ARMCO STEEL CORPORATION MIDDLETOWN, OHIO PIPING
CONSTRUCM'-MATFJm T.
KEN 005261
ARMCO STEEL CORPORATION MIDDLETOWN, OHIO
STANDARD SPECIFICATION No. ACS-UOO-35
PIPING AND EQUIPMENT INSULATION
CONSTRUCTION-MATERIAL
1.0 SCOPE
This Specification covers materials, fabrication, and installation for the insulation of piping and equipment.
2.0 APPLICABLE SPECIFICATIONS
The following Armco Standard Construction Specifications form a part of this Specification:
2.1 PIPING - GENERAL - ACS-UOO-Ol
2.2 PIPING - COLOR CODE - ACS-UOO-37
3.0 GENERAL
3.1 Thickness - For insulation thickness refer to the particular manufacturer's insulation thickness design requirements manual.
3.2 K Factors (BTU/hr./sq. ft./F./inch thickness) - The K Factors
stated in the tables of this specification are given at various Mean Temperatures. To find the best K Factor for a particular application temperature, multiply the stated Mean Temperature by two (x 2) and add "cold face" temperature. The stated K Factors at the result of this calculation which is nearest the application temperature should be compared.
Example: Application temperature = 1000F "Cold Face" (Ambient temperature) = 80F
(1) (2) (3) ) From Table
(K Factor at 500F
.52 .6k .62) )
2 x (500F)+80 1080F Insulation (1) has the best K
Factor (.52) at the Mean Temperature corresponding to the application temperature.
3.3 Layers - All insulation over two inches in thickness shall be applied in layers. Outer layer only shall have jacketing applied in the factory on all sizes commercially available.
3.U Pipe Fittings - Pre-molded pipe- fittings of the same insulation material as the rest of the line, shall be utilized wherever practicable.
3.5 Finishes - All cements, adhesives, finishes, and jackets shall be as
recommended by the manufacturer of the insulation. Any required deviations shall require a statement guaranteeing the compatibility of the cements, adhesives, finishes, or jackets with the insulation.
U.O MATERIALS
li.l High Temperature - 50QF and Above -
Issue Date: 9-27-67
Page 1 of 17
STD. SPEC. No. ACS-U00-35
KEN 005262
PIPING AND EQUIPMENT INSUIATION
b.1.1 Type A - Diatomaceous or expanded silica, bonded with inorganic fibers,.
(l) Insulation for pipe shall be molded, sectional for pipe sizes up to lb inches; insulation for equipment shall be flat or curved blocks 3" or 6" wide by 18" or 36" long, (For some
ftandard thicknesses insulation for pipe size up to 2b." is available.' nsulation shall be as follows:
Type A - Pipe and Equipment
Carey-Temp Superex-M Kaylo 20
(1) K Factor at Mean Temperature
of 300F
b3
.60
.55
K Factor at Mean Temperature of 500F
.52
.6b
.62
K Factor at Mean Temperature of 800F
.66
.69
--
(2) Acid Resistance of insulation material
High
Low Depends on Jacketing (Metal-On)
Low Depends on J acketing
(3) Density (A.S.T.M. 303 Test)
10 lbs/ 21 lbs/ cu. ft. cu. ft.
12 lbs/ cu. ft.
(U Water Absorption
(Immersion)
b.30 by bOO0 by volume weight
--
Water Absorption (1000 R.H.)
.1 to.20 --M by weight
--
(3) Maximum Temperature
1600F 1600F
1800F
(6) Shrinkage (A.S.T.M. 356 Test)
500F
.220
--
1000F
.b50
.70 (1200F)
1500F
1.200 2.00 (1600F)
1.60( 1800F)
(7) Soluble Chlorides (Pipe corrosion accelerators; recommended for Aluminum and Stainless Steel)
(6) Fire Resistant
Low !x>w (Recom (Recom mended) mended)
Non-com Non-com bustible bustible
Low (Recom mended)
Non-com bustible
Issue Date: 9-27-67
Page 2 of 17
STD. SPEC. No. ACS-bOO-35
KEN 005263
PIPING AND EQUIPMENT INSULATION
I*. 1.2 Type B - Calcium silicate, or expanded silica bonded by diatomaceous earth or asbestos/inorganic fibers with canvas (factory applied where commercially available).
(l) Pipe Insulation - Molded, sectional for pipes 1/2" to 10", segmental or sectional for pipes sizes 12" and larger, and blocks of 6", 9"> 12" and 18" widths by 36" length for equipment. Insulation shall be as follows:
Type B (Pipe & Equipment
Carey-Temp Thermobestos Kaylo
(1) K Factor at Mean
.43 .41 .42
Temperature of 300F
K Factor at Mean
.52 .50 .52
Temperature of 500F
K Factor at Mean
.62 .60 .62
Temperature of 700F
(2) Acid Resistance of Insulating Material
High
Low (Depends on Jacketing)
Low (Depends on Jacketing)
(3) Density (A.S.T.M. 303 Test)
10-15 lbs/ 11 lbs/
cu. ft.
cu. ft.
11 lbs/ cu. ft.
CU) Water Absorption
(Immersion)
h.00% by weight
k00% by weight
480% by weight
(5) Maximum Temperature F
1600F
1200F
1200F
(6) Shrinkage (A.S.T.M. 356 Test)
500F
.22%
1000F
.452
1200F
1.20%
(7) Soluble Chlorides (Pipe 50 to 150
corrosion accelerators: ppm
recommended for aluminum chlorides
and stainless steel)
(Recommended)
1.556
250 ppm chlorides
.556
.956
1.45S 200 ppm chlorides (Recommended)
(8) Fire Resistant
Incombu stible
Incombu stible
Incombu stible
Issue Date: 9-27-67
Page 3 of 17
STD. SPEC. No. ACS-liOO-35
KEN 005264
PIPING AND EQUIPMENT INSULATION
U.1.3 Type C - Diatomaceous, expanded silica, or calcium silicate bonded with inorganic fibers covered with factory applied metal jacket.
(1) Pipe Insulation - Shall be in sections 36 inches long in a complete range of pipe sizes up to 2k inches I.P.S. Jackets shall not exceed .016 inches in metal thickness and shall be galvanized or stainless steel. Insulation shall be as follows:
Type C Pipe
Philip Carey
Careytemp Johns-Manville
Metal
TKermobestos
Jacketed Metal-On
OwensCorning Kaylo Klad
(1) K Factor at Mean Temperature of 300F
1*3 .1*1
.1*2
K Factor at Mean Temperature of 500 F
.52 .50
.52 .
K Factor at Mean Temperature of 700F
.62 .60
.62
(2) Acid Resistance of Insulating Material'
High
Low Depends on Jacketing
Low Depends on Jacketing
(3) Density (A.S.T.M. 303 Test)
10 lbs/ cu. ft.
11 lbs./ cu. ft.
11 lbs/ cu. ft.
(U) Water Absorption (Immersion)
(5) Maximum Temperature
(6) Water Soluble Chlorides (Pipe corrosion accel erators; recommended for aluminum or stainless steel)
N. A.
N. A.
l600F
1200F
50 to 150 ppm chlorides (Recommended)
230 ppm
N. A.
1200F
Very low chlorides (Recommended)
(7) Fire Resistance
Incombus tible
Incombus tible
Incombus tible
(8) . Shrinkage (A.S.T.M. 356 Test)
300F
1000F
.22% .1*5*
--
.5* .9%
1200F
1.20/6
1.5*
1.1**
Issue Date: 9-27-67
Page U of 17
STD. SPEC. No. ACS-kOO-35
KEN 005265
PIPING AMD EQUIPMENT INSULATION
ii.l.i; Type D - Mineral Wool or Fiberglass Blankets with Metal Fabric -
(l) Pipe Insulation - Pipe insulation shall be 2k inches long sections cut to correct width for single layer installation. Shall be light weight, uniform density, felted, and secured between inner metal lath and outer galvanized metal fabric, with suitable fastening devices to achieve snug installation.
Type D (Pipe)
Owens-Corning fiberglass Blankets
Philip Carey Mineral Wool
Sagle-Picher rab-Lok (Mineral Wool)
(1) K Factor at Mean Temperature of 300F
.39
.h2 .U2
K Factor at Mean Temperature of U00F
.119
K Factor at Mean Temperature of $00 F
(2) Maximum Temperature
1000F
.57 1200F
.57 1200F
(3) Density
2.U lbs/ cu. ft.
8 lbs/ cu. ft.
--
Ck) Acid Resistance of Insulating Material
--
----
(5) Water Soluble Chlorides (Pipe corrosion accel erators; recommended for
aluminum and stainless
steel)
None (Recom mended)
High Chlorides (Not recom mended for stainless or aluminum
Low Chlorides (Recom mended)
(6) Moisture Absorption (100$ humidity test)
.5$
(7) Fire Resistance
Incombus tible
Incombus tible
Incombus tible
Issue Date: 9-27-67
Page 5 of 17
STD. SPEC. No. ACS-liOO-35
KEN 005266
PIPING AND EQUIPMENT INSULATION
(2) Equipment insulation shall be 2* x 8* or 2' x 1;' blankets. A facing of 1" galvanized hex wire shall be used for irregular surfaces. A facing of 1/2" mesh expanded shall be used for cement finishes, and a facing of 3/8" rib-lath (raised) shall be used with rib turn out to provide air space or in to provide maximum rigidity.
Type D (Equipment)
Philip Carey Rock Wool Blanket
J ohns-Manville Blanket Banroc
Owens-Coming Metal Mesh Blanket
(1) K Factor at Mean Temperature of 300F
.35
3k
.1*0
K Factor at Mean Q Temperature of 1|00 F
-U3
hO
.50
K Factor at Mean Temperature of 500 F
(2) Acid Resistance of Insulating Material
.U9 ------
.U8 --
--
----
(3) Density (A.S.T.M. 303 Test)
8 lbs/ cu. ft.
8 lbs/ cu. ft.
2.U lbs/ cu. ft.
(U) Water Absorption (Immersion)
-- h00% by weight
--
(5) Maximum Temperature
1200F
1000F
1000F
(6) Shrinkage (A.S.T.M. 356 Test)
500F
N. A.
N. A.
N. A.
800F 1000F
N. A. N. A.
N. A. N. A.
N. A. N. A.
(7) Water Soluble Chlor ides (Pipe corrosion acceleratorj Recom mended for stainless steel and aluminum)
(8) Fire Resistant
High (Not Recom mended)
10 ppm (Recom mended)
Incombus tible
*
Incombus tible
Issue Dates 9-27-67
Page 6 of 17
STD. SPEC. No. ACS-UOO-35
KEN 005267
PIPING AND EQUIPMENT INSUIATION
4.1.5 Type E - Mineral Wool Block (for ducts, tanks and equipment -
Properties shall be as follows:
(1) Blocks shall consist of mineral wool, interwoven to form a porous, easily cut or bent block. Shall be in 18" or 36" lengths, and 6" and 12" widths.
Type E (Equipment)
Philip Carey Mineral Wool
Block
J ohns-Manville H.' T. Banroc Block
Eagle-Picher PV Super temp
(1) K Factor at Mean Temperature of 400 F
.40
.42 .40
K Factor at Mean Temperature of 600F
.47
.51 .47
K Factor at Mean 0 Temperature of 1000 F
(2) Acid Resistance of Insulating Material
.63 --
.75 .63 No
(3) Density (A.S.T.M. 303 Test)
20 lbs/ cu. ft.
15 lbs/ cu. ft.
18-19 lbs/ cu. ft.
(4) Water Absorption (immersion)
Negligible
--
Negligible
(5) Temperature Rating (Max.)
1900F
1800F
1900F
(6) Shrinkage (A.S.T.M. 356 Test)
500F
1000F
-- --
-- --
--
--
1900F
2%
h% (1800F)
2%
(7) Soluble Chlorides (Recommended for use, with Stainless Steel or aluminum)
High (Not Recommended)
Low (Recom mended)
(8) Fire Resistant
Incombustible
Noncombustible
Issue Date: 9-27-67
Page 7 of 17
STD. SPEC. No. ACS-400-35
KEN 005268
PIPING AND EQUIPMENT INSULATION
it.2 Low Temperature Insulation - Below 500F *-
4.2.1 Type F - 85% Magnesia, Calcium Silicate, or Expanded Silica-
Properties shall be as follows:
(l) Pipe insulation shall be in sections up to Hi'* size. Larger pipe sizes shall be in segments and curved blocks.
(2) Equipment insulation shall be in block with widths of 3", 6", 9" and 12", and lengths of 18" and 36'-*.
Type F (Pipe and Equipment)
Philip Carey Careytemp
J ohns-Manville Owens- 85% Magnesia Corning Kaylo
(1) K Factor at Mean 0 Temperature of 100 F
.34
.35 .33
K Factor at Mean Temperature of 200 F
.39
.385
.37
K Factor at Mean Temperature of 300 F
.h3
.42 42
(2) Acid Resistance of.. Insulating Material -- Low (Depends --
on Jacketing)
(3) Density (A.S.T.M. 303 Test)
10 lbs/ cu. ft.
11 lbs. cu. ft.
11 lbs/ cu. ft.
(4) Water Absorption (Immersion)
(5) Temperature Rating
--
1600F
--
600F
--
1200F
(6) Shrinkage (A.S.T.M. 356 Test)'
100F
300F
500F
(7) Soluble Chlorides (Recommended for use with stainless steel or aluminum)
N. A. N. A.
N. A.
Low (Re commended)
N. A. N. A. N. A.
--M--
N. A. N. A. N. A.
Low (Re commended)
(8) Fire Resistant
Incombus-' tible
Incombus tible
Incombus tible
Issue Date: 9-27-6?
Page 8 of 17
STD. SPEC. No. ACS-iiOO-35
ken 005269
PIPING AND EQUIPMENT INSUIATION
b2.2 Type G Molded Fiberglass or Rockwool -
(1) Properties of piping insulation - Shall be in sections 36 inches long. Shall be composed of fine fiberglass wool bonded and molded to conform to pipe with factory applied jackets of glass cloth. Insulation shall be as follows:
Type G - Molded Fiberglass or Rockwool (Pipe Insulation)
Philip Carey Thermoglas
Owens-Corning Johns-Manville Stan-Heavy 500F Micro,dard Density Lok
(1) K Factor Mean Q Temperature of 100 F
.23
.23 .25
.2U
K Factor at Mean Temperature of 200 F
.27
.27 .30
.28
K Factor at Mean 0 Temperature of 300 F
.31
.31 .30
-3k
(2) Acid Resistance of
Insulating Material
--
Low-Depends
Medium
on Jacketing (Use
Metal-On)
(3) Density lbs/cu. ft.
(k) Water Absorption (95* R.H.)
(5) Maximum Temperature
3.5-3.75
--_
35of
k Ik 3.5-3.75
---
--
1;00F 1j5of
2% by weight 500F
(6) Shrinkage
100F
N. A.
N. A.
N. A.
200F 300F
N. A. N. A.
N. A. N. A.
N. A. N. A.
(7) Soluble Chlorides (Pipe corrosion accel erators ; recommended for use with stainless
steel and aluminum)
High Chlorides (Not Recom mended)
None (Recommened)
None (Recommened)
300-1000 ppm (not recom mended)
(8) Fire Resistant
Incom bus tible
Incom bus tible
Issue Date: 9-27-67
Page 9 of 17
STD, SPEC. No. ACS-UOO-35
KEN 005270
PIPING AND EQUIPMENT INSUIATION
(2) Properties of equipment insulation - Shall be in lengths 1*8" and widths of 21;". Shall be' composed of fine fiberglass wool preformed with thermo-setting resin, with factory applied jackets. Insulation shall be as follows;
Type G - Molded Fiber
Johns-Manville Owens-Coming Philip Carey
glass or Rockwool (Board) Spintex 1*16 PF-615 PF-617 Thermoglas
(1) K Factor at Mean Temperature of 100 F
.23
.27 .27
.23
K Factor at Mean Temperature of 200F
.27
.32 .31
.
K Factor at Mean Temperature of 300F
.32
.1*0 .38
(2) Acid Resistance of Insulating Material
m---- Depends Depends Low on on
Finish Finish
(3) Density
9 lbs/ cu. ft.
6 lbs/ 9 lbs/ cu. ft. cu. ft.
3 lbs/ cu. ft. .
(10 Water Absorption (Humidity)
(5) Maximum Temperature
-- - U5of
-- 1*50F i|50F
rnmmmm
20F
(6) Shrinkage
100F
N. A.
N. A.
N. A.
- 200F 300F
N. A. N. A.
N. A. N. A.
N. A. N. A.
(7) Soluble Chlorides (Pipe corrosion accelerators; recom mended for stainless steel or aluminum)
None (Recommended)
None (Recom mended)
High Chlor ides (Not
recommended for stain less or aluminum)
(8). Fire Resistant
Yes
Yes
Issue Date: 9-27-67
Page 10 of 17
STD. SPEC. No. ACS-liOO-35
KEN 005271
PIPING AND EQUIPMENT INSULATION
it.2,3 Type H - Molded Fiberglass or Rockwool with Metal Jackets (Properties are'the same as U*2.2 Material-Molded fiberglass,except with metal jackets (factory installed) of stainless steel or aluminum.
"Johns-Manville Microtuf".......................................
350F
"Philip Carey Thermoglas".......................... ............................. 350F
"Owens-Corning Glas-Klad".
......................f . . . lt50F
It,3 'Insulating Cement - Cement shall be composed principally of mineral wool with a K factor of 0.85 maximum at 500F Mean Temperature. It shall not corrode steel and shall withstand temperatures up to 1000F without cracking or powdering. Cement shall be:
"Johns-Manville U50"..... ...................... Maximum Service 1800F
"Eagle-Picher One Cote"'................................ MaximumService 1000F
"Philip Carey MW-One"-....................................... Maximum Service 1000F
"0C-110"................................................................... Maximum Service 1000F
lt.lt Asphalt (Bitumen) Mastics -
lt-It-1 Breathing Type - Shall be a water emulsion blend of petroleum asphalt (or bitumen), asbestos fiber and filler, and non-flammable as practicable in the dry state. Shall weatherproof insulation but permit escape of water vapor. Shall trowel evenly and smoothly. Shall be as follows:
"Johns-Manville Insulkote ET" . . . Maximum Service 250F
"Benjamin Foster H.I. Mastic" ... Maximum Service 200F "Philip Carey Thermotex B". . . . . Maximum Service 200F
it.lt. 2 Spray Type - Shall be a protective asphalt coating compound of chemical dispersion type. Shall provide protection of insulation against weather, corrosion and chemical attack. Shall be suitable for spraying easily with a conventional roofer's or undercoater's spray gun. Shall be non-toxic and shall not contain volatile hydrocarbons.
"Eagle-Picher Spray Mastic". ... Maximum Service "Benjamin Foster H.I. Mastic". . . Maximum Service
200F 200F
Issue Date: 9-27-67
Page 11 of 17
STD. SPEC. No. ACS-ltOO-35
KEN 005272
PIPING AMD EQUIPMENT INSULATION
li.U.3 Vapor Barrier Type - Shall be a* heavy plastic-type coating of asbestos fiber, asphaltum, and special oils for application with trowel or caulking gun. Shall bond securely to metal, wood, concrete, paint, and insulation materials specified herein: Shall be as follows:
"Eagle-Picher Stalastic #HT" .................. . Maximum Service 700F
"Philip Carey Insulation Seal" . . . . Maximum Service 200F
"Benjamin Foster Cl Mastic 60-25" . Maximum Service 200F
ii.5 Lagging Adhesive - Cement shall be suitable for cementing canvas to insulation, shall have high bond strength, shall be vermin and mold resistant, durable, and shall increase the fire resistance of canvas. Shall be as follows:
'Benjamin Foster 81-H2" ... .................. Maximum Service 200F
"Insul-Coustic H4O" . ...................................Maximum Service 180F
U.6 Pasted Canvas - This material shall be supplied with pipe insulation and shall be eight ounces per square yard.
k.7 Roofing Felt - Material shall be first-quality asbestos felt, weighing not less than U5 lb. per 100 sq. ft. and shall conform to A.S.T.M. Specification D-250. Asphalt softening temperature shall be not less than 185F.
4.8 Polyvinyl Acetate Covering - Polyvinyl acetate covering shall be Vimasco Corporation WC-1, Insul-Coustic Corporation Vi-AC Mastic Co., or Philip- Carey PVA No. 100. Color of covering shall be in accordance with the Color Code ACS-I4OO-37, and color shall be integral and shall not require painting. Thickness shall be 1/16" to 1/8" (dry film) as required by application.
li.9 Wire Mesh - Wire mesh shall be zinc-coated (galvanized) hexagonal steel, 1" mesh, with wire size not less than 18 gauge.
1;.10 Weather Resistant Paint - Paint shall bond to metals and the insulating materials and finishes specified herein. It shall provide an elastic, durable, tough coating for weather protection under mildly corrosive conditions. All surface preparation, paint, and paint application shall conform to the Armco Paint Standard.
U.ll Interior Insulation Paint - All insulation inside of buildings shall be painted. All paint shall be compatible with the insulating materials, finish, and auxiliary materials used. All* surface preparation, paint, and paint application shall conform to the Armco Paint Standard. All painting on piping insulation shall conform to the Armco Piping Color Chart with the exception of that piping insulation exposed to a corrosive atmosphere (pickling lines, acids, etc.) or excessive heat (furnaces) which will require special paint subject to Owner's approval.
Issue Date: 9-27-67
Page 12 of 17
STD. SPEC. No. ACS-UOO-35
KEN 005273
PIPING AND EQUIPMENT IilSUIATION
It. 12 Glass Tape - Tape (for pipe where mechanical abuse is anticipated) shall be of knitted construction to permit expansion and smooth wrapping without gapping. Tape shall not contain asphalt as a weave- set. Available in 1", 2", l*", 6" and 8" widths by 15 yard lengths. Shall be: "Benjamin Foster Company Sealfas Lagging Tape".
ii.13 Glass Cloth - Cloth shall be of glass material, with a plain weave and shall increase the film strength of the coating. Asphalt shall not be used as a binder. Shall be as follows: "Benjamin Foster Company Mast-A-Fab".
5.0 APPLICATION METHODS
5.1 Materials and Workmanship - All insulation, finish and auxiliary materials used shall be new and meet the requirements of this Specification. The application workmanship shall be in accordance with best practice in every detail. All surfaces to be insulated shall be clean, dry and free of loose scale, grease, dirt, oil, rust, and water when insulation or coatings are applied. Painted piping, or equipment with paint in good condition, will require no further paint. Sufficient time shall be allowed to permit dryingout of insulation and cement before sealing. Surfaces to be insulated shall be warm, and in no case shall surface temperature fall below i*0F during application. Heat shall be applied to maintain a satisfactory temperature. Equipment and piping shall have been tested prior to application of insulation*
5.2 General Application Requirements for Piping and Equipment -
5.2.1 Layers - Where double layer insulation is specified, lateral and longitudinal joints at second layer shall be staggered with those of the first layerj canvas shall not be used between layers.
5.2.2 Soluble Chlorides - Piping or equipment which contains any stainless steel or aluminum materials shall have insulation applied which contains low soluble chlorides and is recommended for stainless steel and aluminum service.
5.2.3 Imperfections - Surface imperfections, chipped edges, small joints, cracks and holes not over 1" square shall be filled with insulating material or with insulating cement.
5-2.1i Supports - Angle supports shall be placed under bands and wires at the edges of flat surfaces or square-cornered equipment to prevent cutting the insulation. Insulation on vertical runs of pipe shall be supported by clips or other means (weight of upper segments of insulation shall not be supported by lower insulation). All items such as angles, flat bars, studs, floating rings, wire, etc. necessary to complete the Work shall be included in the Work.
5.2.5 Quality - The insulation on piping and equipment shall safely withstand the continuous service temperatures specified without cracking, disintegration, decrease in insulating properties, or otherwise failing.
Issue Date: 9-27-67
Page 13 of 17
STD. SPEC. No. ACS-1*00-35
KEN 005274
PIPING AND EQUIPMENT IMSUIATIQN
5.2.6 Cement Application - Insulating cement shall be applied in layers not exceeding I/J4" thick each. Cement used on outer coating must be troweled smooth and allowed to dry before felt or canvas covering is applied.
5.2.? Nameplates, Inspection Stamps, etc. - Nameplates, inspection stamps, identification tags, etc. shall not be covered with insulation. In problem areas where water may enter the insulation, the Engineer shall be notified in writing before insulation is applied.
5.2.8 Equipment - Blocks applied to cylindrical vessels and dished heads shall be kerfed or scored to provide full contact with vessel surface. Irregular surfaces shall be covered with insulating cement (reinforced if required). Expansion joints shall be furnished at insulation supports. Blocks applied to cylindrical vessels shall be supported by stainless steel bands on 12" centers with ends tuckedin, and impaling studs as required.
5.3 Application Requirements for Piping Only -
5.3.1 Tolerances - Pipe covering shall fit snugly on the pipe; inside circumference of pipe covering shall not vary from outside circumference of steel pipe (A.S.A. Specification B-36.10) by more than 1%,
5.3.2 Steam-Traced Lines - Pipe covering on steam-traced lines shall be sized so as to enclose both pipe line and tracer, and shall fit as snugly as possible (preferably molded with extra long legs). Steam-traced expansion loops shall be boxed in with block insulation wired in place and finished same as adjoining insulation. If the traced line may at times be below dew-point temperature, such as a steam-traced cold-water line, then the insulation shall be sealed to make all joints vapor-tight.
5.3.3 Sectional Covering - Sectional covering shall be used for pipe up to the largest size commercially.availablej on larger pipes, blocks or segments shall be used. Segments shall be curved to fit the surface to which they are applied, and shall be cut radially to fit against each other. All joints between blocks and sections of pipe covering, both butt and longitudinal, shall be pointed with insulating cement.
5.3-li Wire Binding - Each layer of pipe covering shall be tightly bound to the pipe with independent loops of wire for pipe sizes 1/2" to 6" inclusive, spaced not to exceed 12" on centersj for pipe sizes larger than 6" nominal diameter, wire loops of 16 gauge annealed galvanized wire shall be used and spaced not to exceed 9" centers. (On insulation with metal jacketing, the above paragraph applies only to interior layers.)
Issue Date: 9-27-67
Page li; of 17
STD. SPEC. No. ACS-IiOO-35
KEN 005275
PIPING AND EQUIPMENT INSULATION
5.3.5 Flanges, Fittings and Valves - *A11 surfaces of flanges, fittings, and. valves shall be insulated in a similar manner with the same kinds and thicknesses of insulation, finishes, and jacketing as that specified for the pipe line of which they are a part, except that steam traps shall not be covered.
5.3.6 Valve Bonnets - Valve bonnets shall be covered to a point immediately below the vent plugs if the bonnets are of the flanged or welded type.
5.3.7 By-Pass Connections - The by-pass connections on valves shall be insulated in accordance with specification for piping of the same size.
5.3.8 Flange Insulation - On ii50F and higher temperature steam, and on boiler feed discharge lines, flange insulation shall be applied in such a manner that insulation can be removed without destroying adjacent pipe covering. Pipe covering shall be stopped off at line flanges a sufficient distance to permit easy removal of all bolts. This shall be done by reducing thickness by beveling the insulation at both sides of the joint. For each size of pipe, the amount of this reduction shall be fitted over such reduced covering. Insulation for line flanges shall lap over the pipe covering for a distance equal to the thickness of the pipe covering, but never less than 2 inches per lap. Flanges shall not be' insulated until after they have been retightened.
5.3.9 Outdoor Applications - Outdoor pipe lines shall be covered with metal jackets or shall have a weatherproof jacket or other weatherproof type finish. Special care shall be taken to provide a tight seal where hangers or supports penetrate the outdoor jacket and finish. On horizontal pipe, the seams of a metal jacket shall be on the side of the pipe with the lap downward, with no raw edges of metal exposed. Piping located close to the ground or where jacket might be injured shall be protected with a steel jacket.
5.3.10 Temperature/Humidity - On hot temperature lines or equipment with insulation without metal jackets, where humidity is above 7Q% or where insulation contains equivalent moisture from dew, fog, or rain, the outer jacket shall not be applied until lines are heated and insulation is dry.
5.3*11 Pipe Hangers - Where pipe hangers are attached to the pipe, they shall be covered with the pipe covering. Yfaen necessary part of the inside surface of the insulation shall be removed to maintain a continuous unbroken, outer surface of the pipe covering. The insulation around the hanger clamps shall be sealed with finish cement and carefully flashed if outdoors. If necessary to remove or displace hangers while-insulating^the pipe and hangers shall be returned to original position when completed.
Issue Date: 9-27-67
Page 15 of 17
STD. SPEC. No. ACS-U00-3S
KEN 005276
PIPING AND EQUIPMENT INSULATION
Where necessary to support an insulated pipe outside the insulation, 12 gauge galvanized steel half-round shields shall be installed (minimum of 8 inches long and diameter to fit insulation.)
5.3#12 Expansion Joints - Where insulation is 3 inches or more in thickness and pipe temperature does not exceed 730F, expansion joints in the insulation shall be installed midway between fixed points of the insulation (e.g., between anchors) limiting the cumulative movement of the pipe covering at each expansion joint to 3 inches maximum.
5.3#13 Movement of Pipe Covering - For spans between fixed points which would permit more than 3 inches movement in the pipe covering, added fixed points in the form of lugs or angles shall be installed. Adjacent sections of pipe covering between expansion joints shall be stapled together with 3" x 1" galvanized iron staples placed every 6 inches around the circumferential joint. Wnere the temperature is above 730F, similar procedure to the above is to be followed except that the maximum movement of the pipe covering per expansion joint is to be limited to l'*.
3.3.1h Canvas - Where canvas is to be applied. Standard 8 ounce canvas shall be factory-applied, (F.A.) if possible. For on-thework-site-application, insulation on indoor piping shall be securely and smoothly wrapped with 8 ounce canvas pasted in place with cold water paste (no sewing permitted). Canvas shall be free from winkles and other flaws, longitudinal seams or joints shall be located in the least visible sector of the covering. Adhesive shall be brush applied and canvas shall not be dipped.
3.3.13 Bare Lines/Safety - All bare lines whose contents are 124.0F or over, shall be insulated to a point 7,-0" above the floor when such pipes are in the vicinity of stairways, ladders, walkways, or operating aisles or where such piping may injure operating personnel who come into contact with it. This shall include boiler soot blower piping as well as power piping.
3.3.16 Application Requirements for Blanket Piping Insulation with Metal Jackets - Protective jacketing shall not exceed .016 inch. in thickness. (Metal jacketing exceeding .016 inch must be applied by sheet metal workers.)
(1) Blanket shall be so cut that the abutting joints between sections, and the longitudinal joints in each section, knit tightly together so joints will not be a source of excessive heat loss. Blanket, after wrapping around the pipe, shall have the facing selvages laced or tied together with 18-gauge wire, or special tabs furnished with the blanket.
(2) On bends, the selvages shall be secured on the outside radius to permit shortening of wire mesh on inside radius to conform to pipe contour.
Issue Dates 9-27-67
Page 16 of 17
STD. SPEC. No. ACS-liOO-35
KEN 005277
PIPING AND EQUIPMENT INSUIATION
(3) Where several pipes are in closely spaced arrangement, the blanket shall be applied over the entire pipe assembly, including any steam tracer.
(U) When specified on the drawings, the casings of pumps shall be insulated with removable blankets constructed to fit the pumps. These blankets shall be provided with fastening hooks to hold them in place and shall be pulled tight against the pump casings.
5.3*17 Application Requirements for Anti-Sweat Pipe Covering Insulation shall be sectional type, 1 inch thick, bonded glass fibers with an integral asphalt saturated asbestos jacket, or aluminum covered Kraft. Insulation shall be as follows:
"Johns-Manville Micro-Ink1' ........ Cold Water 50F
"Eagle-Picher Superglas" (low temp.) ... Refrigerant Lines to -120F
"Eagle-Picher Superglas" (White Dual). . . Chilled +35F
"Owens-Coming Heavy Density" with FRJ and self-sealing lap ....................................... Cold Water -120 to +1*50F
"Philip Carey Thermoglas" with FRVB ... To - 120F
5.3.18 Application Requirements for Steam-Traced Lines - Hot oil or water lines where steam traced outdoors shall have covering as specified in Item 5.3.2 with jacketing as specified in 5.3.9.
6.0 PRECAUTIONS
6.1 Safety precautions are to be followed where materials handled may cause harmful effects.
6.2 No paint or plastic finish of any kind shall be applied over insulating or finish cement until such cement is thoroughly dry.
6.3 On piping located where people might brush against it, the crimps and twists of exposed bands and wires shall be located to minimize possibility of catching on them.
6.1* All insulation cut or damaged in making connections to existing insulated piping shall be patched and put into original state.
6.5 Tarpaulins shall be spread over equipment for protection from dirt and rubbish from the insulation application.
6.6 Piping and equipment shall have been previously tested and released by the Engineer before any pipe covering or equipment insulation is applied.
Issue-Date: 9-27-67
Page 17 of 17