41--Electrical Hazards TABLE 500-2(c) CHEMICALS BY GROUPS Group A Atmospheres acetylene Group B Atmospheres butadiene1 ethylene oxide2 3 hydrogen manufactured gases containing more than 30% hydrogen (by volume) propylene oxide2 Group C Atmospheres acetaldehyde cyclopropane diethyl ether ethylene isoprene unsymmetrical dimethyl hydrazine (UDMH 1,1-dimethyl hydrazine) Group D Atmospheres acetone acrylonitrile ammonia1 benzene butane 1- butanol (butyl alcohol) 2- butanol (secondary butyl alcohol) n-butyl acetate isobutyl acetate ethane ethanol (ethyl alcohol) ethyl acetate ethylene dichloride gasoline heptanes hexanes methane (natural gas) methanol (methyl alcohol) 3- methyl-1-butanol (isoamyl alcohol) methyl ethyl ketone methyl isobutyl ketone 2-methyl-1-propanol (isobutyl alcohol) 2-methyl-2-propanol (tertiary butyl alcohol) petroleum naphtha4 octanes pentanes 1-pentanol (amyl alcohol) propane 1- propanol (propyl alcohol) 2- propanol (isopropyl alcohol) propylene styrene toluene vinyl acetate vinyl chloride xylenes 1 Group D equipment may be used lor this atmosphere if such equipment is isolated in accordance with Section 501--5(a) by sealing all conduit Vi-inch size or larger i Group C equipment may be used for this atmosphere if such equipment is isolated in accordance with Section 501-5(a) by sealing all conduit Vi-inch size or larger 3 For Classification of areas involving ammonia atmosphere refer to ANSI B9 1 Safety Code tor Mechanical Refrigeration--1971 and ANSI K61 1 Storage and Handling of Anhydrous Ammonia --1971 4 A saturated hydrocarbon mixture boiling in the range 20-135 C (68-275 F) Also known by the synonyms benzine, ligroin, petroleum ether or naphtha 1272