DEPARTMENT 246 TENTATIVE OPERATING INSTRUCTIONS''
HC1 SCRUBBER SYSTEM
INDEX A. SYNOPSIS B. EQUIPMENT C. EQUIPMENT FUNCTION D. CONTROL LOOPS, INTERLOCKS & ALARMS E. START-UP INSTRUCTIONS F. SHUT DOWN INSTRUCTIONS
1. Emergency 2. Normal G. ELECTRICAL POWER FAILURE H. GENERAL INFORMATION I. PRE-CONDITIONING INSPECTION J. EQUIPMENT CONDITIONING PLANS
Written by: V. Brawley 1/10/74 Approved by: G. Johnson 1/10/74
PCB-ARCH-EXT0374535
Dept. 246 - Tentative Operating Instructions HG1 Scrubber System
'
1
A. Synopsis
.
The purpose of the HC1 off-gas scrubber, system is to
reduce the amount of PCB's in the off-gas to an
acceptable level to protect the environment. The
chlorinators can continue to run for short periods
of time or at a reduced rate when the HC1 using
department is down.
'
B. Equipment
1. Scrubber colum(item 439)
2. Scrubber liquor tank(item 44l)
.
3* Scrubber liquor heat exchanger(item 44o)
4. Scrubber liquor circulating pump(item 442)
5. Entrainment separator
C. Equipment Function
1. The function of the scrubber column is to remove the Aroclor and Biphenyl from the HC1 off-gas by passing the gas up through the cool liquor that is being circulated downward through the column.
2. The function of the scrubber liquor tank is to hold liquor while it is being circulated through the heat exchanger and column scrubber.
3. The function of the scrubber liquor circulating pump is to circulate the liquor from the liquor tank through the heat exchanger and scrubber column.
4.. The function of the scrubber liquor heat exchanger is to cool the circulating liquor to the desired temperature.
5. The function of the separator is to remove droplets cf liquids that may carry-over with the off-gas as it leaves the HC1 storage tank.
PCB-ARCH-EXT0374536
Dept. 246 - Tentative Operating Instructions
2
HC1 Scrubber System
D. Control Loops, Interlocks and Alarms
1. Control loops. There are 4 in this system.
(a) Scrubber liquor tank temperature control-TIC-44l The function of this loop is to prevent the material in the liquor tank from going below 35C. Set point is 35C. This temperature controller is field mounted.
(b) Scrubber liquor tank level indicator - L-44l The function of loop is to provide an indication
of the scrubber liquor level in the tank. The level indicator is located on the tank, on the
ground floor. Normal level is about 6o$(l,26o gal).
(c) Scrubber liquor heat exchanger temperature controller -
tic-44q
^
; '
The function of this loop is to control the temper- .
ature of the liquor to the scrubber column, and to
sound an alarm on a high liquor temperature of 50C.
Normal set point is 4oC. This temperature controller
is panel mounted.
(d) Scrubber column liquor flow controller - FIC-439 The function of this loop is to control the flow of scrubber liquor to the column. The controller is in the field. Normal set point is 8o GPM.
2. Interlocks
There are no interlocks on this system.
3. Alarms
There are two alarms:
(a) If the temperature of the scrubber liquid on the top tray in the column reaches 50C the
alarm will sound and the window marked "Hi temp off-gas scrubber" will light.
(b) If the motor on the liquor circulating pump stops the alarm will sound and the window marked "scrubber liquor circ pump" will light. Both alarms use the same telalarm window.
PCB-ARCH-EXT0374537
Dept. 246 - Tentative Operating Instructions
3
HC1 Scrubber System
E. Start-Up Instructions
1. Close the bottom outlet valve on the scrubber
liquor tank.
.
2. Have distilled 1016 residue pumped from #2 receiver into the scrubber liquor tank to 6o$ on the level indicator.
3. Start cooling water through the scrubber liquor heat exchanger and set the temperature controller on 4oC. (Controller is on panel board in control room).
4. Set the liquor flow, controller on 50 GPM, on
manual control.
.
5. Line up all valves in the liquor circulating line from the pump, through the heat exchanger, into the top of the column, out of the bottom of the column and into the top of the liquor tank.
6. Open the bottom outlet valve on the scrubber liquor tank to allow liquor to flow to the cir culating pump, then turn the circulating pump on.
7- Set the liquor flow controller on automatic and raise the set point to 80 GPM.
Note: Normal conditions at this point.should be:
(a) liquor temperature 4oC.
(b)-liquor flow - 80 GPM
(c) the telalarm window light should be
.
out for the circulating pump and hi
temp off-gas scrubber. . .
(d) the level in the scrubber tank should
be about Go%
(e) the temperature on the liquor tank
should be 4oC.8 9 10
8. Open the HC1 sewering valve to the drowning jet. (Lower the set point on the controller on the 3rd floor).
9. Start up a batch chlorinator in the normal manner.
10. When the batch chlorinator is running, check the back pressure on it. It should not be over 6 pounds.
PCB-ARCH-EXT0374538
Pepo,' 246 - Tentative Operating Instructions
4
HC1 Scrubber System
E. Start-Up Instructions(Cont1d2.)
11. If the HC1 scrubber system functions properly
with the batch chlorinator, start up the con-
tinpus chlorinators at 40$ biphenyl rate.(The
back pressure on the HC1 storage tank should not
be above 6 pounds). 1
.
12. Allow time for the sp.gr. on. the chlorinators to line out, and if the back pressure is no problem, increase the biphenyl feed rate to 50$ and allow it to line out.
13- Increase the biphenyl feed rate to 60$, then to 70$ in the same manner as above in 11 and 12.
14. If all operations look normal, call Dept. 217 and send the HC1 to them.
15. To change out the liquor in the liquor tank use the pump under the HC1 storage tank and transfer
the material through the head tank and out to #7 storage tank. Keep the liquor circulating pump running and don't let the level go below 10$. Re charge from #2 receiver.
F. Shut Down Instructions
1. Emergency
.. 1
a. Shut down all chlorinators.
.
b. Shut off the liquor circulating pump.
2. Normal
a. Shut down all chlorinators. b. Keep the liquor circulating pump running and
the liquor temperature in control.
G. Electrical Power Failure
Electrical power failure will:
.
1. Shut off the liquor circulating pump. 2. Close the water valve to the liquor heat exchanger.
When power is restored, start the circulating pump.
/
PCB-ARCH-EXT0374539
Dept. 24$ - Tentative Operating Instructions
5
HC1 Scrubber System
H. General Information
1. The back pressure on the chlorinators should.not
.
exceed 8 pounds due.to the scrubber system.
2. The pressure drop across the column should be about 3 pounds. A higher pressure drop may indicate flooding in the column(too much liquor).
3. When making 1142 in the continuous chlorinators, the scrubber liquor is expected to last about 7 days before requiring a change out.
4. The scrubber liquor must be changed when the bi
phenyl content reaches 5-0$ or the monochloro-
biphenyl(MCB)content reaches 1.3$j as reported by
the lab. If the biphenyl level exceeds
the
biphenyl will solidify on the HC1 transfer line
walls.
5* To by-pass the scrubber system it is necessary to:
.
a) Shut the chlorinators down.
b) Remove the 6 inch slip blank.
c) Put in two 6 inch slip blanks,
6. There are 7 thermo(steam) panels on the liquor tank. Two have steam applied to them automatically. The
. other five require opening manual block valves if more heat is needed.
7* The scrubber liquor can freeze at temperatures below 30C. If there is a steam failure and the temperature of the scrubber liquor falls below 30C manually turn on the other 5 thermo panels until the liquor exceeds 30C. If the circulating pump is off, do not turn it on until the circulating tank temperature exceeds 30C.
I. Pre-Conditioning Inspection
Item 429 - off-gas storage tank
Visual inspection of tank ______'
Is dip pipe(l) installed for the entrainment separator?
Item 430 - Brinks Mist Eliminator Visual inspection of tank
Fill the dish with 50 gallons of distilled 10l6 residue bottoms
PCB-ARCH-EXT0374540
Dept. 246 - Tentative Operating Instructions
6
HC1 Scrubber System
I. Pre-Conditioning Inspection(Cont'd.)
Item 441 - Scrubber Circulating Tank Visual inspection of tank Are dip pipes(2) installed? Are corrosion coupons and the corometer
installed?
Item 439 - Off gas scrubber Visual inspection of column and demister pad _______ Are corrosion coupons and the corometer installed (top tray)? _________ ' Is the thermowell properly installed(top tray)?_____
Item 442 - Scrubber circulating pump Check rotation of pump
Check pump failure alarm
Instrumentation
,
* .
A. Scrubber liquor heat exchanger
Check manual operation of water valve
Check temperature indicator against amibient temperature
B. Circulating tank temperature controller
Check manual operation of steam valve
Check temperature indicator against ambient
temperature _____________
.
C. Column liquor flow controller Check manual operation of flow control valve _____
D. HC1 gas temperature indicators, scrubber column
inlet and outlet
-
Check temperature indicators against ambient temperature ________
E. Circulating tank level indicator Check zero point
P. Brink differential pressure manometer Check piping connections for manometer _____________
PCB-ARCH-EXT0374541
Dept. 246 -v Tentative Operating Instructions
HC;l4:,^cru'b6er System
'
.
'
'
8
J1.';Bqaiprnent ConditionlngCPlans (Cont 'a .)
. .
Take the following,readings:
b. Shut off the circulating pump to check
telalarm. ___ _y
_________ _.
Then start pumn; again.
.
.
c. Check the sight;, glass in the return line on top of the liquor tank. How full is the glass?______ . Color of liquor _______ .
d. Cool the liquor- to 35C to check the temperature control._________ .
e. Shut off the H20 to the heat exchanger and heat liquor to 50C`7 Use the panels on the liquor tank. _ Did the telalarm come in on high temp?_______ _____
f. Turn the steam off the liquor tank panels and turn water back on the heat exchanger to cool the liquor down to 4oC.
PCB-ARCH-EXT0374543