Document ZB7vbo2bEyyML1QVV7ZD20wQV
148
CHAPTER 10
1960 Guide
by parking or a good exterior grade sheathing paper on the outside of the insulation can be effective in such cases.
Vapor which diffuses inwards under cooling conditions adds to the cooling load. Vapor barriers in walls installed for winter conditions are a help is reducing this. However, if condensation does occur on the back of a vapor barrier installed on the inside of the insulation, the latent heat which is then released on the inside of the insulation may add to the heat gain through the wall.
REFERENCES
I S. C. Hite and J. L. Dray: Research in Home Humidity Control (Purdue University, Engineering Experiment Station
Research Series No. 106, November 1948).
'6. C. Chang and N. B. Hutcheon: Dependence of water vapor permeability on temperature and humidity (ASHAE Transactions, Vol. 62, 1956, p. 437).
* F, A. Joy and E. R. Queer: Permeance measurement im proved by special cell (ASHVE Transactions, Vol. 55, 1949, p. 377).
4 F. A. Joy, E. R, Queer, and R. E. Schreiner: Water Vapor
Transfer Through Building Materials (Pennsylvania State College, Engineering Experiment Station Bulletin No. 61, December 1948).
* J. D. Babbitt: The diffusion of water vapor through vari ous building materials (Canadian Journal of Research, Feb ruary 1939, p. 15).
*F. A. Joy and D. R. Fairbanks: Effect of unbalanced air pressure on permeance (ASHAE Transactions, Vol. 62. 1956, p. 451).
' R. M. Barrer: Diffusion In and Through Solids (Cambridge Press, London, 1951).
* L. V. Teesdale: Remedial Measures for Building Construc tion (U. S. Forest Products Laboratory Report R171Q, 1947).
*F. B. Rowley, A. B. Algren, and C. E. Lund: Methods of Moisture Control and Their Application to Building Construc tion (University of Minnesota, Engineering Experiment Station Bulletin No. 17).
19 H. J. Barre: The Relation of Wall Construction to Moisture
Accumulation in Fill-Type Insulation (Iowa State College of Agriculture and Mechanic Arts, Agricultural Experiment Station Bulletin No. 271, 1940).
II P. F. McDermott: Moisture migration: a survey of theory
and existing knowledge (Refrigerating Engineering, August
1941, p. 103).
6
u R. I. Wray and A. R. Van Vorsfc: Permeability of paint films to moisture (Industrial and Engineering Chemistry, Vol. 25, 1933. p. 842).
11 R. R. Britton and R. C. Reichel: Water Vapor Trans mission of Building Materials Using Four Different Testing
Methods (U. S. Housing and Home Finance Agency Technical Bulletin No. 12, January 1950).
14 E. R. Bell, M. G. Seidl, and N. T. Krueger: Water-vapor
permeability of building papers and other sheet materials (ASHVE Transactions, Vol. 57,1951, p. 287).
14 Value from unpublished texts of Pennsylvania State Col lege Experiment Station.
19 F. A. Joy: Basic concepts of water vapor migration and their application to frame walls (ASTM Special Technical Pub lication No. 119, 1951, p. 2).
" Condensation Control in Dwelling Constructions (U. S. Housing and Home Finance Agency, 1949).
BIBLIOGRAPHY
H. W. Wooley: Moisture Condensation in Building Walls
(National Bureau of Standards Report BMS 63, December 14,
1940).
'
F. B. Rowley, A. B. Algren. and C. B. Lund: Condensation
of moisture ana its relation to building construction and opera tion (ASHVE Transactions, Vol. 45,1939, p. 231).
P. D. Close: Permissible relative humidities in humidified
buildings (ASHVE Journal Section, Beating, Piping and Air Conditioning, December 1939, p. 766).
F. B. Rowley, A. B. Algren, and C. E. Lund: Condensation within walls (ASHVE Transactions, Vol. 44,193S, p. 95).
H. Edenholm: Moisture movement and moisture distribution in the walls of buildings (MeddeUmden Fran Statens Forskningskommille for Lantmanntdtyggnader No. 5, 1945, p. 53, available as Technical Translation TT-361 from the National Research Council of Canada, 1952).
J. D. Babbitt: Physics of Condensation in Buildings (Na tional Research Council of Canada Bulletin No. 2).
L. V. Teesdale: Comparative resistance to vapor transmission of various building materials (ASHVE Transactions, Vol. 49, 1943, p. J24).
Durability of moisture-resistant membrane materials in con tact with the ground (Housing and Home Finance Agency, Housing Research No. 4, October 1952, p. 23).
Proposed method of test for water vapor transmission of building materials utilising the Penn State-Armstrong cell (ASTM Bulletin No. 215, July 1956, p. 63).
Beat and water vapor transmission apparatus for iasulated panels (National Bureau of Standards, Technical News Bulle tin, November 1954, p. 157).
F. A. Joy and A. W. Sherdon: Automatic permeance measure ment by the permeometer (ASHAE Transactions, Vol. 59, 1953, p. 435).
F. B. Rowley: A theory covering the transfer of vapor through materials (ASHVE Transactions, Vol. 45, 1939, p. 545).
F. G. Hecbler, E. R. McLaughlin, and E. R. Queer: Simul taneous heat and vapor transfer characteristics of an insulat ing material (ASHVE Transactions, Vol. 48, 1942, p. 505).
J. A. Paxton and N. B. Hutcheon: Moisture migration in a closed, guarded hot plate (ASHVE Transactions, Vol. 58, 1952, p.301).
C. G. Gurr, T. J. Marshall, and J. T. Hutton: Movement of water in soil due to a temperature gradient (Soil Science, November 1952, p. 335).
W. A. Hadley and Ray Eisenstadt: Moisture movement in soils due to temperature diBerence (ASHAE Transactions, Vol. 59, 1953, p. 395).
K. R. Solvason: Moisture in transient heat flow (ASHAE Transactions, Vol. 62, 1956, p. 111).
H. F. Winterkora: Fundamental similarities between electroosmotic and thermo-osmotic phenomena (Proceedings g?lh Annual Meeting, Vol. 27, Highway Research Board, 1947, p. 443).
S. C. Chang and N. B. Hutcheon: Performance of desiccants in the dry pan test for water vapor permeance of membranes (Canadian Journal of Technology, September 1953, p. 175).
F. A. Joy: Thermal conductivity of insulation containing .moisture (ASTM Special TecknicalPvhlicaiionlio. 217, Febru ary 1957, p. 65).
J. S. Cammerer: The effect of moisture on heat transmission through building and insulating materials (Wdrme und KdlteUchntk. September 1939, p. 126, available as Technical Trans lation TT-317 of the National Research Council of Canada. 1952).
H. B. Jespersoa: Thermal conductivity of moist materials and its measurement (Journal of IBVE, August 1953, p. 157).
D. Krischer: Heat conductivity and water vapor diffusion in materials for insulation against cold (Wdrme und Kdltetechnik, 1941, 43(0), p. 2, translation available from British Build ing Research Station as Library Communication No. 492).
D. A. De Vries: The thermal conductivity of soil (Mededelingen van de Landbouwhogeschool te wageningen, 1952, 52(1), p. 1, translation available from British Building Re search Station as Library Communication No. 759).
C. H. Johansson: MoUture transmission and moisture dis tribution in building materials (Wirme-Ventilotions-Sanitelstek, 19: 67, 1948, available as Technical Translation TT-189 from the National Research Council of Canada).
J. D. Babbitt: The movement of moisture through solids (ASTM Bulletin No. 212, February 1956, p. 58).
J. R. Philip and D, A. De Vries: Moisture movement inporous materials under temperature gradients (American GttP physical Union Transactions, April 1957, p. 222).
CHAPTER U
INFILTRATION AND VENTILATION
Causes of Infiltration, Infiltration Due to Wind Pressure, Infiltration Due to Temperature Difference, Sealing of Vertical Openings, Infiltration Measurement, Natural Venfi/afion, Wind Forces, Temperature Difference Forces, Heat Removal, Effect of Unequal Openings, Combined Wind and Temperature Forces, Types of Openings, General Ventilation Rules, Ventilation of Animal Shelters, Garage Venfi/afion
INFILTRATION is the air leakage through cracks and interstices, around windows and doors, and through floors and walls. Its magnitude depends on the structural design, workmanship, and condition of the building. The rate of infiltration cannot be controlled by the inhabitants of the building to any considerable extent. Natural ventila tion is the controlled displacement of air through openings, such as windows, doors, and ventilators as well as through combustion heating devices.
CAUSES OF INFILTRATION
The air leakage which takes place through various aper tures in buildings must be estimated in heating and cooling calculations and enough heating or cooling capacity provided to offset the heat lost or gained by the air leakage. The rate of air flow into and out of a building depends on the magnitude of the pressure difference between the inside and outside of the structure and on the resistances presented to this pressure difference. The pressure difference exerted on the building walls by the air may be caused either by wind or by a difference in density of the air inside and out side the building. The effect of the wind depends on the interrelation of the speed and direction of the wind and the exposure of the building. The effect of the difference in the density of the air depends on the magnitude of the indooroutdoor temperature difference, the height of the rooms, the shape of the openings, and their elevation in the room or building. The effect of the difference in density is often re ferred to as the chimney or stack effect. The pattern of air flow through any part of the structure depends on both the pressure difference and the openings. In general, when the pressure difference is the result of wind pressure, air will enter the building through openings in the' windward walls and leave through openings in the leeward walls or through ventilating ducts in the roof. When the pressure difference is caused by the indoor-outdoor temperature difference the flow will be along the path of least resistance from inlets at lower levels to outlets at higher levels in a heated build ing or in the opposite direction for an air-conditioned build ing. - An exact estimate of the amount of infiltration under design conditions is difficult to make. The complicating factors include (1) variations in building construction, par ticularly as to width of crack or size of openings through which air leakage takes place; (2) variations in wind ve locity and direption; (3) exposure of the building with re' spect to air leakage openings, and with respect to adjoining buildings; (4) variations in outdoor temperatures which in fluence the chimney effect; (5) relative area and resistance
of openings on the windward and leeward sides, and on the lower floors and on the upper floors; and (6) influence of a planned air supply and the related outlet vents. Tight construction is essential for preventing large heat loss due to infiltration.
In view of the meager information available on infiltra tion, a cooperative investigation was undertaken in 1954 in which the infiltration rates of residences were obtained by actual measurement.1' * In 1956 a study was started at the ASHAE Research Laboratory to obtain additional infor mation on infiltration through building entrances* These studies are yielding quantitative information on factors af fecting infiltration rates, but more data are still needed-
INFILTRATION DUE TO WIND PRESSURE
The wind causes a pressure to be exerted on one or two sides of a building. As a result, air comes into the building on the windward tide through cracks or porous construction, and a similar quantity of air leaves on the leeward side through like openings. In general, the resistance to air movement is similar on the windward to that on the leeward tide. This causes a building up of pressure within the building, and a lesser air leakage than that experienced in single wall tests as determined in the laboratory. It is assumed that actual building leakages, owing to this building up of pres sure, will be SO percent of laboratory test values. While there are cases where this is not true, tests in actual buildings substantiate the factor for the general case. Mechanical ventilating systems are frequently designed to produce positive or negative pressures in an enclosure, which are greater or lower than prevalent wind pressures. In such designs, if the specified rate at which air is to be supplied to, or removed from, the enclosure by positive means, ex ceeds the infiltration rate, it is common practice to use the greater value in determining the heating capacity to warm the outdoor air.
Infiltration Through Walls
z''
Data on infiltration through brick and frame wails are given in Table 1.* The brick walls listed in this table are walls that show poor workmanship, and which are con structed of porous brick and lime mortar. For good work manship, the leakage through hard brick wails with cementlime mortar does not exceed one-third the values given. These tests indicate that plastering reduces the leakage by about 96 percent; a heavy coat of cold water paint, 50 per cent; and three coats of oil paint carefully applied, 28 per cent. The infiltration through walls ranges from 6 to 25 percent of that through windows and doors in a 10-6tory