Document ZJD77YxJ255jpyQLezX7x79QY

344 CHAPTER 25 1959 Guide Table 4 .... Approximate Attenuation in Straight SheetMetai Duct Runs in Decibels Per Foot Duct Site. Inches AD Frequencies Small............................... Medium.......................... Large.............................. 6x6 24 X 24 72 x 72 0.1 0.05 0.01 excessive air velocity or poor duct fittings. No systematically taken data have been published from which conclusions can be drawn. The reader is referred to Chapter 21 Air Duct Design for good design practice. SOUND ATTENUATION IN DUCTS fig. 9 .... Octave Band Spectrum of Ceiling Diffusers overall sound power level (from 75 to 10,000 cps) can be found within 2 db by the equation: PWL, - 13 logt*Au + 60 logi.ymiI - 2 dbe (21) where PWln " overall sound power level in the seven octave bands from 75 to 10,000 cps, decibels re 10"w watt. Ai = minimum flow area for the air passing through the diffuser, square feet. For undamped flow the mini mum area will normally occur in the diffuser neck, whereas for damped flow it will occur at the damper position (see Fig. 9). mftYimnm air velocity (q/Aau)i feet per second. q quantity of air discharged, cubic feet per second. For coiling diffusers of cone-type construction used in conjunction with deflecting vanes and a damper, Fig. 9 presente the approximate octave band spectrum relative to the overall sound power level as given by Equation 21. The curves of Fig. 9 agree within approximately 3 db of the octave band data collected on &-, 12-, and 18-in. neck diameter ceiling dif fusers. NOISE GENERATE) BY OTHER SOURCES Objectionable noise may be produced by fan motors, pumps, compressors, etc. The designer must give attention to these sources of noise. It is not possible to predict the noise, because unite from different manufacturers differ greatly in the noise produced. Objectionable noise is also generated in the duct system by Unlined Straight Sheet-Metal Ducts The attenuation of sound in straight sheet-metal ducts is a function of the length, shape, and size of the duct. If a ther mal incnlftt.ing material is applied to the outside of the duct this will-also affect the attenuation characteristics.11 Attenua tion values in common use are given in Table 4.14 A recent investigation conducted at the Massachusetts Institute of Technology indicates that the attenuation values given in Table 4 are probably satisfactory above a frequency of 500 cps, but are in most cases significantly lower than the observed values of attenuation below this frequency.11 Only two nixes of ducts were tested, a 12 x 12 in. and a 12 x 24 in. However, these ducts were investigated not only bare, but ftlon with two types of glass fiber thermal insulation applied to the outside of the duct. The first type used was a 1-in. thick glass fiber insulation with a density of 0.75 lb per cu ft. The second type was a glass fiber semirigid 1-in. board with a density of 6 lb per cu ft. Attenuation values were determined by plotting SPL readings made at 3-ft intervals over a total duct length of 40 ft. The results are presented in Table 5. - It should be noted from Table 5 that the addition of ther mal insulation to the outer duct walls had little or no effect on the attenuation in the four octave bands above 600 cps for the ducts tested, and that the values are substantially in agreement with Table 4. In the lower octave bands, however, the effect of added thermal insulation on attenuation is in deed striking. More data on larger size ductwork is needed to confirm these results. Branches At a junction where a duct divides or has side branches or outlets, the sound power traveling down the duct divides. The decibel reduction in sound power from the main duct Table 5.... Octave Band Attenuation of Bare and Thermally Insulated Straight Sheet-Metal Ducts Attenuation--db per ft Dud Size Indies Type of limitation Density 12 X 12 12x24 type 1-in. Glass Fiber, semirigid board type _ 0.75 6.0 _ 0.75 6.0 Frequency Bond--Cyde* pet Second 20-75 75-100 150-300 300-500 6001200 0.26 0.40 0.66 0.30 0.38 1.01 0.26 0.20. 0.40 0.320.66 0.50 0.36 0.44 0.56 0.16 0.22 0.28 0.08 0.16 0.28 0.06 0.10 0.16 0.08 0.08 0.08 0.12 0.12 1200- 2400- 48002400 4800 10.000 0.12 0.24 0.24 0.12 0.12 0.12"' 0.12 0.12 0.12 0.16 0.16 0.16 0.16 Sound Control Table 6------Power level Attenuation at Duct Branches or Outlets Brandi Dud Area Suet of Brooch Areas Attenuation db Ratio Brandi Dud Area Sum of Branch Areas Attenuation db 1.0 0 0.25 6 0.8 1 0.2 7 0.63 2 0.16 8 0.5 3 0.13 9 0.4 4 0.1 10 0.32 5 to any branch may be calculated as 10 logio of the ratio of the branch area to the total area of all branches leaving the junc tion. Generally the total area of the branches leaving a junc tion is greater than that of the duct entering a junction; there fore, the area of the branch should not be divided by the area of the supply duct. In a complicated branched system, errors . incurred by such a practice may accumulate to several db. Table 6 gives the db reduction for various ratios of branch duct area to the total branch duct area. Square Comer Bends Square comer bends can be quite effective in noise reduction provided they are widely separated in tire system. The noise reduction for a single square comer bend with no turning vanes, unlined, is'shown in Fig. 10 Part A. Turning vanes are usually employed in square comer ducts. When the width of 345 the turning vanes is small, say less than one-fourth wavelength of the sound, they do not affect the noise reduction. At higher frequencies, they decrease the noise reduction substantially below that shown in Fig. 10 Part A. When a square comer bend is lined with sound absorbing material, the lining should be extended several duct widths beyond the comer in the direction of sound transmission. For square bends lined in this manner the attenuation may be estimated from Fig. 10 Part B. End Reflection Losses All' of the noise power that is produced in a duct by a fan (or by turbulence) does not radiate from the end of a duct into the room. Instead, part of the power is reflected back from the end toward the fan. The amount of noise power reflected is related to the product of the frequency of the sound and the length of a duct side L, assuming that the duct is square. If the duct is not square, the value of L is taken to be approxi mately equal to y/L,Lf. The end reflection loss is shown in Fig. 11 for two cases: (1) a duct ending in free space *md (2) a duct ending flush with the wall Duct lining Procedure In the past, the most common method of obtaining mnd absorption in ventilating systems has been to linn the duct with absorbing material. It is usually more convenient to line all four sides of the duct, but a lining on one side over a longer length of the duct will, in general, give the same effect for the same area of applied acoustical material. Subject to certain restrictions, the attenuation of a fully lined duct to singlefrequency sounds may be expressed by the approximate Equation 22.u R = 12.61 db (22) where R -- attenuation, decibels. I -- length of lined duet, feet. P = perimeter of duct, inches. A = cross-sectional area of duct, square inches, o " absorption coefficient of lining (a function of fre quency).lt END REFLECTION LOSS AT THE OPEN END OF SQUARE DUCTS \ \ DUCT END FREE SPACE tXICTENoJhs. \ FLUSH WITH WMXV f<g. 10..... Attenuation In Decibels Provided by (A) Unlined Bend, and (B) Lined Bend in a Duct with the Lateral Dimension D .02 05 09 07 2 9 7 10 20 90 90 70 FREQUENCY X LENGTH X|0'3"/L/1000 IN. CPS - INCHES H* oh*e*o equals fl/1000 where f is the geometric meat) frequency of on octave bond fa cps and tislb* (tad dimension in indies. Two corn ore thenm, wrtii the duct end flush fa tfe waif ond wifh (he dud end projecting fata the room. fig. 11 .... End Reflection losses in Decibels at the Open End of a Square Duct of Area Is