND CHOCKS
INSTALLED.
BRAKES SET AND CHOCKS INSTALLED
1093J/KP 9/28/8/
VMD ?S0923
HAVE YOU EVER EXPERIENCED AN UNCONTROLLED RELEASE IN THE LOADING/ UNLOADING OPERATION? PLEASE DESCRIBE THE INCIDENT. THE CAUSE AND THE CORRECTIVE MEASURES TAKEN.
LOADING:
.
'
YES - 4 NO - 7
INCIDENTS:
RUPTURE OF A HOSE DUE TO DISPLACEMENT OF RAILROAD CARS BEFORE DECONNECTION OF ONE HOSE. ACTION: FLANGES WITH MALE AND FEMALE PARTS AND APPLICATION OF NEW GRAPHITED GASKETS ON EACH FILLING OPERATION.
A RAILCAR BEING LOADED ROLLED OFF THE SPOT AND SEPERATED A 2" FLEX HOSE. THE CAR WAS BEING LOADED. THE AUTO SHUT DOWN V*uVE WAS CLOSED. THE CAR WAS BACKFLOWING OUT THE LOADING VALVE. THE EXCESS FLOW DID NOT SEAT. VALVE WAS MANUALLY CLOSED. INVESTIGATION REVEALED THERE WAS NO PROPER CHECKING PROCEDURE AT THAT TIME. CARS ARE NOW REQUIRED TO BE CHOCKED A AND B END AND HAVE HAND WHEEL BRAKE SET PRIOR TO LOADING.
v YES. ORIGINAL HOSES WERE 3" CARBON STEEL TUBE AND EXTERNAL BRAID. HOSE WAS APPROXIMATELY NINE MONTHS OLD. BRAID WAS CORRODED AT THE END FITTING AND SEPERATED. A RUPTURE OCCURRED. CAR XS FLOW VALVE SEATED AND LOADING VALVE ON ROCK WAS MANUALLY CLOSED. INSTALLED MANUAL REMOTE SHUTDOWN VALVES CHANGED TO STAINLESS BRAIDED HOSE AND NON-METALLIC HOSES PLUS FREQUENT HOSE INSPECTIONS.
A HOSE FAILURE OCCURRED APPROXIMATELY FIVE YEARS AGO. AT COMPLETION OF LOADING THE MANUAL LIQUID VALVE AT THE T/C LOADING STATION #1 WAS CLOSED. THE LOADING OPERATOR STARTED WALKING TO THE NEXT T/C TO CHECK ITS PROGRESS. AFTER HEARING A NOISE HE TURNED TO SEE THAT THE HOSE AT #1 HAD COMPLETELY SEPERATED AT THE RING THAT COUPLES THE INDIVIDUAL HOSE COMPONENTS TO THE FLANGED SECTION. THE T/C EXCESS FLOW VALVE CHECKED SO THAT ONLY THE CONTENTS OF THE HOSE WERE SPILLED. ThE CAUSE OF THE FAILURE WAS IMPROPER ASSEMBLEY BY THE HOSE MANUFACTURER.