HEATING VENTILATING AIR CONDITIONING CUIDE 1941
seasonal efficiency and is designed to maintain an average inside temperature of fis c
when it is 10 F outside in a city where the average outside temperature is 45 F anriftf
heating season is 5088 hours long?
tllf
Solution. The area of the round leaders is: 12 in., 113 sq in.; 10 in., 79 sq in , ,
8 in., 50 sq in. From Table 1 the total Btu transmitted is:
'' 1,11
First Floor: [(4 X 113) + (2 X 50)) X 111 = 61,272 Btu per hour.
Second Floor: (6 X 79) X 167
= 79,158 Btu per hour.
Total 140,430 Btu per hour. Allowing 10 per cent for duct and furnace losses, the gross output would be 154 vin Btu per hour.
1 ' * ' ` 1 ' " i i i i | j i i li--i--i--i |-i i -f i--i--i--r--i--i--r
O5
IO
IS
20 25
30
GROSS OUTPUT* HUN0RED FEET WATER RAOIATION
Fig. 3. Gas Fuel Burning Rate Chart
Enter Fig. 3 at 154.5 on the upper horizontal scale, move to the 70 per cent efficiency curve and thence to the 500 Btu per cubic foot vertical scale and find ^ -^=. ^ to be ap
proximately 440 cu ft per hour. Substituting in Equation 2:
F = 440 X
(65 - 45) 5088 (70 - 10)
= 746,428 cu ft.
Maximum Rate of Fuel Burning
The rate at which fuel is burned during the maximum, or design hour, is frequently useful in setting, or adjusting, the fuel feed devices attached to
<#c)stokers, oil-burners, and gas burners. This rate
and can be found
from the charts of Figs. 1, 2 and 3 in the same way as outlined in the
Examples 4 and 5. In using the charts for this purpose, however, it
should be noted that the efficiency (E) is the overall efficiency of the boiler
210
CHAPTER 10. HEAT AND FUEL UTILIZATION :
are at the time of peak load. This efficiency is generally considerr turn ^ ^an value selected for E when the seasonal efficiency of
r ^tion is used in making seasonal fuel estimates. Failure to disuUlizau ketween the two essentially different meanings attached to E
mavUresult in grossly inaccurate estimates.
The correct fuel burning rate can be determined directly from the 1 " 1 charts for oil or gas burning installations, as these customarily ^rate on a strictly intermittent basis. These fuel burning devices 0Pnallv introduce the fuel at a single fixed rate during the on periods and tVs rate should be sufficient to carry the gross or maximum design load. I the case of coal stokers, which are usually capable of variable rates of fiine it is desirable to operate at as low a rate as weather conditions will n^rmi't but the maximum firing rate of the stoker should be sufficient to carry the gross load. This rate may be determined by the same method
as used for oil or gas.
Table 1.
Heat Carrying Capacity of Gravity Warm Air Furnace Round Leader Pipes
180 F Register Temperature
Leader Pipe
Btu per Hr at Design Conditions per Sq In, op Leader Pipe
hi
167 200
Example 6. The estimated net load (including domestic hot water supply) as calcu lated for a residence is 1500 sq ft of hot water radiation. Determine the firing rates for various mechanically fired fuels assuming an overall boiler efficiency of 70 per cent; using coal with a calorific value of 12,500 Btu per-pound; No. 3 fuel oil and natural gas having a gross heating value oflOOO Btu per cubic foot.
Solution. Referring to Fig. 1, Chapter 11, a piping and pick-up factor for a net-load of 1500 sq ft is found to be 43 per cent or the gross output is equivalent to 1500 X 1.43 = 2145 sq ft of hot water radiation.
Using the charts in Figs. 1, 2 and 3 project vertically from the gross output value on the proper horizontal scale to the intersection of the 70 per cent efficiency line. From the intersection of this line proceed horizontally to.the proper vertical scale where a direct value of the required fuel burning rate is given. These values are rates of burning while firing device is in operation and are not indicative of hourly fuel consumption.
By use of the respective charts the firing rates for the various fuels will be found to be: coal 36.8 lb per hour, oil 3.2 gal per hour, and gas 460 cu ft per hour.
DEGREE-DAY METHOD
This method is based on consumption data which have been taken from buildings in operation, and the results computed on a degree-day basis. While this method may not be as theoretically correct as the Calculated Heat Loss Method, it is of more value for practical use.
The amount of heat required by a building depends upon the ou'. doortemperature, if other variables are eliminated. Theoretically it is pro portional to the difference between the outdoor and indoor temperatures: Some years ago the American Gas Association2 determined from experi-
'See Industrial Gas Series, House Heating, (third edition) published by the American Gas.Association.