Document Yj9mGVKxq9pZ3gK5aMR4dqdo0
FlG 35-15 -- Demonstration of explosive properties of flour dust Sifting flour through a cloth into the flame produces fiery bursts that illustrate what happens in gram elevators and other dust-laden atmospheres when dust clouds are ignited
sions (a) prevent the formation of explosive mixtures of dust and air, and (b) prevent the ignition of such mixtures if their formation cannot be prevented
Extraordinary precautions, if such are nec essary, should he taken to prevent accumula tions of dust which may build up to explosive proportions Extensive use of local exhaust and frequent cleaning will do much to mini mize the hazard Where possible, dusty operations should be segregated, and dustproducing equipment should be totally en closed and exhausted to prevent leakage of dust into the general work area
Buildings with high explosion hazards, such as grain elevators or plastics plants, are generally provided with extensive dust collecting equipment and so constructed that explosive pressures will push out hinged windows or blow out wall sections or panels designed and built to fail in a predetermined area, rather than cause structural collapse (See NFPA Standard No 68, Explosion Vent
ing ) Floor openings should be kept to a minimum and openings for pipes and duct work should be sealed
Portable fire extinguishing equipment should be readily available Fog nozzles or finely divided streams of water are more effective than are solid streams of water, which stir up dust
Ignition of an explosive mixture of dust and air may be prevented by control of open flames, friction sparks, static electricity, welding, and excessive heat, or by increased humidity, or bv using inert gas Every pre caution should be taken to prevent-over heated bearings, smoking, friction sparks, and sparks from hand tools, from grinding or welding operations, and from static electric ity Only nonferrous tools should be used in dust exposures, and employees should wear shoes with nonferrous nails
Nonferrous material should also be used tor truck wheels, and bucket conveyors should be prevented from striking sparks Pneu matic or magnetic separators can be used to re move stones, nails, and other spark-producing foreign objects from the material being processed
Only approved dust-tight winng, fixtures, and motors should be used, and employees should be instructed to use only extension cords, lamps, and portable electric tools de signed for protection against this hazard (See NFPA "National Fire Codes," Volume 3)
Cases and vapors Gases and vapors that produce flammable mixtures with air or oxy gen are common in industry Some such gases are acetylene, propane, hydrogen, car bon monoxide, methane, natural gas, and manufactured gas
Highly volatile liquids which emit flam mable vapors include gasoline, benzene, naphtha, and methyl alcohol Kerosene, tur pentine, Stoddard solvent, and other liquids with flash points above 100 F must generally be heated above normal room temperatures before they give off sufficient vapors to form ignitible concentrations
When flammable liquids, including those with flash points above 100 F, must be han dled and used, only minimum amounts, m safety containers, should be allowed in work areas
1069