Document YjpD1oN50Zy1L2K9X3yEvVyV0
HEATINC VENTILATING AIR CONDITIONING CUIDE 1941 Table 6. Typical Calculation of Pipe Sizes on Down-Feed Rises with
Flush Valve Water-Closets and Urinals (Riser No. . Fig. 4)
Then the allowable drop per 100 ft will be 25 6 *1^ 100 = 8.5 lb and the sizes shown in Fig. 5 are based on this amount of drop. Of course the other risers will have the same maximum flows at the bottom as they formerly had at the top, namely 215 and 122 gal, respectively, for Risers Nos. 2 and 3. Combining these maximum flows in the same man ner as pursued in the down-feed system it is seen that the maximum flow between Riser No. 2 and Riser No. 3 is 255 gpm, and between Riser No. 3 and the street main, 282 gpm which at a drop of 8.5 lb gives the main sizes indicated. It will be noted that in determin ing the maximum flow in an up-feed riser it is necessary to begin at the top floor and work down instead of beginning at the bottom floor and working up as was done in the down-feed sizing.
SIZING UP-FEED AND DOWN-FEED HOT WATER SYSTEMS Hot water supply systems, when of the circulating type, have a few differences to be considered although the same general principles of sizing apply to these lines as to the cold water lines. Owing to the fact that there are no flush valves on the hot water piping and also because many plumbing fixtures haVe no hot water connections, the sizes of the hot water piping in general will be considerably less than the cold water piping in the same building. On the other hand it is almost invariably
780
CHAPTER 45. WATER SUPPLY PIPINC AND WATER HEATINC
Table 7. Typical Calculation of Pipe Sizes on Down-Feed Riser with Flush Valve Water-Closets and Urinals
(Riser No. S. Fig. 4)
Floor
of
Bldg.
1st
Fixtures on
Floor
1 S. S.
3 W. C. 1 Lav.
Gpm PER Fixture
4
45 3
Maximum Gpm ON
Floor
Maximum Gpm
on
Riser
Probable Use
(per cent)
Probable Demand
Riser Gpm
Allowable Drop
Lb per 100 Ft
4 4 100 4 30
135 3
138
142
63
89
3rd 2 Lav.
3
6 148 61 90
4th
3 W. C.
45
1 Lav.
3
1 S. S.
4
135 3
4
30 30
3th 6tb 7th ' 8th
1 s. s. 1 S. S. 1 S. S. 1 S. S.
4 4 4 4
142 4 4 4 4
290 294 298 302 306
41 119
41 120 40 120 40 121 40 122
30 30 30 30
2
Pipe Size In.
H
IX IX
.2 . . 2 2 2
3
required that a gravity circulation be kept up in such hot water lines and this often has a considerable influence on the size. There are three methods of arranging circulation lines, as follows:
! By using the plain up-feed with a return carried back from the top of the riser and paralleling it.
2. By carrying a supply riser up in one location thus supplying fixtures on up-feed then crossing over at the top and coming down past another collection of fixtures and supplying these by a down-feed.
3. By carrying all of the water to the top of the building and dropping risers wherever needed, feeding all hot water on a down-feed system.
Table 8. Size of Distribution Main for Down-Feed Systems (See Fig. 4)
Riser No.
1
Maximum Gpm Riser
1038 1794
306
Maximum Gpm Main
1038 2832 3138
Probable Use
(per cent)
18 9 9
Probable Gpm
187 255 282
Allowable Drop
Lb per 100 Ft
2 2
Size of Main In.
5
In the first instance the up-feed riser may be sized for the same pressure drop as used for the cold water riser and, from the top of the riser just below the top fixture connection, a return circulation line may be carried" Lit0 the ma*n return line *n the basement and connected through a check valve, set on a 45-deg angle, and a gate valve; these return circu lation lines should never be less than % in., and on the farther half of the ns*:r?' not less than 1 in'.'to favor circulation in the far end. Typical top and bottom connections for such risers are shown in Fig. 6.
781