jr If di m I I *. '-iSifft{t: 1,0 5r b ' . 'l >1 170 CHAPTER 9 1949 Guide The accuracy of the results obtained by the use of Equation 1 depends upon the placing of the openings, as the formula assumes that ventilating openings have a flow coefficient slightly greater than that of a squareedged orifice. If the openings are not advantageously placed with respect to the wind, the flow per unit area of the openings will be less and, if un usually well placed, the flow will be slightly more than that given by the 1 -1 ; IfatifiaiVentilRtion V 171 where , Q = air flow, cubic feet per minute. ' ^ = free area of inlets or outlets (assumed equal), square feet. A = height from inlets to outlets, feet. ( = average temperature of indoor air in height h, Fahrenheit degrees. ( = temperature of outdoor air, Fahrenheit degrees. 94 = constant of proportionality, including a value of 65 per cent for effectiveness of openings. This should be reduced to 50 per cent (constant = 7.2) if con- ' ditions are hot favorable. HEAT REMOVAL In problems of heat removal, knowing the amount of heat to be'removed and having selected a desirable temperature difference, the amount of Fig. 2. Increase in Flow Caused by Excess of One Opening Over Another Fig. 1. The Jump op Wind from Windward Face of Building. (A--Length of Suction Abea; B--Point of Maximum Intensity of . Suction; C--Point of Maximum Pressure) air to be passed through the building per minute to maintain this tempera ture difference can be determined by means of Equation 3. formula. Inlets should be placed to face directly into the prevailing wind, H = 0.0175 Q (f - k) (3) while outlets should be placed in one bf the five places listed: H =, heat , removed, Btu per minute. 1-. On the side of the building directly opposite the direction of the prevailing wind. 2. On the roof in the low pressure area caused by the jump of the wind (sec Fig. 1). .Q = air flow, cubic.feet per.minute. 1.4- (o -- inside-outside temperature difference, Fahrenheit degrees. . ,3. On the sides adjacent to the windward face where low pressure areas occur. 4. In a monitor on the side opposite from the wind. 5. In roof ventilators or stacks. EFFECT OF UNEQUAL OPENINGS The largest flow per unit area of openings is obtained when inlets and outlets are equal,'and the preceding equations are based on this condition; M' TEMPERATURE DIFFERENCE FORCES2 Increasing outlets over ,inlets, or vice-versa, will increase the air. flow, but ;i tI >'!' The stack effect produced within a building when the outdoor tempera ture is lower than the indoor temperature is due to the difference in weight of the warm column of air within the building and cooler air outside. The not in proportion to the added area. . When solving problems having an unequal distribution of'openings, use the smaller area, .either-inlet or out let, in the equations and add the increase as determined from Fig. 2: flow due to.stack effect is proportional to the square root- of the draft head, or approximately: Q = 9.4A y/h(t-Q (2) COMBINED FORCES OF WIND AND TEMPERATURE Equations for determining the air flow due to temperature difference and wind have already been given. It must be remembered that when