Document Yr00vyV70DVznpz1vb8EG1LJK
314
CHAPTER 28
1962 Guide And Data Book
removal particulates in the size range of 1 to 5 microns is
recommended for this room. The media room, essentially a kitchen, should be ventilated
to remove odors and steam. Infectious disease and virus laboratories, found only in large
hospitals, require special treatment. A ventilation rate of 10 room volumes of air per hour is recommended for these lab* oratories, which should have a negative air pressure relative to any other area in the vicinity to prevent the exfiltration of any airborne contaminants from them. The exhaust air from fume hoods or safety cabinets in these laboratories will require sterilisation before being exhausted to the outdoors. This may be accomplished by the use of electric or gas-fired heaters, placed in series in the exhaust systems, and designed to heat the exhaust air to 600 F. A more common and less expensive method of sterilization of exhaust is to use ultra-high effi ciency filters in the system. These filters are equipped with integral electric resistance wiring. The integral electrical systems provide a means of sterilising the filters prior to re moval for replacement, as a protection for maintenance per
sonnel. Pathology department. The areas of the pathology section
which will require special attention are the autopsy room and in larger hospitals the animal quarters.
Autopsy rooms are subject to heavy bacterial contamina tion and odor. A minimum ventilation rate of 10 room air volumes per hour is recommended, with no recirculation. The exhaust system should discharge the air above the roof of the hospital. A negative air pressure relative to the air pressure of adjoining areas should be provided in the autopsy room to prevent the spread of this contamination. For smaller hos pitals where the autopsy room is used infrequently, it may be desirable to provide local control of the ventilation system.
Animal quarters, principally because of odor, will require a ventilation rate equivalent to 15 room volumes of air per hour with no recirculation and a mechanical exhaust system which will discharge the contaminated air above the hospital roof. To prevent the spread of odor or other contaminate from the unimal quarters to other areas, a negative air pressure of not less than 0.1 in. of water relative to the air pressure of
adjoining areas must be maintained. Throwaway-type filters should be installed on the exhaust grilles in animal quarters to prevent animal hair from entering the exhaust system. Depending upon the type of work performed' in the animal quarters, sterilization of outboard exhaust similar to that recommended for infectious disease laboratories may be re quired. Air movement within the rooms must be carefully controlled to prevent drafts because of the adverse effects upon most animals. A temperature range of 70 to 80 F with a relative humidity of 50 percent should be available for all animal rooms. Individual temperature control must be pro vided in each room to ensure the proper temperature for the species of animals housed.
Radiology department. Fig. 3 illustrates a radiology depart ment for a hospital of approximately 100 beds. The fluoro scopic, radiographic, therapy, and dark room areas will re quire special attention.11 Among conditions which make posi tive ventilation mandatory in these areas are the odorous characteristics of certain clinical conditions treated, special construction designed to prevent ray leakage, and lightproof window shades which reduce any natural light infiltration to the fluoroscopic area.
Fluoroscopic, radiographic, and deep therapy rooms will re quire a minimum ventilation rate of 6 room volumes of air per hour with temperatures of 75 to 80 F and humidity of 40
to 50 percent. A negative pressure should b& maintAined js these rooms. Because of the odor problem, the air from these rooms should not be recirculated during the time the rooms are in use, unless provision for adequate odor removal is in corporated in the ventilation system. For economical opera tion, where odor control is not used, provision should be made for recirculation of the air during idle periods.
Depending upon the location of air supply outlets and ex haust intakes, lead lining may be required in supply and re turn ducts at tbe points of entry to the deep therapy treat ment area to prevent ray leakage to other areas.-
The darkroom will require a minimum ventilation rate of 10 room air volumes with no recirculation. As the darkroom will normally be in use for longer periods than the X-ray rooms, an independent system to exhaust the air to the out doors whould be provided. The exhaust from the film dryer may be connected into the darkroom exhaust.
Physical therapy department. The cooling load of the elec trotherapy section will be affected by the short-wave di athermy, infrared, and ultraviolet equipment used in tilts area. The hydrotherapy section, with its various water treat ment baths, will generally be maintained at temperatures up to 80 F. The potential latent heat build-up in this area should not be overlooked. The exercise section will require no special treatment and temperatures and humidities may be within the comfort zone. As bacterial contamination is not a hazard in these areas, air may be recirculated but the systems should include medium-grade filters.
Occupational therapy department In this department, spaces for activities such as weaving, braiding, artwork, and sewing will require no special ventilation treatment. Recir culation of air using medium-grade filters is permissible.
Larger hospitals or those specializing in rehabilitation wifi
Hospital Air Conditioning
have a greater diversification of skills and crafts, such as carpentry, metalwork, plastics, photography, ceramics, and
paintingihe air conditioning and ventilation requirements of the
various sections should conform to normal practice for such &rraa and to the code requirements relating to them. Tem peratures and humidities should be maintained within tbe comfort zone.
pharmacy. The pharmacy should be treated for comfort aod will require no special ventilation.
Nursery
Air conditioning will be required for nurseries in most areas of tiie United States to provide the constant temperature and humidity conditions essential to care of the newborn. In addi tion, the air-conditioning system through its ventilating features will remove odor and will materially reduce the bac terial contamination of the environment.
A minimum ventilation rate of 12 room volumes of air per hour should be provided for all nurseries, with air mover ntent patterns carefully designed to reduce possibility of drafts.0 The systems should include high-efficiency filters of 90 to 95 percent efficiency in the removal of particulates in the 1 to 5 micron size range. It should be emphasized that the air of other areas of the hospital should not be circulated through the nurseries.
The use of ultraviolet lights exposed in the nurseries is not recommended because of their limited effectiveness, the maintenance required to keep them effective and the false sfnse of security which they engender.
Full-term nursery. A temperature of 75 F and a relative humidity of 50 percent are recommended for the full-term nursery, examination room, and work space.2* Similar con ditions must be maintained in all of these areas as the care of full-term infants requires that they be moved periodically from the nursery to the work space and examination room. The maternity nursing section should be treated similarly, to protect the infant during visits with the mother. The nursery should have a positive air pressure relative to the work space and examination room and the rooms usually interposed between the nurseries and the corridor should be similarly pressurized relative to the corridor. This will prevent the infiltration of contaminated air from outside areas.
Premature nursery. The premature nursery will require a temperature of 80 F and a relative humidity range of 55 to 65 percent.0 Although this nursery is equipped with in dividual incubators that provide dose regulation of tem peratures and humidities, these conditions should be main tained in the nursery proper to accommodate the infant who hay require removal from the incubator and for those infants not placed in incubators. The pressurization of these nurseries should correspond to that of the regular nurseries.
Observation nursery. The observation nursery will require a temperature of 75 F and a relative humidity of 50 percent.0 Because infanta in these nurseries have unusual clinical symp toms, the air from this area should not enter other nurseries. A negative air pressure relative to the air pressure of the work room should be maintained in the nursery, and the work room usuaUy interposed between the nursery and the corridor 8hould be pressurized relative to the corridor.
Nursing Deportment
Patient rooms. Because of the ever-present possibility of cross-infection, particularly of the respiratory tract, and to prevent the spread of odors, air circulation should be confined
315
to the individual rooms. This confinement of the air of pa tient rooms is particularly desirable in nursing units where the rooms may be used for isolation of infected patients or for patients with odorous conditions such as bums. Central fancoil systems with recirculation of air are considered acceptable for patient rooms if high-efficiency filters are used in these systems and if the individual patient rooms will not be used for isolation.
Where room unit type systems are used, it is common prac tice to exhaust an amount of air equal to the amount brought into the room for ventilation through the adjoining toilet room. The ventilation of toilets, bedpan closets, bathrooms, and all interior rooms should conform to applicable codes.
A temperature of 75 F with a relative humidity of 40 to 50 percent and a minimum ventilation rate of 1^ room volumes of air per hour are recommended.
Isolation unit The air exhaust system serving individual rooms in the isolation unit should be designed to permit the outboard exhaust of all air when the rooms are used for con tagious or odorous cwy*- Where use of these rooms for isola tion patients may be infrequent, the system should be de signed to permit switching over to recirculation of air when the rooms are used for other types of patients.
A minimum venilation rate of 4 room volumes of air per hour with a negative air pressure relative to the air pressure of adjoining areas should be provided. Temperatures and hu midities should correspond to those of other patient rooms.
Treatment rooms. Patients are brought to these rooms for special treatments, that cannot be conveniently performed in the patient rooms. To accommodate the patient, a tempera ture of 80 F and relative humidity of 50 percent should be provided. A minimum ventilation rate of 4 room volumes of air with a negative air pressure should be provided for these rooms because they will be highly contaminated at times.
Utility rooms. The clean utility room serves as a storage and distribution center for clean supplies and will require no special ventilation treatment. It'should be air conditioned for comfort, and a positive pressure relative to the corridor should be provided.
The soiled utility room serves primarily as a collection point for soiled utensils and materials. It is considered a contami nated room and for this reason should have a negative air pressure relative to the air pressure of adjoining areas. A' ventilation rate of 3 room volumes of air per hour is recom mended with temperatures and humidities within the comfort range.
Floor pantry. Ventilation requirements of this area will depend upon the type of food service adopted by the hospital. Where bulk food is dispensed and dishwashing facilities are provided in the pantry, the use of hoods over equipment, with exhaust to the outdoors is recommended. Small pantries used for between-meal feedings will require no special ventila tion. The air pressure of tire pantry should be in balance with that of adjoining areas to reduce the movement of air into or out of it.
Surgical Department
No area of the hospital requires more careful control of the aseptic condition of the environment than does the surgical department. The systems serving the operating rooms, including cystoscopic and fracture rooms, will require careful design to reduce to a minimum the concentration of airborne organisms in these rooms. It has been established that the greatest amount of the bacteria found in the operating room