Document Zn5R5aEvDEkgQOv80qJ48ay0
INDUSTRIES PPG INDUSTRIES. INC. INDUSTRIAL CHEMICAL DIVISION P. 0. BOX 1000 LAKE CHARLES, LA. 70602
March 13, 1984
Mr. Gus Von Bodungen Department of Environmental Quality Air Quality Division Office of Environmental Affairs P. O. Box 44066, Capitol Station Baton Rouge, LA 70804
Dear Mr. Von Bodungen:
RE: VCM LESHAP Quarterly Report
In accordance with LESHAP Regulation 77.11, PPG Industries' Lake Charles Complex herein submits its quarterly report for the period of December 1, 1983 through February 29, 1984.
A record of one-hour emissions in excess of the 10 ppm standard in the stack gases exiting each incinerator system is attached as Exhibit I.
During this quarter approximately 576 pounds of VCM were released due to
failure to incinerate vent gases. One such instance, as indicated below, exceeded forty minutes in duration.
Date
Time/Duration
Reason
Estimated Quantity VCM Emitted
2-8-84
1 :Q6 - 2:06 PM
Emergency maintenance
33 lbs.
on vent header to
incinerators
Very truly yours.
UJifcAaJIP
James E. Wyche, III Coordinator, Environmental Systems
/bh
SL 026319
EXHIBIT I
Continuous Stack Emission Results >10 ppm VCM Decembeir 1, 1983 - February 29,
00
Stack No. 1 (Incinerators #1 and #2)
Date
Hour Ending
Hourly Average (ppm )
Comment
12/4/83
5:00 p.m.
11.24
Surge in vent flow to incinerator
12/8/83
2:00 p.m.
10.57
1/26/84
3:00 p.m.
172.51
Vent isolation valve slow to close following incinerator trip
Stack No. 2 (Incinerator #3)
Date
Hour Ending
12/8/83
9:00 p.m.
12/9/83
10:00 p.m.
12/10/83
5:00 p.m.
12/11/83 10:00 p.m.
12/12/83 7:00 a.m.
12/24/83 2:00 a.m.
12/31/83 12/31/83 1/29/84
9:00 p.m. 11:00 p.m. 4:00 p.m.
Hourly Average (ppm )
Comment
. 43.19
Incinerator tripped and restarted this hour
10.36
Upset by liquid waste feed stream
19.81
Incinerator tripped and restarted this hour
41.23
Incinerator tripped and restarted this hour
43.12
Upset by liquid waste feed stream
29.24
Incinerator tripped and restarted this hour
165.30 51.74
Incinerator tripped
27.91
Upset of liquid waste feed stream
SL 026320
EXHIBIT I
Continuous Stack Emission Results > 10 ppm VCM Page 2
Date 1/29/84 2/6/84 2/7/84 2/7/84
Hour Ending 5:00 p.m.
10:00 p.m. 7:00 a.m. 8:00 a.m.
Hourly Average (ppm) 35.74 10.51 29.37 15.48
Comment
Incinerator tripped and restarted this hour
Upset in flows to incinerator
Upset in flows to incinerator
Upset in flows to incinerator
SL 026321