HEATING VENTILATINC AIR CONDITIONING GUIDE 1940 SIZES OF DUCTS ' The sizes of ducts and flues for gravity or mechanical circulation of air are usually based on the losses due to friction, and these losses must be kept within the available pressure difference. This pressure difference in mechanical ventilation is that derived from the fan, while in gravity ventilation the aspirating effect due to the temperature and height of the. column of heated air causes the pressure difference. General Rules The general rules to be followed in the design of a duct system are: 1. The air should be conveyed as directly as possible at reasonable velocities to obtain the results desired with greatest economy of power, material and space. 2. Sharp elbows, bends and transformation pieces should be avoided. 3. The sides of all ducts or flues should be as nearly equal as possible. (In no case should the ratio between long and short sides be greater tnan 10 to 1.) Procedure for Duct Design The general procedure for designing a duct system is as follows: 1. Study the plan of the building and draw in roughly the most convenient system of ducts, taking cognizance of the building construction, avoiding all obstructions in steel work and equipment, and at the same time maintaining a simple design. 2. Arrange the positions of duct outlets to insure.the proper distribution of heat. 3. Divide the building into zones and proportion the volume of air necessary to supply the heat for each zone. 4. Determine the size of each outlet, based on the volume as obtained in the preceding paragraph, for the proper outlet velocity. 5. Calculate the sizes of all main and branch ducts by either of the following two methods: . Velocity Method. Arbitrarily fix the velocity in the various sections, reducing the velocity from the point of leaving the fan to the point of discharge to the room. In this case the pressure loss of each section of the duct is calculated separately and the total loss found by adding together the losses of the various sections. . Friction Pressure Loss Method. Proportion the duct for equal friction pressure loss per foot of length. 6. Calculate the friction for the duct offering the greatest resistance to the flow of air, which resistance represents the static pressure which must be maintained in the fan outlet or in the plenum space to insure distribution of air in the duct system. The duct having the' greatest resistance will usually be that having the longest run, although not necessarily so. Air Velocities The following velocities of air are considered standard for public buildings: 1. Through the outside air intakes, 1000 fpm. 2. Through connections to and from heating unit, 1000 to 1200 fpm. 3. Through the main discharge duct, from 1200 to 1600 fpm. 4. In branch ducts, 600 to 1000, and in vertical flues, 400 to 800 fpm. 5. In registers or grilles, 200 to 400 fpm depending upon the size and location. If diffusers of proper design are used, 25 per cent higher air velocities are permissible. These duct velocities may safely be increased 20 per cent if first class construction is used to prevent any breathing, buckling, or vibration. High velocities at one point in the system neutralize the effect of proper 548 CHAPTER 30. AIR DUCT DESIGN design at all other points; hence the importance of splitters in elbows and similar precautions. For industrial buildings noise is seldom considered, and main duct velocities as high as 2800 or 3000 fpm may be used where conditions will permit. For department stores and similar buildings, maximum velocities with good construction and design may be as high as 2000 or 2200 fpm in main ducts, with suitable reduction in branches and outlets. With these velocities first class duct construction is essential. One recent trend in grille design, for.all types of buildings is toward the use of much higher grille and'branch duct velocities. With proper design and installation, 1600 fpm may be entirely satisfactory. Proportioning the Size for Friction By means of Fig. 3 the diameter of branch pipes necessary to carry a given percentage of the total air in the main pipe and to maintain equal friction per foot of the length through the entire system may be deter mined. Example S. Suppose a 60 in. main pipe with 50,000 cfm air flow is to be used, and it is desired to know the size of branch pipe required to carry 50 per cent of the total air in the main. Find 50,000 cfm at the right scale of Fig. 3 and move horizontally left to the diagonal line marked 60 in. Directly below this intersection it is found that the friction per 100 ft is 0.13 in. At this same friction, intersect 50 per cent capacity (25,000 cfm) and it is found that the branch pipe will be 46.5 in. in diameter. Where rectangular ducts are used it is frequently desirable to know the equivalent diameter of round pipe to carry the same capacity and have the same friction per foot of length. Table 1 gives directly the circular equivalents of rectangular ducts for equal friction and capacity, which are based on values determined from Formula 6: d = i.265 (6) where a = one side of rectangular pipe, feet or inches. b = other side of rectangular pipe, feet or inches. d -- equivalent diameter of round pipe for equal friction per foot of length to carry the same capacity, feet or inches. To'obtain the size of rectangular ducts for different capacities, but of the same friction per foot of length, first obtain the equivalent round pipe for equal friction. Thus, if a branch of sufficient size to carry 30 per cent of a 12 x 36-in. pipe is desired, it is found from Table 1 that the main is Table 1. Circular Equivalents of Rectangular Ducts for Equal Friction 8idb ftECTANGULAB 8 8.5 9 9.5 10 10.5 11 11.5 12 12.5 13 13.5 14 14.5 15 15.5 Duct 16 3 3.5 :4 ; 4.5 5 5.5 5.2 5.4 5.5 5.7 5.8 5.9 6.0 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 7.0 5.7 5.9 6.0 6.2 6.3 6.5 6.6 6.7 6.9 7.0 7.1 7.3 7.4 7.5 7.6 7.7 6.1 6.3 6.5 6.7 6.8 7.0 7.1 7.2 7.4 7.5 7.7 7.8 7.9 8.1 8.2 8.3 6.5 6.7 6.9 7.1 7.2 7.4 7.6 7.7 7.9 8.0 8.2 8.4 '8.5 8.6 8.7 8.9 6.9 7.1 7.3 7.5 7.7 7.8 8.0 8.2 8.3 8.5 8.7 8.8 8.9 9.1 9.2 9.4 7.3 7.5 7.7 7.8 8.1 8.3 8.5 8.6 8.8 9.0 9.2 9.4 9.5 9.6 9.8 9.9 7.8 8.4 9.0 9.5 10.1 549