Document Yvwe3gqYpZR24XedbybGJRrN

American Society of Heating and Ventilating Engineers Guide, 1935 the'room temperatures, which is the same as assuming the dry-bulb temperature of the entering air to be 68 F, calculate the required air capacity of the system. Solution. 199,736 X 55.2 ; Q = ----- W----X =1 15,313 & cfm = 1146 lb per minute. If a system similar to the one shown in Fig. 1 is used, 1146 lb per minute will be the capacity of the dehumidifier as well as of the fan equipment. Example S., If in addition to the 199,736 Btu per hour sensible heat load, the con ditioned space has a moisture gain of 384,000 grains per hour, calculate the apparatus dew point required to give maintained conditions of 80 F dry-bulb and 65 F wet-bulb with a corresponding 56J^ F dew point. ' Solution. With 384,000 grains of moisture per hour to be picked up, the entering dew point temperature should be low enough so that the addition of this moisture will not increase the dew point above 56H F. Grains per pound of air saturated at 56J4 F (Table 5, Chapter 1) Less: Grains per pound to be picked up, ... / 384 000 li46~X 60* 68.0 5.6 Grains per pound allowable in entering; air 62.4 This corresponds to an apparatus dew-point temperature of 54.17 F. Example S. Illustration of the by-pass system. (See. Fig. 2.) Assume the same data as for Example'2. Instead of passing all of the air through the dehumidifier for cooling and dehumidifying, a portion may be passed through and the balance be mixed with the conditioned air at the leaving end of the dehumidifier, the mixture being proportioned so that the resultant conditions will be those required to give proper conditions in the area considered. Solution. The quantity of air to be dehumidified, the quantity to be by-passed, and the apparatus dew-point temperature may be approximately calculated as follows: Let X = percentage of air to be by-passed. K = percentage of air to be passed through the dehumidifier. id = apparatus dew-point temperature, degrees Fahrenheit. . The quantity X of 80-F air must mix with the quantity Y of dehumidified air to produce air with a resultant 68 F dry-bulb temperature. Also, X quantity of air at 56F dew point must be mixed with Y quantity of dehumidified air to give a resultant dew-point temperature of the' mixture of 54.17 F. It is assumed that the air passing through the dehumidifier is saturated. Solving simultaneous equations, 80.0X + Ytd = 68.00 56.5X + Kid = 54.17 23.5X + 0 = 13.83 (3) W v 13.83 X 100 r,, X =-----235--:-- = 59 per cent, air by-passed. Y = 100 -- X . = 41 per cent, air passed through washer. The second step is to determine the apparatus dew-point temperature. Substitute X in either Equation 3 or Equation 4, and solve for la: 80 X 0.59 + fa X 0.41 = 68 id = --q- = 51.2 F, the apparatus dew point. 174 HEAT to be removed by cooling and DEHUMIDIFYING APPARATUS KxamOle 4. Assume the same datai aass flor Example u3. uIf tfchuev amount of outside air, at 0-p dur,v,-b.u. lb and 75 F w et-b,u.lb, reqquuiired for ventilation has been f`ound' to 'Be 169 l"b~ apoer minute, determine the refnrigeration capaci`t-y---r-e-q--u-Jired. Solution. As the total weight of the air introduced per minute is 1146 lb and 41 per cent of it goes through the dehumidifier, the total work to be done may be computed as foAlloiwr ps:assing through dehumidifier, 1146 X 0.41:....;...... ................... 470 lb Less: Outside air for ventilation...... ........... ............]...[ 1691b Return air.............................................. . 301 lb The refrigeration required.for the:retum ; Total heat per pound at 65 F................. Less: Total heat per pound at 51.2 F.. 29.96 Btu 20.92 Btu 9.04 Btu 3R0e1qulbireXme9n.0t 4foBr ctuool=ing2712l1b oBftureptuerrnmaiirn.u_.t.e....r.e. quired to cool the return air. The refrigeration required for the outside air is: : pound of outside air. ;............... ................. .......... 38.46 Btu Total heat per pound or Less: Total heat per pound at 51.2 F~ ......... -..........- 20.92 Btu. 17.54 Btu Requirement to cool 1 lb of outside air.......................... ....... ............. 169 lb X 17.54 Btu = 2964 Btu per minute required to cool the outside air. Thus, the total refrigeration required is: 2721 Btu + 2964 Btu = 5685 Btu per minute, which is equivalent to a load of 28.4 tons of refrigeration. SIZE OF REHEATERS A properly designed air-conditioning system will have reheaters of sufficient capacity to heat the conditioned air from the apparatus dew point temperature to the inlet delivery temperature. If winter heating is to be accomplished, consult Chapter 22. The following general formula may be used to determine the amount of heat necessary to reheat a given quantity of air: Hi = 0.24 (Jy - Id) M (5) where Hi = heat to be supplied to reheater coil, Btu per hour. Example 6. Assume the same data as for Example 1, and find,the amount of reheating required. ' Solution. ' H\ = 0.24 (68 - 54.17) 1146 X 60 = 228,200 Btu per hour. SURFACE COOLING PROBLEM The amount of coil surface required for a given amount of work is dependent upon factors previously listed. Obviously, the various types of !75