Document Zx1gGzN57Om5864Y63Zo3qN8
i
Monsanto
IONI A.FROM (NAME & LOCAT L. Rasmussen, Krummrlch
DATE SUBJECT REFERENCE
TO
March 5* 1971 . WASTE AROCLOR DISPOSAL KEY PREMISES REVIEW
'
CC: Messrs. W. Bo Papageorge J. R. Savage R. M. Kountz
W. R. Richard W. C. Engman A. E. Leisy R. M. McCutchan^
Messrs.
A. L. Rasmussen - Manufacturing Representative
N. B. Wolk
- CED Project Manager
Q. E. Thompson - Research Representative
The above three people met to review the "key premises"
for the Waste Aroclor Disposal project, CEA 2415. We
agreed that all of the key premises as stated in our
memo of 12/7/70 are still valid. In addition, we added
premise #9. -
.
--
Key premises:
-
1. The incinerator-scrubber package will perform as designed.
This system is being purchased from John Zink Company, consequently Monsanto is relying upon Zink's technology. Two days of tests on Aroclor materials were run at Zink's pilot plant. A performance warranty has been signed which specifies rates, efficiency, pollution emissions, etc.
2. The incinerator has sufficient capacity to burn all waste PCB liquids returned over the next 2-3 years.
At the present time, it is impossible to predict how much PCB will be returned. A completely ''closedsystem" return for incineration of PCB's manufactured would greatly overload the incinerator. Installation of a solids burning system in conjunction with the incinera tor could require 1/3 of the incinerator capacity.
3. The incinerator, will satisfactorily dispose of PCB liquids containing contaminants.
The tests at Zink were run only on pure Aroclors, Montar, and Inerteen PPO. We know that the PCB liquids being returned contain various contaminates such as mineral oil, kerosene, xylene, etc. Since these materials can be considered fuels, they should present no major difficulty In incineration.
DSW 295494
STLCOPCB4065542
Messrs. N. B. Wolk, Q. E. Thompson WASTE AROCLOR DISPOSAL KEY PREMISES REVIEW ________
Page 2
3/5/71 W.G.K.
3. (cont'd.)
Some Pydrauls are also to be incinerated. Mixing Pydrauls (containing phosphate esters) with 1260 Aroclor could produce a mixture difficult to burn. With the small quantities involved, we do not feel it justified to run further tests (rJ$1500 cost) at Zink at this time.
4. The materials of construction will have an acceptable life.
The materials were selected on the best knowledge available to CED and WGK materials specialists. However, these selections were based on anticipated conditions and no corrosion tests have been made.
5. The tight PCB emission criteria to the sewers can be met without additional treatment of the sewered streams.
The overflow water from the settling basin and the HC1 stream from the scrubbing tower will go directly to the sewer. The project carries some money in undeveloped design for a carbon absorption or other system. However, technology is not currently available for designing such a system.
6. The Mon tar pickup and handling system will function as envisioned.
Several problems may prove themselves difficult to resolve:
a) Pumping the high-crystallizing point Montars.
b) Proper mixing of the 1242 and Montars.
c) Settling out of the lime.
7. The-incinerator must operate on a round-the-clock, 7 day a week basis.
The present state of knowledge relative to costs, safety, and maintenance dictate such a mode of operation. The Incinerator will be started-rup in this manner.
Initially, we plan to run full-out until inventories are exhausted and then shut down. This will require part-time supervision - possibly the Dept. 246 supervision.
Experience may dictate another method of operation for subsequent runs.
DSW 295495
STLCOPCB4065543
Messrs. N. B. Wolk, Q. E. Thompson
WASTE AROCLOR DISPOSAL KEY
PREMISES REVIEW __________
__ __
Page 3
3/5/71 W.G.K.
8. The Aroclor incinerator will be able to burn other combustible waste generated by Monsanto.
This assumption is in the back of most people's minds. However, this assumes, a) the incinerator will have excess capacities, b) all materials of construction are compatible, and c) the products of combustion will be scrubbed out in the existing system.
Each proposed material for incineration will need to be considered separately and some sort of tests likely run.
9. The Aroclor incinerator will meet all State and Federal criteria and regulations to permit operation.
An Installation Permit Application has been filed with
the Illinois Environmental Protective Agency. This
permit must be approved before the incinerator can
start-up.
.
/gjs
A. L. Rasmussen Manufacturing Representative
os***5496
STLCOPCB4065544