Document ZJOGyrExNJrxmMwrR0qa8gEm8

174 CHAPTER 12 1960 Guide A fioea or Spec* Bedroom A and Bedroom B and Closet Bedroom D and Bathroom 1 living Room Dining Room Kitchen and En- trance to Garage bule Entrance Hall Recreation Room* Toble 9 .... Heat Loss Calculation Sheet for Uninsulated Residence (Fig. 1) B C0 E F Pari of Structure or Infiltration Air Not Area or Air Volume CoofficMfll Temp. Diff.* Heat lets (Sfv per hoar) Walls Glass Infiltration (K)` 238 sq ft 40 sq ft 252 sq ft 1510 ctnb 0.29 0.45 0.74 0.018* 80 80 39.8* 80 5520 1440 7410 2180 Walls Glass Ceiling Infiltration (K)f 156 sq ft 40 sq ft 170 sq ft 1020 cfhb 0.29 0.45 0.74 0.018* 80 80 39.8d 80 3620 1440 5000 1470 Walls Glass Ceiling Infiltration (K)' 114 sq ft 27 sq ft 129 sq ft 874 cfhb 0.29 0.45 0.74 0.018* 80 80 39.8d 80 2650 970 3800 1260 Walls Glass Ceiling Floor over garage Infiltration (K) 118 sq ft 20 sq ft 110 sq ft 110 sq ft 660 cfhb 0.29 0.45 0.74 0.26 0.018* 80 80 39.8d 35* 80 2740 720 3240 960* 950 Walls Ceiling Infiltration (1)* 30 sq ft 55 sq ft 440 efnb 0.29 0.45 0.74 0.018* 80 80 39.8d 80 690 500 1620 630 Walls Ceiling Floor over garage Infiltration (1)* 79 sq ft 9 sq ft 35 sq ft 35 sq ft 280 ctnb 0.26 0.45 0.74 0.26 0.018* 80 80 39.8d 35* 80 1640 320 1060 320* 400 Walls Walls (adjoining garage) Glass Floor Infiltration (lK)h 267 sq ft 94 sq ft 50 sq ft 294 sq ft 3745 efhb 0.29 0.39* 0.45 0.018* 80 35* 80 80 6200 1280* 1800 5400 Walls Glass (doors) Glass (windows) Floor Infiltration (IK)1 166 sq ft 35 sq ft 20 sq ft 168 sq ft 2140 cfnb 0.29 0.85 0.45 0.018* 80 80 80 80 3850 2380 720 3080 Walls Walls (adjoining garage) Glass Door Floor Infiltration (IK)1 96 sq ft 51 sq ft 18 sq ft 17 sq ft 125 sq ft 1595 efhb 0.29 0.39' 0.45 0.51 0.018* 80 35* 80 35 80 2220 700* 650 300 2300 Walls Walls (adioinine earoeel Glass Door Floor Infiltration (lK)k 82 sq ft 85 sq ft 9 sq ft 19 sq ft 30 sq ft 383 cfnb 0.29 0.39* 0.45 0.51 0.018* 80 35* 80 80 80 1900 1160* 320 780 550 Walls Door Ceiling' Infiltration (2)1 39 sq ft 21 sq ft 87 sq ft 1110 cfnb 0.29 0.38 0.74 0.018* 80 . 80 39.8d 80 900 640 2560 1600 Walls Glass Doors Infiltration (IK) Floor Gain adjoining rooms 167 sq ft 53 sq ft 44 sq ft 2360 cfhb 29 ft* 0.29 1.13 0.51 0.018* 0.81 45* 45 45 45 45 2180 2700 1010 1910 1060 -4420* Walls Glass Infiltration (1)* 220 sq ft 8 sq ft 287 sq ft 2010 cmb 0.10 1.13 0.10 0.018* 38 80 20 80 840 720 570 . 2890 TOTAL G Totals (6Ja per hoar) 16,550 11,530 8,680 8,610 " 3,440 3,740 14,680 10,030 6,170 4,710 5,700 4,450 5,020 103,310 Heating Load 175 Notes for Table 9... Heat Loss Calculation for Uninsulated Residence (Fig. 1). * The indoor-outdoor temperature difference is 70-- (--10) or 80 F except where otherwise noted. b Volume of infiltration, cfh * (no. air changes) x (floor or ceiling area) x (ceiling height). * From Equation 5a. d The ceiling heat losses are calculated by estimating the attic temperature and then calculating the loss through the ceiling lining the propet temperature difference. This unheated attic is not ventilated during winter months. The attic temperature is estimated from Equation 1 to be 30.2 F wbeo the outdoor temperature is --10 F and room temperature is 70 F. The temperature difference is then 70--30.2 or 39.8 deg. For'the insulated residence, attic temperature becomes 4.6 F and temperature difference 70--4-6 = 65.4 deg. * Temperature in garage assumed to be 35 F. ' Coefficient for wall adjoining garage calculated on basis of metal lath and plaster on both sides of studs (O -- 0.39). * One-half of value from Table 4, Chapter 11, for storm windows or weatherstripping. b Exposed on two sides, weatherstripped windows offset by fireplace. Use IK* 1 Window on one side weatherstripped but double-doors are hard to close tightly. Hence, conservative value of IKi Assuming kitchen veat, door to vestibule usually open, allow full table value of IK* k One-half value in Table 4, Chapter 11, increased to IK by nearby outside door in vestibule. 1 Full value in Table 4, Chapter 11, to allow for frequent opening of outside door. " Two sides exposed, large doors but large volume. Use value IK as given in Table 4, Chapter 11. a Two small unweatherstripped windows in protected location, but fireplace, indicate 1 change. * Heat lasses from these rooms into garage are heat gains for garage. * Neglect heat loss to basement, as losses from boiler, piping, etc., will probably keep basement near, if not above, 70 F. r Upstairs hall ceiling figures with downstairs. Heat should be provided downstairs for both. 1 Linear feet of exposed edge. Fig. 1 .... Floor Plans of Residence rage and basement (1.13; from Chapter 9, Table 18, U. is 1.13 for all glass and the application factor is 1XX)). French doorain dining room 50 percent glass, no storm doors (0.85; from Chapter 9, Table 18, U is 1.13 for all glass; by interpolation the applica tion factor is 0.75). Floor (Bedroom D): Maple finish flooring on yellow pine sub flooring; metal lath and plaster ceiling below (028). Floor (Basement and Garage): 4 in. stone concrete on 3 in. cinder concrete (0.10). Solution; The calculations for this problem are given in Table 9, and a summary of the results in Table 10. The values in col umn F of Table 9 were obtained by multiplying together the figures in columns C, D, and E. The heat losses are to the nearest 10 Btu. See reference notes for Table 8 for fur ther explanation of data. Attention is called to the summary of heat (Table 10) for the uninsulated residence. As storm windows are used in thin instance the glass and door transmission heat losses of 19.8 per cent are relatively small. The infiltration losses of 14.0 percent are also comparatively small because the storm windows are equivalent to weatherstripping. In this problem, the wall, ceiling, and floor transmission losses comprise 662 percent of the total. Example 7: Calculate the heat loss of residence shown in Fig. 1 based on the same conditions as in Example 6 but having construction improved or insulated to obtain coefficients as fol lows; Walls, 0.13; Walls of Dormer over Garage, 0.12; Attic Walls, 028; Walls Adjoining Garage, 0.18; Basement Walls (Recrea tion Room), 0.10. Roof, 053. Ceiling (Second Floor), 0.15. / Windows (Same as in Example 6). Floor (Bedroom D), 0.18. Solution: The procedure for calculating the beat losses is .similar to that for Example 6 A summary of the results is given in Table 11.