CHAPTER 42
P. W. Wyckoff: Design search for the foolproof air conditioner (Refrigerating Engineehinq, January 1959, p, 43)..
W. EL Lewis: The evaporation of a liquid into a gas (ASMS Transaction*, VoL 44,-1922, p. 325).
' W. H. Carrier: The contact-mixture analogy applied to beat transfer with mixtures of air and water vapor {ASMS Transac tion*, VoL 59, 1937, p..49).
1965 Guide And Data Book
William Goodman: The evaporative condenser--theory and characteristics (Heating, Piping and Air Conditioning, March 1938, p. 165; April 1938, p. 258; May 1938, p.'327).
D. D. Wile: Evaporative condenser performance factors (Re frigerating Engineering, January 1950, p. 55).
F. Rasori: Cooling potential vs. specific enthalpy (Refriger ating Engineering, November 1953, p. 1207).
CHAPTER 43
EVAPORATORS FOR LIQUID COOLING
Types of Wafer and Brine Coolers, Design Criteria, Mechanical and Chemical Requirements, Performance Requirements, Fluid * friction, Heat Transfer, Refrigerant and Chilled liquid Film Coefficients, Separation of Coefficients, Overall Heat Transfer Rates, Wafer and Brine Properties
EVAPORATORS used for cooling water and brines- with
Ammonia flooded coolers are customarily designed with
the commonly used refrigerants are discussed in this bare steel tube surfaces while flooded coolers using other com
chapter. Evaporators for cooling air are discussed in Chapmon refrigerants usually will be designed with non-ferrous
ter 34. An evaporator is that part of a refrigerating system in which
tubes having extended surface on the refrigerant side- -. . Refrigerant feed .methods- for flooded coolers control in
the refrigerant is vaporized to produce refrigeration.
some manner the liquid level in the cooler. .This can be.ac-,
A brine is any liquid cooled by a refrigerant and used for the complished by a low pressure float valve, by a high pressure .
transmission of heat .without a change in its state, having'no float valve on single cooler systems, by a constant pressure
Sash point, or a flash point above 150 F, as determined by expansion valve, by a thermostatic expansion valve, by a
the American Society for Testing. Materials Method D93.
float switch and solenoid valve combination, or by mwaim of a
Items to be considered in evaporator design" and selection restrictor.
are: (a) evaporator surface heat transfer rates, (b) methods of supplying liquid to the evaporator, (c) safety, (d) loss of re Spray Type
frigerant through leakage, (e) liquid carryover, (f) oil return to compressor, (g) fouling of evaporator surface, (h) corrosion;' (i) space and weight characteristics, (j) possible freezing of the medium being cooled, (k) circulation pressure losses of the medium being cooled, and (1) cost
A spray .type cooler, is similar to a flooded shell-end-tube .
cooler except that the refrigerant liquid is recirculated through. spray nozzles located above the top tubes. None of the tubes are submerged in liquid. The quantity of refrigerant circulated is usually three to four times the quantity evaporated in order
TYPES OF WATER AND BRINE COOLERS
to thoroughly wet the tube surface. The spray cooler is Bpe-
The various types of water and brine coolers are listed in
Toble 1 .... Types of Water and Brine Coolers
Table 1, which also indicates the refrigerant flow control, capacity range, and refrigerants commonly used with each type.
Type of Coder
Kafriyernnf Food Dovico
UbioI tango of Capacity
(rood
Comoonfy Utod with tmfngormt
Nos.
Flooded Shell-and-Tube Typo
/
Theflooded coder is one in which the refrigerantis vaporized on the outside of finned or plain tubes which are within a closed shell. Space is usually provided above the tubes sub merged in the boiling liquid for the separation of liquid drop lets from the leaving vapor. These coolers utilize straight' tubes, U-shaped tubes, or coiled tubes for the evaporator sur-" face through which the water or brine flows. The number and
Flooded SheU-and- Low Pressure
Bare-Tube
Float
Flooded Sheil-andFmned-Tube .
[Low Pressure j Float
I High Pressure
Float.
(Low Pressure
Spray Type-Shell I Float
and-Tube
]Higb Pressure
50-500 717 (Ammonia)'
25-2000] 11, 12, 22, 113,
50-3000J 114, 500
)
T 11,12,113,114
size of tubes per pass determines the velocity of the fluid circulated. This velocity is usually held between the limits of 3' ud 10 fps. Fig. l shows a cross section of a typical amra/mia bare-tube cooler. Fig. 2 shows a cross section of a typical
Dry Expansion Shell-and-Tubo
Flooded Baudebt Cooler
Thermal Ex- - 5-150 pansion Valve
Low Pressure 10-100 Float
12,22,500,117 717
finned-tube cooler designed for use with fluormaied hydro carbon refrigerants.
Other types of coolers may be operated flooded by providing a suction trap located above the evaporator, of suitable size and arrangement to effectively separate the liquid refrigerant from the vaporized refrigerant flowing to the compressor, and to return the liquid refrigerant to the cooler..
repontb>liW tor this chapter b aaabMd'to TC 9.2, LnjnM
Dry Expansion Thermal Ex
5-25' .12,22,717
Baudelot Cooler pansion Valve
Flooded Double- Low Pressure 10-25 -. 717
Pipe Cooler
Float
Dry Expansion .Thermal Ex- : 5-25 12,22,717.
Double-Pipe
pansion Vahre
Cooler
Thermal Ex-
2-10 . -12,22,717 ,
Cooler
pansion Valve
Flooded Tank-
Low Pressure 50-200 717
and-AgUator .
Float '