American Society of Heating and Ventilating Engineers Guide, 1934
sure is applied to one leg, one side will fall and the other will rise an equal amount. The difference in height between the two liquid levels indicates the pressure expressed in inches of liquid used in the gage.
TEMPERATURE MEASUREMENT
In engineering work, mercurial thermometers are largely employed to measure the intensity of heat. These depend on the uniform expansion of mercury to indicate changes in temperature. An amount of mercury held in a sealed tube with a bulb at one end will rise to one definite level when immersed in melting ice, and to another definite level when immersed in boiling water. These two points are marked, and the space between them is divided into a number of equal portions, each of which is called a degree. In the Fahrenheit scale, there are 180 deg thus obtained, while the centigrade scale has 100 and the Reaumur has 80. Like divisions are marked off on the column above and below these two determined points in order that a greater range of temperature may be read.
Thermocouples1 may be used to measure any range of temperatures up to 2,900 F. When two dissimilar metals are joined at two points and a temperature difference exists between these junctions, an electromotive force will be developed. Its magnitude depends on the composition of the wires and the difference in temperature between the junctions. A poten tiometer or sensitive galvanometer of high resistance connected to the thermocouple will give a deflection which is proportional to the tem perature difference between the hot and cold junctions. Thermocouples connected in series are called thermopiles. Thermocouples for the measure ment of high temperatures are calibrated with the aid of the known melting points of pure metals.
For temperatures above 500 F various types of pyrometers are employed. The mercurial pyrometer is a thermometer with an inert gas, such as nitrogen or carbon dioxide, above the mercury column to prevent the mercury from boiling. The radiation pyrometer consists of a thermopile upon which the radiation from a hot source is focused by a concave mirror. A sensitive galvanometer with a calibrated temperature scale indicates the thermo-electromotive force created by the heat on the thermopile. The optical pyrometer measures radiant energy by comparing the intensity of a narrow spectral band, usually red light emitted by the object, with that emitted by a standard light source (electric lamp). Thermo-electric pyrometers operate on the same principle as thermocouples. When measuring high temperatures, it is customary to hold the cold junction at room temperature which may cause some error if the room temperature is above or below the calibration point.
In the measuring of room temperatures care must be exercised to pre vent the results from being affected by the body heat of the observer, by drafts from doors, windows and other openings, or by radiant heat from some local source such as a radiator or wall. All thermometers should be mercury thermometers with engraved stems. The total gradua tions of the thermometers should be from 20 to 120 F, in one degree
See A.S.H.V.E. research paper entitled Study of the Application of Thermocouples to the Measurement of Wall Surface Temperatures, by A. P. Kratz and E; L. Broderick (A.S.H.V.E. Transactions, Vol. 38. 1932).
570
Chapter 40--Test Methods and Instruments
graduations. No ten degrees should occupy a space of less than one-half inch. The accuracy throughout the whole scale must be within one-half degree. The operator should take hold of the top and no part of the body, including the hand, should be nearer than 10 in. to the bulb. The thermometer should not be closer than 5 ft to any door, window, or other opening; should not be closer than 12 in. to any wall; and should be between 3 and 5 ft from the floor. A sling instrument should be used for extreme accuracy.
For measuring duct temperatures an angle-duct thermometer should be used, having a flange to bolt on the side of the duct, with the bulb extending into the duct at least 6 in.
Recording thermometers generally have considerable lag and should not be used for the taking of temperatures for testing, but rather for giving continuous records of the operation of the plant, as the charts will indicate any lack of attention on the part of those responsible for the operation of the plant.
MEASUREMENT OF AIR MOVEMENT
The quantity, velocity and pressure of air discharged by a fan or flowing through a duct or grille may be determined by various methods.
Those in common use are by Pitot tube, anemometer and Kata-thermo-
meter readings, the latter being suitable for low air velocities and being
commonly used for measurements at points where the air is not confined
in a duct. The use of calibrated nozzles, orifice plates, and Venturi meters are recognized methods, which, however, have little application in con nection with ventilation practice.
Pitot .Tube
This.usually consists of two tubes, one within the other, which when properly held in the air stream will register the total or impact pressure and the static pressure, respectively. If these tubes are connected to opposite sides of a water column the recorded pressure will be the dif ferential or velocity head. Volume measurements may thus be made in a duct of known area. Pitot tube measurements are preferably used for air velocities exceeding 20 fps. Volumetric determinations from Pitot tube readings must take into account the barometric pressure, temperature and humidity. These factors determine the weight or density of the air.
In general no accurate velocity pressure readings can be taken when the flow of air in ducts is turbulent. To insure accuracy a straight section of duct from 5 to 10 times its own diameter is desirable in order to straighten out the air currents. If it is necessary to take Pitot tube readings in shorter sections of straight duct, the results must be considered subject to some doubt and checked atcordingly. For accurate work it is neces sary to make a traverse of the duct, dividing its cross section into a number of imaginary equal areas and taking a reading in the center of each, the average of the Velocities corresponding to these pressures giving the true velocity in the duct.
Anemometer
~
This instrument is delicate, and requires frequent calibration when