Document a1xwQ7DpYvoRkQao36n3DxzZN
HEATINC VENTILATING AIR CONDITIONING GUIDE 1943
it is not practical to install a hood 2 ft high it is recommended that the face velocity be increased from 100 to 150 fpm, depending on peak load con ditions in the kitchen. Exhaust connections to range hoods should always be made at the top and back of hoods, and should be spaced pref erably not more than 6 ft apart and be rectangular in shape with the long side parallel to the back of the hood. Exhaust openings into, range hoods should be designed to maintain a velocity of 1500 to 1800 fpnri
An approved fire damper with fusible link should be (and is required by code in many states) installed in the main exhaust duct or branch adjacent to the range hood. Should there be more than one hood con nected to a common duct, then the branch duct to each hood should be provided with a fire damper. Access doofs should be provided at the fire damper for purpose of inspection, cleaning or for renewal of fusible link. All exhaust piping to range hoods, commonly- called grease ducts, should be provided with tight fitting cleanout doors of adequate size to permit easy removal of grease.
Hoods over steam tables should be of similar construction to range hoods. In determining the necessary amount of air to be exhausted it is considered good practice to design such hoods with a face velocity of 60 to 70 fpm. Hoods over dishwashing machines are usually relatively small and generally 1500 to 2000 cfm per hood is allowed, which is equivalent to a velocity of approximately 100 fp/n per square foot of face area. Range hoods in diet kitchens are constructed the same as restaurant range hoods but with less exhaust air per square foot of face area, depending upon the nature of the food cooked.
Hoods are not often used in private residences unless they are quite large and the consideration of expense is not important. For such residences the hoods should be designed on the same basis as diet kitchens. Most all residence kitchens can be effectively arid economically, venti lated by the installation of a built-in kitchen ventilator, which should be located in an outside wall and in close proximity to'the kitchen range. It has been found that the capacity of the built-in kitchen ventilator should be at least 350 cfm regardless of the size of kitchen.' This can be justified on the basis that the smaller the kitchen the more concentrated the heat will be thus requiring a more rapid rate of air change: Standard' size built-in kitchen ventilators are generally available in. three sizes, namely 350, 500 and 800 cfm. The proper size to use will depend on' design conditions and available wall space.
\
DUCT SYSTEM DESIGN
In designing a duct system it is necessary to recognize a few funda mental principles (see also Chapter 32). Knowing the. quantity of air required, the size of the.duct may be computed from Equation 5:
A = cross-section area of duct, square feet. Q = air quantity to be handled by the duct, cubic feet per minute. V = velocity of air, feet per minute.
740
CHAPTER 40. INDUSTRIAL EXHAUST SYSTEMS -
Table 5., .Gages of Metals for Exhaust System
Duct Diameter. In.
9 to 18............................;........... 18 to 30.............................. .......
Dust
20
18 16 14
Gage of Metal
Non-Corrosive Fumes. Vapors and Gases
24"
22 20
18
Air Velocities in Ducts
Where it is riecessary to transport the particulate material collected in an exhaust system, minimum carrying velocities must be maintained in the ducts preceding the collector. It has been found that good design results
" when air velocities in horizontal runs are not less than 3000 fpm or not greater than 5000 fpm. When the dust being carried is organic and other than wood flour, or similar material, a velocity of. 2500 fpm is adequate. The velocity in vertical piping should be increased 25 per cent over the minimum required for transport in horizontal ducts.
For duct.systems wherein the air has no dust or solid load, a lower
velocity is desirable, which may range from 1200 to 2000 fpm.- In view of the fact that the horsepower required by a system depends directly
on the resistance and the resistance is a function of the velocity, eco nomical design requires velocities of this, magnitude.
The equal friction method is generally used for designing a duct system as this insures equal resistance to air flow in all branches throughout the system (see Chapter 32). Long main ducts do not generally provide the ' most economical layout. Where it is necessary to ventilate a large number
of-machines, or machines which are widely separated, it is desirable to
locate the fan at approximately the center of the system: With this
arrangement it is possible to choose a fan which will deliver the required
air quantity against a lower resistance pressure, and this will generally
result in a horsepower saving.
When a system carrying dust is designed with an oversize main duct to allow for future extension, the air velocity may be' found to be too low to
carry the dust, and serious plugging may occur. In this case it is desirable to install an orifice in the end of the pipe to allow for the lower air quantity.
Construction
The ducts leading from the hoods to the exhaust fan should be con- ; structed of sheet metal not lighter than is shown in Table 5: The piping should be free from dents, fins and projections on which refuse might. catch.
All permanent circular joints should be lap-jointed, riveted and sol dered, and all longitudinal joints either grooved and locked or riveted and soldered. Circular laps should be. in the direction of the flow, and piping installed out-of-doors should not have the longitudinal laps at the bottom. Every change.in pipe size should be made with an eccentric taper flat on the bottom, the taper to be at least 4 in. long for each inch"
741