Document Zax5gBw1Z1vE7ROXzxNm86MJ
A Guide to Accumulation and Shipment of WASTE ASKAREL FLUIDS
Note: The following instructions are intended only as a guide. For additional instructions refer to the ANSI CI07 document, "Guidelines for Handling and Disposal of Capacitor and Transformer Grade Askarels, Containing Polychlorinated 8iphenyls", available from the American National Standards Institute, 1430 Broadway, New York, New York 10018.
SAFE HANDLING OF ASKAREL FLUIDS
VSkarel fluids contain Polychlorinated Biphenyls (PCBs). Care should
te taken to prevent entry into the environment through spills, leakage,
.use, vaporization, or disposal of liquid or containers. Avoid prolonged
trsthing of vapors or mists. Avoid contact with eyes or prolonged
sontact with skin. If skin contact occurs, remove by washing with
ssap and water. Following eye contact, flush with water. In case of
spillage onto clothing, the clothing should be removed as soon as skin washed, and clothing laundered. ACCUMULATION of haste fluids
DRUMS - WHAT TO USE fuL-gallon drums: Must be 18-gauge steel or heavier and have a
'
2-bung head. S.-gallon drums: Must be 24-gauge steel or heavier. (Drums must meet DOT 17-E specifications)
CO NOT USE:
Old drums
Rusted drums
Corroded drums
Damaged drums Drums with weak walls or seams
0483637
I TOWOLDMON0033268
WATER_PCB-00017737
LABEL DRUMS Drums used for waste askarel fluids should be labeled as to contents and with the above "Safe Handling" statement or its equivalent.
FILLING DRUMS
'
Liquid Waste Only
Keep all solid materials out of drums used for waste askarel liquid. Solid materials (sludge, rags, paper, sawdust, metal parts, floor sweeping
chemicals, etc.) must be accumulated and disposed of separately.
Contact your environmental department for proper disposal methods
for solid materials.
Keep water out of drums Waste askarel fluids shipped to Monsanto for incineration must not
contain more than 12 water, or possible damage to the incinerator
may result.
Do not overfill drums Airspace is needed to allow for possible thermal expansion of the fluid:
Minimum airspace: 55-gallon drums -- 1 1/2 - 2 inches 5-gallon drums -- 1 inch
Failure to leave sufficient airspace can result in possible fluid
leakage or seam failure due to pressures caused by fluid expansion.
SEALING DRUMS
Use a proper bung. Inspect the bung and the drum opening
to Insure tight, leak-proof seal.
.
Do not use damaged bungs, rags, pieces of wood, or other inappropriate
materials to seal drums.
.
STORING FILLED DRUMS PRIOR TO SHIPMENT
If askarel-filled drums must be stored prior to return to Monsanto:
Inspect Drums for Leakaoe Inspect drums for leakage around seams and bung, making sure
0*63636
TOWOLDMON0033269 WATER_PCB-00017738
f
3
all seals are tight and leakproof.
Clean Up Spillage lcan the outside of the drum of any spilled fluids, following approved .cleaning methods. Properly dispose of materials and any water used to
Clean drums. .Store In Protected Area
Drums should be stored in an enclosed area where they will be protected
from possible damage and inclement weather.
.In .Exposed Areas Store On Sides
ilf drums must be stored in an exposed area, store drums on their sides
.with ioth bungs below the fluid level so that rain water will not
accumulate on the top of the drums. (As drums "breathe", water can be
drawn into the drum through the bung seal). Use blocks or other device
-to keep drums stationary.
iCo .'rot Stack
'
JJo-not stack drums, whether stored on their sides or on end.
.
In-plant drum transportation _U*a? Proper Drum-Handling Equipment
iAsUrcl.-filled drums should be moved only with proper drum-grabbing
tfkvice. A parrot beak type of drum-grabbing device will reduce the
jtqss'pnmy of damage to drums. Common drum handling devices of this
type are the Lift-O-Matic, manufactured by Marvel Industries, or the
Vurt-O-Matic drum carrier.
Pellets Not Recommended
,
.Askerel-filled drums should not be palletized. If pallets must be used:
. sore pallets are properly constructed and undamaged to minimize
possibility of the drum falling from the pallet while being
transported.
'
0*83639
TOWOLDMON0033270 WATER_PCB-00017739
4
. SteeUband all drums to their pallets.
Drums should be banded together horizontally as well as vertically
to the pallet.
.
. So that four drums can be loaded across the width of a truck to
prevent shifting in transit, multiple (2 or 4) drum pallets should
be no more than 46 inches wide. bRUH LABELING
The following procedure must be adhered to for labeling askarel-filled
drums shipped to Monsanto. For EACH Shipment:
.
IA. Contact: Mr. C. R. Field
.
Monsanto Company
'
800 N. Lindbergh Boulevard
'
St. Louis, Missouri 63166
(314) 694 3024
IB. Supply the following information to Mr. Field:
'
. Number of drums in the shipment.
. Name and address of person to receive drum labels.
. Purchase order number, if a specific number is to be used.
,, Anything out of the ordinary about the fluid or the
shipment.
VC. Mr. Field will then send the following:
. Letter of authorization for the shipment
. Pre-addressed shipment/warning labels for each drum.
. Carrier's Advisory Note to be attached to the bill of
lading
. Terms of shipment and charges, if any. Upon receipt of above materials:
?. -Fill in EACH label with Monsanto identification number,
.product description and YOUR telephone number.
0<t836<i0
i
TOWOLDMON0033271 WATER_PCB-00017740
3. Label EACH drum
5
4. Put Monsanto identification number and your telephone number
on Carrier's Advisory Note and attach to bill of lading.
LOADING and shipment . . Perform a final check for leakage, damage, and to assure bungs
are tightly sealed. . Load and secure drums to prevent shifting in transit. . If shipment is part of a mixed consignment, be certain drums are
stowed away from any human or animal feedstuffs or pharmaceuticals. . Be certain driver is aware of Carrier's Advisory Note and telephone
numbers in case of leakage or other problems. . Do not ship via piggyback.
Please note: Monsanto checks all shipments upon arrival. Failure to adhere to above guidelines could result in fluids being returned to the shipper and additional charges assessed.
Monsanto (logo)
4
0483641
TOWOLDMON0033272 WATER_PCB-00017741