Heating Systems Boiler Feeders
M?DONNELL & MILLER
Safety Devices for Steam and Hot Water Boilers and Liquid Level Controls
General offices: Wrigley Building, Chicago 11, Illinois
"Doing etne^^^thing u/eD *
PRODUCTS:
Boiler Water Feeders; Feeder Cut
off-Combinations; low Water Fuel Cut-offs; Pump Controls; Low
Water Alarms; Humidifier Water Level Controls; Safety Relief Valves
for hot water heating boilers and storage tanks; High and Low Oil Switches and Liquid Level Con
trollers for a wide range of services.
The service range and types of in stallations covering most common applications of McDonnell Boiler Water Level Controls are described here. For facts concerning pro tection of process boilers, or any special information, consult our engineering department.
McDonnell Combined Boiler Water Feeder and Low Water Cut-off
McDonnell No. 47s for healing boilers under 6000 SQ- ft. capacity. Maximum steam pressure, 6 lbs.
McDonnell No. 61-S for heating boilers over 6000 sg. ft. capacity. Maximum steam pressure, 36 lbs.
A typical installation of the McDonnell No. 47-2 Combined Boiler Water Feeder and Switch is illustrated above. The water feeder maintains safe level by feeding when water line drops. In case of foaming and priming or failure of water supply, causing water level to drop to % in. in the water glass, low water switch comes into action. For automatically fired boilers switch may be wired to cut current to burner. For hand fired boilers switch may be wired to com plete alarm bell circuit. Also furnished for hand fired boilers without switch--desig nated No. 47.
Installation time is cut to minimum by QuickHook-Up Fittings for gauge-glass installation. Valve
mechanism is iso lated from the heat of the float chamber. Large area straightthrough blow-off valve is standard equipment.
The McDonnell No. 2 Switch used in the No. 47-2 is Underwriters' ap proved. Electrical rating: a-c., % hp 110-220 V.; d-c., 10 amp. 125 V.
The illustration above shows a typical in stallation of the McDonnell No. 51-2 Com bined Boiler Water Feeder and Switch used for larger boilers. This combination func tions the same as the No. 47-2, the feeder taking care of normal requirements and theswitch safeguardingagainst emergencies by cutting off the burner in automatically fired boilers or completing a low water alarm circuit for hand fired installations. The feeder is also furnished for hand fired boilers (as No. 51) without low water cut-off and alarm switch.
Basic features of the No. 51-2 are the same as in the No. 47-2, except that it is installed with 1 in. equalizing pipe instead of the McDonnell "Quick-Hook-Up" and has the larger feeding capacity required for larger boilers.
For boiler operating at pressures from 35 lb to 75 lb use the McDonnell No. 53*2 (with switch) or No. 53 (without switch). Electrical rating of switches used in No. 51-2 or 53-2 is the
same as previously given for the No. 47-2.
1068
McDonnell & Millar
Heating Systems Bailor Foodota
McDonnell No. 67 Low Water Cut-off for automatically-fired steam boilers of any size. Maximum steam pressure, 25 lb
The No. 67 takes care of low water cut-off requirements of automatically fired boilers with steam pressure below 25 lbs. It has the McDonnell "Quick-Hook-Up" for quick, easy and trouble-proof installation in the
gauge glass, tappings; deep sediment chamber with large quick opening blow-off; packless, non-binding construction; adjust able terminal box to make wiring neat and easy; dependable, snap-action, twin switches.
One switch closes on small drop without stopping burner. It can be used to complete an alarm bell circuit, warning of ap proaching low water, or can be used to complete circuit to the McDonnell No. 101 Electric Water described below. Second switch cuts current to burner if water level drops to inch in gauge glass.
Underwriters' ratings for both switches: a-c., $4 hp, 110-220 V.; d-c M hp, 115 V.
McDonnell No. 101 Electric Boiler Water Feeders for boilers up to 5000 sq. ft. capacity
The No. 101 is an electric water feeder for use with No. 67 Low Water Cut-off or with McDonnell "built-in" Low Water Cut-offs which are standard equipment on many modern heating boilers. It converts the cut-off into a combination boiler water feeder and low water cut-off as described on the opposite page.
McDonnell No. 150 Pump Control, Low Water Cut-off
and Alarm Switch for boilers of any size. Maximum steam pressure, 150 lb
This boiler water level
control may be used as a pump control, a low water
cut-off, a low water alarm switch, or any combination
been restored. If emergency occurs and water level falls to arrow mark on body of
control, cut-off switch stops burner. If steam pump is used. No. 150 is wired to
of these func
tions. Elec
trical ratings ' are: a-c., 1 hp,
110-220 V., d-c, H hp, 110-220 V.--as
pump control or cut-off; 1 amp. 110 V,
a-c. or d-c--as low water alarm. No. 150
has automatic reset low water cut-off
switch but may be ordered with manual
reset as No. 150-M.
A typical hook-up of the McDonnell No. 150, controlling an electric pump and providing low water cut-off, is shown opposite. When water level drops in. below normal, No. 150 starts pump and then stops it when normal water line has
control electric valve in steam line to pump. Note that McDonnell No. 51-S Feeder is used to supply make-up water to the pump receiver.
Drawings available covering use of No. 150
on two or more boilers supplied by a common
feed pump; ask for No. 150 Data Book.
McDonnell Safety Relief .Valves
The No. 29 series of Safety Relief Valves
have "snap action"--a mechanical means
of opening full orifice capacity at precise
instant set pressure is reached. Resulting
large discharge capacity makes it feasible
to rate them in heat dissipa
ting capacity so they can be
matched to Btu. output of
unit on which they are in
stalled, thus preventing
over-pressures and protect
ing against explosions.
Stainless steel cone re
places conventional com-
No. 29
position disc. Long-lived,
compact bellows replaces broad diaphragm of ordinary valves. Testing lever is easy to
operate. All valves comply with A.S.M.E.
code.
(1) For Hot Water Heating Boilers
Valve No.
Opening Pressure
Btu. Output
29 29 lbs 156.000
129
29 lbs
350.000
(2) For Domestic Hot Water Heaters and Tanks
Valve No.
Opening Pressure
Max. Water Supply Pres.
Btu. Output
229
75 lbs
50 lbs
316.000
329
100 lbs
75 lbs
380.000
429
150 lbs
100 lbs
432.000
1069