Document a47KONomRpvMOyowzEEOKp0M
620
CHAPTER 23
1958 Guide
Table 1. Thermal Resistance of Plaster and Metal Ceiling Panels
Spac
ing
in.
Thermal Resistance to Down-
ward Heat Flow (rd) . (F deg) (hr) (sq ft) per Btu ,
Heat Flow Ratio, qQ/q&
Plaster Panels15 Standard Gypsum Plaster, Three
Coats
' SPACING
TUBES OR P1PCS
H in. (nom.) non-ferrous tube or Yi in. (nom.) fer
rous pipe above metal lath tied at 8-inch intervals
with good tube embed ment,or in. (nom.) non-
METAL LATH
ferrous tube below metal or gypsum lath.
/METAL OR
/'GYPSUM LATH
0 0.2 0.4 0.6 0.8 1.0* 4H 0.30 0.34 0.38 0.42 0.46 0.50 6 0.45 0.61 0.57 0.63 0.69 0.75
9 0.75 0:85 0.95 1.05 1.15 1.25 12 1.16 1.29 1.43 1.57 1.71 1.85
^VuBES
Aluminum Panel0 >6 in. Minimum Thickness
TUBES ^ SPACING
\j*A n
Q iO CT
t-FLANGC
ALUMINUM
pipe or tube installed so that excellent heat con
duction to ceiling surface is obtained.
3
0.07 0.07 0.07 0.07 0.07 0.07
Any ceiling panel also acts as a floor panel to the extent of its upward heat flow. If the upward heat flowjs high and the space above is occupied, check floor surface temperature for possible foot discomfort (see Rtference 7). Also check effect on heating requirements of the space above. It is not good practice to have the major portion of the upper room's heating requirements supplied by the upward neat flow of a ceiling panel below.
b Recommended maximum inlet water temperature (tmax) 140 F. '
fl Recommended maximum inlet water temperature Umax) 220 F.
quired. Also in Table 1 find the resistance of each panel (r<t), using heat flow ratios calculated from the flow rates determined in Steps 2 and 4, interpolating as required.
Room
Spacing (Inches)
Heat Flow Ratio
Resistance (rd)
A B9 C9
12.5 -- = 0.26 47.7
6 --- = 0.30 19.7
5 ----- = 0.19 26.1
0.35 0.90 0.85
Step 6. Mean Water Temperature
For the required panel output (qi) found in Step 2, the panel resistance (rd) found in Step 5, and the room air temperature (fa), find the mean water temperature (flaw) from Fig. 15. This use of Fig. 15 is illustrated in Fig. 15B.
Fig. 15B. Determination of Mean Water Temperature for Room A from Fig. A from Fig. 15
Paiiel Heating
Values of fmw for Rooms A, B and C as determined from Fig. 15 are as follows:
Room A fmw = 131 F, Room B fmw = 110.5 F, Room C = 119 F
Step 7. Design Mean Water Temperature
Select a single design mean water temperature (fdmw) for each group of rooms which is to comprise a zone, choosing the highest mean water temperature (lm.) of the group subject to the following:
a. If fmw + 2"^" *s e0ual t or less than fmx (see Nomenclature and Table 1,
this mean water temperature (fmw) is an acceptable design mean water temperature (fdmw). Proceed to Step 8.
b. If fmw + ^ l^ is greater than f,,xx , go back to Step 5 and select a panel con
struction which has a lower panel resistance (rd). This can. be accomplished by either or both of the following:
1. Reducing the tube spacing, ^
>;
2. Decreasing the upward heat flow (qa) by providing additiohal insulation above the panel.
If the required mean water temperature is still too high apply either or both of the following:
1. Reduce the heat loss of the room,
2. Provide supplementary heating.
In Example 1, assume f, -- f,, = 15 F deg and tmMI = 140 F. Then since fmw = 131 F, f,,w 4- % (ft -- to) -- 138.5 F and is less than f,,xx . Thus 131 F can be used as the design mean water temperature ldmw
Step 8. Design Panel Output
From Fig. 15, find the panel output (gd) for design mean water temperature (fdmw), room air temperature (f) and panel resistance (rd). Fig. 15C shows how Fig. 15 is used to find qd for Room B in this step.
Fig. 15C. Determination of Design Panel Output for Room B from Fig.. 15
The mean water temperature (fmw) found for Room A in Step 6 was used as the
design mean water temperature (fdmw). The panel output for Room A which was
determined in Step 2 is therefore the .design panel.output for this room. Design
panel outputs for Rooms B and C can be found from Fig. 15 using the design mean
water temperature (fdmw).
./
Room
A B C
Design Panel Output (ga) . BTU per (hr) (sq ft)
47.7 32.5 33.