Document ZJZJGpLwjGkMNJRQwJzQ0ML6p
HEATINC VENTILATING AIR CONDITIONING GUIDE 1940
Medical and nursing care is complicated, as the tent must be opened or removed with attendant loss of oxygen. Oxygen concentrations of 50 per cent or more are difficult to maintain, and it is a problem to keep the temperature and humidity low enough in hot weather. The direct advantages are portability and low cost.
Oxygen Chambers
The conventional oxygen chamber is an air-tight sheet metal enclosure of fire-proof construction, large enough to accommodate one or two patients. Trap doors or curtains are provided for the personnel, food and service, to avoid loss of oxygen. Glass windows in the ceiling and walls admit light from outside the chamber.
The air conditioning system may be of the gravity type, or of the fan type using mechanical refrigeration or air drying agents. The gravity system includes a bank of cooling coils controlled thermostatically, which dehumidify and cool the air. The cool air falls over trays of soda lime at the bottom of the coils, to remove the carbon dioxide given off by the occupants. A heater at the base of the opposite wall warms the air to the desired temperature. Ordinary industrial oxygen is introduced from storage tanks outside the chamber and the concentration is regulated according to the prescription of the physician. The only change of air in the chamber is that taking place by air leakage through the trap doors.
The chief objections to the gravity circulation system are stratification of cold air near the floor and accumulation of odors, which may require the use of activated charcoal, or an excess of oxygen fo'r dilution of the
air in the chamber. The. fan circulation systems include compact extended surface coolers,
heaters, and sometimes air-drying beds installed outside the chamber for
the removal of moisture. The temperature and humidity requirement in oxygen therapy depend
primarily upon the physical condition of the patient, and secondarily upon the type of disease.. In pneumonias, according to Bullowa19, prescribed conditions should be an effective temperature of 66-68 F, humidity of 50 per cent, air movement of not less than 50 linear feet per minute, oxygen concentration of 50 per cent, and carbon dioxide of less
than 1 per cent. Oxygen chambers are more comfortable than oxygen tents. The
patients receive unhampered medical and nursing care, and the oxygen concentration, the temperature and humidity can be adequately con trolled at any desired level. The chief disadvantages are high initial and operating costs in comparison with oxygen tents or with the nasal catheter method of oxygen administration. The nasal catheter method is the simplest and most inexpensive of all but it may cause considerable discomfort to the patient and it is not satisfactory for continuous admini stration nor for restless or delirious patients. Moreover, oxygen con centrations greater than 40 per cent in the inspired air are difficult to maintain, although concentrations as high as 48 per cent have been
obtained.
"The Management of Pneumonias, by J. G- M. Bullowa, 1037. p. 260.
582
CHAPTER 3Z AIR CONDITIONING IN THE TREATMENT OF DISEASE
GENERAL HOSPITAL AIR CONDITIONING
Complete conditioning of a large hospital involves a capital investment and running expense which may not be justified. In clean and quiet districts, the requirements of almost all general and private wards during the cool season of the year can be satisfactorily fulfilled by the use of usual heating in conjunction with window air supply and gravity or mechanical exhaust. Insulation against heat and sound is much more important than humidification in winter; it will also help considerably in keeping the building cool in warm weather. Excessive outside noise oapnedndinugsst. may require the use of silencers and air filters in the window
Cooling and dehumidification in warm weather are important. In new hospitals particularly, the desirability of cooling certain sections of the building should be given serious consideration. Financial reasons may preclude the cooling of the entire building, but the needs of the average hospital can be met by the use of built-in room coolers and a few portable units which can be wheeled from ward to ward when needed. Objection able noise is an important drawback to the use of self-contained units, but the difficulty is gradually being overcome by improvements in design.
In the North and certain sections of the Pacific Coast, cooling is needed but a few days during summer, while in the South, it can be used to advantage from May to October, and in tropical climates almost con tinuously throughout the year.
Aside from comfort and recuperative power of the patients, cooling is of great assistance in the treatment of fevers in the new-born and in post-operative cases, in enteric disorders, fevers, heat stroke, heart failure, and in a variety of other ailments which often accompany summer heat waves.
Considerable research is in progress on the influence of air conditioning upon a wide variety of diseases such as pneumonia, upper respiratory diseases, tuberculosis, arthritis, nervous instability, hyper-thyroidism, essential hypertension, skin diseases, and vascular disorders.
REFERENCES
Engineering in the Hospital of Tomorrow, by Charles F. Neergaard (A.S.H.V.E. Transactions, Vol. 40, 1934, p. 303).
Hospitals Benefit in Five Ways from Air Conditioning, by Howard E. Bishop (Hospital Management, July, 1934).
Air Conditioning for Hospitals, by John Paul Jones and Victor B. Phillips (Modern Hospital, November, 1936).
Committee on Air Conditioning {American Medical Association, A.M.A. Journal, 1937: Vol. 108, p. 1531, 1708, 2209: Vol. 109, p. 945, 1802. 1938: Vol. 110, p. 1479, 155, 2603: Vol. Ill, p. 44, 1647).
The Economical Hospital Plant as a Fundamental Factor in Economical Hospital Service, by James Govan (Hospitals, January, 1937).
Bactericidal Radiant Energy for the Operating Room, by Deryl Hart (Archives Surgery, May, 1937, 34:874).
The Extent of Air Conditioning Requirements from the Standpoint of Hospital Administration, by James Goven (Hospitals, January, 1938).
583