Document YjZGBx3D91Nz2VQXyX7xL3570

C. C. Shipp & Company Heating and Ventilating Unit, Air Methods of Calcula tion Applying to Gravity Ventilation To determine the size of a foul air vent flue, first find out the number of pupils by allowing 225 cu. ft. of room con tents to each pupil, then allow 16 sq. in. area in the flue to each pupil. To determine the size of an aspirating radiator for a basement or first floor vent flue, allow % sq. ft. of radiation to each pupil; for a second floor vent flue, allow % sq. ft. to each pupil. All vent flues should be connected to a col lecting chamber or chambers constructed in attic. Size of chamber or chambers should be 10 per cent larger than the combined free area of all flues connecting into same. Each collecting cham NOTe: -- BOTTOM OF RAOIATOR TO SET NOT LESS THAN *INCHES ABOVE TOP OF OPENING. ber should be connected to a revolving automatic ventilator. To deter mine. the size of the ventilator, ]/2 sq. in. free area in ventilator should be allowed to each l.sq. in. free area in foul- air vent flues. Note.--For positive ventilation and to insure the withdrawal of 30 cu. ft. of air per minute per pupil, we recommend the use of an exhaust fan in the attic, properly connected to all foul air TYPICAL DETAIL OF CLASS ROOM OOEAL ARRANGEMENT AS DESIGNED BV JACOB M. MILKENE, SUPT. BUILOINGS ANO GROUNDS. INDIANAPOLIS. PUBLIC SCHOOLS. ANO APPROVED 0T THE BOARD OF EDUCATION.I Copyright I9!8. C. C. Shipp & Company vent flues. 654 C. C. Shipp & Company Heating and Ventilating Unit, Air AMERICAN AUTOMATIC VENTILATORS Diameter In. 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 Area in Sq. In. 78 113 153 201 254 314 380 452 530 615 706 804 907 1017 1134 1256 1385 1520 1661 1809 1963 2123 2290 2463 2642 2827 Shipping Weight 20 25 35 45 48 60 70 78 94 110 140 155 165 197 225 250 275 300 350 378 400 425 450 500 575 660 Trade Price * 12.78 15.53 18.56 ,, 24.06 24.75 25.78 28.18 29.91 33.68 35.75 37.81 44.68 48.13 50.88 61.88 68.75 71.50 78.38 83.88 89.38 96.25 103.13 110.00 119.63 126.50 134.75 Noth.--Furnished in galvanized iron only unless otherwise ordered. Base extra. AMERICAN STATIONARY VENTILATORS Diameter In. . 12 14 16 18 20 24 30 36 42 48 54 60 Area in Sq. In. 113 153 201 254 314 380 706 1017 1385 1609 2290 2827 Shipping Weight 40 50 60 70 90 100 150 210 350 450 570 700 Trade Price $ 3.92 5.63 8.66 10.65 13.75 17.18 23.38 37.13 49.50 65.25 75.63 92.61 Note.--American Ventilators are received by all transportation companies under Classification One, double rate. Copyright 1937, 1938, C. C. Shipp & Company METHOD OF CALCULATION FOR D-I SANITARY VENTILATING RADIATOR UNITS The following method of calculation for amount of air required is based on State requirements of Indiana, and will naturally vary in states where the requirements are different. However, the general principles of the method will apply to all cases. 1. The amount of Direct Radiation installed, which is not enclosed with the Air Diffusers, is that required for the ex posed wall and glass. This Radiation is determined in the following manner; 2. Multiply.square feet of glass surface in room by 89, if from zero to 70 deg., or by 99 if from --10 deg. to 70 deg. 655