Guidelines for Handling and Disposal of .Transformer-Grade Askarslfi first Draft - For ANSI C-107 - April 3. 1972
VII. DISPOSAL PROCEDURES AND SERVICES
A. Sources of Materials Requiring Special Handling and Disposal Procedures
Liquids containing PCB's and solids containing or contaminated with
PCB's may be obtained from any of the following souroes:- transport
containers, transformer manufacturing processes, in test failures, liquids contaminated beyond reclamation, in-service transformer leaks and failures, askaiel-filled transformers scrapped for any reason, etc.
B. Classification for Disposal of Materials Containing PCB's
In general, there are three types of materials for disposal; liquids, burnable solid materials containing PCB's, and non-bumable solid materials contaminated with PCB's.
I. Liquids Liquids containing PCB's requiring disposal by high-temperature in cineration may consist of the following:
1. PCB's contaminated with mineral oil.
2. Mineral oil contaminated with PCB's.
3. Non-reclaimable contaminated transformer askarels, arced askarele, from manufacturing spills, sump accumulation, etc. rich in PCB's,
holding basins, drip and drain pans and containers, washings, sample jars and containers, etc.
II. gqmahie ffoj&d Wa^g,
EfiBls
These materials can be disposed of by high temperature incineration
and consist of cellulosic materials, rags, pressboard, wood, saw
dust, fullers earth In bulk or in cloth bags, blotter papers, nitrile
or cork gaskets, etc.
HI. Non-bumable Solid Waste Materials Containing or. Contaminated wltkiW-S
These materials may consist of coil structures, steel, copper, aluminum,
filter units of the steel mesh construction type, askarel drums, cans,
etc.
.
Materials of this nature should be allowed to drain with the liquid collected In drip pans, etc. Further removal of adhering PCB's can
be accomplished by washing or solvent extraction with kerosene or other approved washing liquids such as perchloroethylene or tri chloroethylene. Accumulated liquids can be disposed of as indicated
in "I" above. Solid materials may be handled as normal scrap.
c. aflmrffltr <pf
Id-quids f<?r Mr/nasai
All liquid scrap material should be placed In appropriate metal transport
drums, properly labeled, for shipment to a company offering an acceptable
disposal service.
'
9-
DSW 333217
STLCOPCB4079794
guidelines for Handling and Disposal of Transformer-Grade AskflEels
flrrtJfrtft
mi Q-W - Aprti 2, Vm
VII. D. fih*nmnfc of Burnable Solid Waste Material Containing PCBts for Disposal
Materials of this type should be placed In open head drums with suitable closures and with the drum properly labeled for shipment to a company offering an acceptable disposal service.
E. Liquid and Solid Waste Disposal Service Organizations
I. General Disposal of askarel-soaked materials must be accomplished by means
In which there is no significant release of askarel to the environ ment. At present, disposal is acconplished by carefully-controlled
Incineration of liquids and soaked software, and by controlled land-fill burial of apparatus and other hardware from which askarel
has been previously drained and washed.
II. Costs In addition to the normal costs of collecting scrap liquids and
solids for disposal, additional costs borne by the owner of such scrap include shipping container, cost of transport to the disposal service organization and a disposal fee usually based upon a per gallon or per pound charge. In general, lowest disposal costs are obtained by using the closest disposal service organization.
III. Known Liquid and Solid Disposal Service Organizations Organizations offering disposal services are listed below, including location, facilities available, types of material handled, and dis posal procedures used. Specific shipping directions and disposal
costs should be obtained from the company.
a. Chem-Trol Pollution Services. Inc.
1. Shipping Address:
Chemtrol Pollution Services, Inc.
Balmer Road Model City, New York 14107
2. Facilities Capable of Handling
1. Liquids - polychlorinated biphenyls (Aroclors) alone or mixed with other oils or solvents.
2. Solids (Software) - Aroclor-soaked compounds, rags, cartons, fullers earth, wire coatings, etc.
3. Solids (Hardware) - Transformer tanks, cores, capacitors, drums, etc.
3. appeal Rreqqflureg 1. Thermal oxidation (incineration)
.
2. Controlled and scientific land-fill -10-
DSW 333218
STLCOPCB4079795
ft
Guidelines for Handling and Disposal of Transformer-Grade Askarels First Draft - For ANSI .0-107 - April 3, 1922
VII. E. (Cant'd)
3. Disposal Procedures (Cont'd)
3. Reclamation by distillation, filtration, and centrifuge as applicable.
b. Monsanto Company
1. Shipping Address:
Incinerator Department (631) W. G. Krunorich Plant Monsanto Company Sauget, Illinois 62206
2. Facilities Capable of Handling
1. Liquids - Polychlorinated biphenyls (Aroclors) alone or mixed with other oils or solvents.
3. Disposal Procedures
1. Incineration at 2000-2500F with auxiliary natural gas followed by scrubbing to remove HCL.
c. figlllns-^alft, ...jpg^
1. Shipping Addresses:
a. Rollins-Purle, Inc. Route 322 Logan Township Bridgeport, New Jersey 08014
b. Rollins-Purle, Inc. Scenic Hay. & W. Cheatham Lane Scottandvilie, East Baton Rouge Parish, La. 70807
c. Rollins-Purle, Inc. Tidal Road & Huy. 134 Deer Park, Texas 77536
2. Facilities Capable of Handling
a. Liquids - polychlorinated biphenyls (Aroclors) alone or mixed with other non- or low-chlorinated hydrocarbons.
b. Solids (Software) - Aroclor-soaked compounds, rags, cartons, fullers earth, wire coatings, etc., containing a minimum of metals.
3. Disposal Procedures Incineration at combustion temperatures up to 2500F. Incinera tion gases are scrubbed, washing out solids remaining from Incineration. Steam and OO2 are expelled from stacks. n DSW 333219
STLCOPCB4079796
Guidelines for Handling and Disposal of Transformer-Grade Askarels
flirt graft - Ipr.jflsi griaz
2,..JL322
PART II - SPECIFIC GUIDELINES
A. Guidelines for Askare1 Transformer Manufacturing. Repair Plant Areas and for Pilling Equipment with Askarel
i. fpr fllllaK, Jfrylpgfeqk-With
It is necessary to assume that In filling equipment with aslcarel and further handling of this equipment that an aslcarel spill will occur. Therefore, it is necessary to provide facilities and a procedure for clean-up to prevent contamination.
a. Agteffiei .flUiBK Area
1) It is desirable that the location of the aslcarel filling area should be adjacent to the test area and final shipping area to minimize the danger of damage of units during handling.
2) It is desirable that the main manufacturing area provided for filling of equipment with aslcarel should be cement floors with adequate cement curb around the entire area to act as a basin for containing the volume of aslcarel from the largest production unit. All aslcarel handling equipment such as pumps, hoses, etc., shall be of the aslcarel-resistant, type.
3) Floor drains must not connect to a sanitary or storm sever but to a sump provided with a manually activated pump capable of punping spilled aslcarel or other liquids to "Scrap aslcarel" drums.
4) Drip pans shall be provided for hose connections and filling valves.
b. Special Containers for Scrap Materials
1) Drums labeled "Scrap aslcarel" must be available for handling all spilled and waste aslcarel from sumps, failed units, drip pans, sample jars, etc.
2) Open-head drums with suitable closures and labeled "Scrap Burnable aslcarel Waste" must be available for handling contaminated cellulose Insulation, rags, paper presaboard, wood, gaslcets, sawdust, etc.
3) Separate containers for handling steel, copper, and aluminum, each adequately marked, shall provide for the components of contaminated core and coll assemblies. These containers are required for the various materials when repairing or sorapping assemblies.
4) Containers for supplies of sawdust for absorbing small askarel spills or clean-up of larger spills must be provided.
12- DSW 333220
STLCOPCB4079797
MdeiUrajp f?r flanflUffiff. apfl i4spoefli ZtafcJKaft - Isx MSI C-3,07 - April 3. 197/?
c. flavULUgring pf_Afi^anJLe
1) Askarel Conditioning Equipment
a. The conditioning unit should he located either In the storage tank area which has a curb to contain an askarel spill or the main transformer manufacturing area for filling with askarel.
2) Fullers Earth
a. Conditioning of new askarel or recycled askarel requires fullers earth treatment. The spent fullers earth in cartridges or bags when replaced Should be allowed to thoroughly drain over drip pans to remove as much liquid askarel as possible. The car tridge units of steel mesh construction should be placed in the "Steel Contaminated with askarel" container for disposition. Cloth bags filled with fullers earth shall be placed in the "Scrap Burnable askarel Waste" container for disposition.
d. issxztom ,9f Units for flsBfltaJBt -ggraa
1) Tear-down Procedure
a. Drain all askarel from the unit either into a holding tank for reuse or into the drum labeled "Scrap askarel" for disposition,1 then allow sufficient time for all the askarel to drain from the core and coils.
b. Remove the core and coil assembly from the unit and place it on a steel tear-down table having a raised edge to contain any run-off askarel from the soaked material. A center drain with a collection container should be provided under the table to collect the fluid askarel.
c. The personnel that dismantled the unit must wear approved gloves, apron and eye protection.
d. Place all materials in the appropriate salvage containers during the dismantling for later disposition.
e. The tear-down table can be cleaned with kerosene or other approved fluids after the dismantling operation. The used cleaning fluids should be placed in the "Scrap askarel" drums for disposition.
f. All used materials, including rags, sawdust, tape, etc., regard less of quantity, shall be put into the appropriate containers for disposition.
-13-
DSW 333221
STLCOPCB4079798
Guidelines for Handling and Disposal of Transformer-Grade Askapsls first Draft,- For ANSI C-107 - April 3. 1972
B. Transformer Labeling
1. New Transformers
All new transformers that contain PCB's shall have a label of adequate durability permanently and prominently attached to the tank by the manufacturer, giving the following warning and instructions. Label Instructions should include the following:
CAUTION
The insulating fluid in this transformer contains polychlorinated biphenyls, which some studies have shown may be an environmental contaminant. Extreme care should be taken to prevent any entry into the environment. In case of malfunction or leaks, con sult the instruction manual or the manufacturer.
2. In-Service Transformers
The transformer manufacturer should make suitable labels available with a similar warning as in B-l above for use on existing transformers.
C. Guidelines for Askarel Transformer Users
'
1. General
Askarel-filled transformers are delivered to customers as sealed units from
which there is no escape of askarel under normal operation. While certain
types of equipment failures can permit loss of some askarel to the environ
ment, such cases are extremely rare.
;
2. Receiving
Imnediately upon receipt of the equipment, examine the tank and fittings for any leakage or spillage that may have occurred in shipping. If leakage
is evident, correct cause of leakage and clean tip askarel with rags soaked
with kerosene or other approved solvent.
3. ipgjLtfllflUan md Periods Inrogsttaa
Following installation, the unit should again be inspected for any damage or leakage. It is recommended that periodic in-service inspections be made for any leaks.
4. Pilling. Filtering, or Diving Askarel
Host askarel units are shipped with the proper amount of askarel but if #.t becomes necessary to top off a unit, follow manufacturer's instructions.
If necessary to dry or fuller's earth treat an askarel unit, follow manu
facturer's instructions. When filtering or conditioning askarel, all of
the same precautions previously described apply as to drip pans, proper
disposal of filter media, etc.
'
-14-
DSW 333222
STLCOPCB4079799
<-' - -r-
Guidelines for Handling and Disposal of Transformer-Grade Askanels First Draft - For ANSI C-107 - April 3. 1972
C. Guidelines for Askarel Transformer Users - (Cant'd)
5. fimnUng
It Is common practice to sample askarel from a transformer for periodic maintenance testing. As previously described, such samples should be taken in a manner to avoid any contamination of the environment. Wash
ings should be collected for proper disposal. Field and laboratory test samples, washings, etc., should also be collected for proper disposal.
6. Transformer DLsoosal
I
The ultimate disposal of an askarel-filled transformer may be accomplished in either of two ways.
a) Complete drainage and dismantling with the proper disposal of the askarel
and askarel-soaked components as described earlier in Part VII.
.
b) Disposition of the complete unit to a scrap or junk dealer. In this event,
the scrap or junk dealer should be suitably warned concerning the proper
handling procedures for disposing of liquid askarel and the askare1-
soaked components.
1
-15-
DSW 333223 STLCOPCB4079800