Waterhammer Considerations for PVC Pipel ine in Irrigation Systems
W. R. Seipt
MEMBER ASAE
ABSTRACT
WATERHAMMER pressure develops whenever flow is changed. Flow changes occur by operaring valves, by starring or stopping pumps, or by sudden release of entrapped air. Its in tensity depends upon the rate of change. On occasion, it damages piping. Waterhammer can be contained by: adequate design; proper installation and responsible use.
PRESSURE REDUCING VALVE
FIG. 1 Underground PVC piping irrigation system.
INTRODUCTION
A good irrigation system, providing satisfactory long term service, should have the lowest investment cost practi cal. An important part of any irrigation system is the underground piping to de liver the water from its source to the irrigation means (i.e. a sprinkler or the like), Fig. 1.
Poly (vinyl chloride), PVC, is an in expensive piping material which, like any piping material, when adequately designed, properly engineered, properly installed, and responsibly used, will per form satisfactorily. The ways in which waterhammer is restrained to within acceptable bounds is a major considera tion too often ignored.
One purpose of this paper is to draw attention to waterhammer, its causes, its extent and its effect. The second pur pose is to emphasize the need to contain waterhammer forces through design, in stallation and use of an irrigation sys tem.
Everyone has at one time or another experienced waterhammer. You hear it when a spigot is suddenly closed--pipes shake and simultaneously .emit a sharp, hammer-like noise. Unbridled, waterhammer often does more than just vi brate and jar the piping; it imposes dam age to the system--sometimes to a con siderable extent, even to blowing pipe out of the ground. Fig. 2.
Article was submitted for publication in November 1973; reviewed and approved for publication by the Soil and Water Division of ASAE in January 1974. Presented as ASAE Paper No. 73-233.
The author is: W. R. SEIPT, Manager, Sales Engineering, Certain-teed Products Corp., Valley Forge, Pa.
BASIC CONSIDERATIONS
To understand waterhammer and its control, it is necessary to review the basic physical principle involved. Waterhammer occurs when water under pres sure in a pipe line is subjected to a change in its rate of flow, (i.e. its veloc ity). The intensity of the waterhammer, evidenced as a surge in pressure, de pends among other things upon the rapidity with which the velocity is al tered.
Water flowing through a pipe bears energy. Part of this energy is kinetic, due to the velocity. Part is potential, a result of pressure. The sum of two en ergies (ignoring friction losses) remains constant throughout the line. Simply explained, whenever the velocity changes there follows a change in kinetic energy. Since the system does not essentially gain or lose energy, a compensating change occurs in potential energy with a corresponding change in pressure. Hence, when a valve is closed quickly and flow is brought to a rather sudden halt, relatively high pressures de velop on the upstream side of the valve. This pressure-increase produces pres sure-waves which travel the pipe and water system at sonic velocities--an ef fect designated waterhammer, see Figs. 3 and 4.
Since any change in water velocity produces a change in pressure, the veloc ity change should be made gradually so as to prevent excessive pressure in creases.
CAUSES OF VARYING VELOCITY
Water velocity in a pipe of constant
cross-sectional area will vary due to any one of the following conditions:
1 Closing a valve 2 Opening a valve 3 Rythmic valve operation 4 Starting a pump (especially a
centrifugal pump, with or with out a check valve in the pump discharge) 5 Stopping a pump 6 Pulsation of an operating re ciprocating pump 7 Movement of air pockets along a pipe line S Sudden or rapid release of air from a pipe line 9 Sudden halt in flow when air has been exhausted out of an air release value 10 Recombination after watercolumn separation
INTENSITY OF WATERHAMMER PRESSURE The increase of pressure in a pipeline full of flowing water due to a change in water velocity can be determined by the equation:
AP = Ca (AV)
FIG. 2 Waterhammer generation.
This article is reprinted from the TRANSACTIONS of the ASAE (Vol. 17, No. 3, pp. 417, 418, 419. 420, 421, 422. 4 23. 1974) Published by the American Society of Agricultural Engineers, St. Joseph, Michigan
CTD000841
V, V2
F3
~n. p3S5U*E w*v*T VACVE*^!.
f?/w * V,2/2g
= /w + V22/2g
! POTENT: a J i k.nETiC I EnEPGT | ^ ENERGY
. sOTSTlAL . KINETIC i ENERGY 1JI ENERGT l
FIG. 4 Pressure wave propagation quick valve closure.
FIG. 3 Water flow energy adjustment.
Where:
4000
, 1143 Hence AP =-------------- =
(SDR-1)
AP pressure increase, psi
AV
velocity change, ft per
PR =
sec (SDR-1)
sonic velocity of pressure
79.22 AV' n/SDR^O.443
C w/144
g
wave in pipe-water sys tem, ft per sec w/144g, a constant weight, lb per sq in. of a 1-ft column of water acceleration of gravity, 32.2 ft per sec per sec
Where:
4000
PR = pressure (class) rating, psi
= design hoop stress, psi with a 2:1 safety factor
EFFECT OF VARYING VELOCITY
From which AV =
14.43 V SDR-0.443 (SDR-1)
See Table 1. Hence a sudden change in velocity of
a If we restrict waterhammer pressure 2.92 ft per sec (AV' = 2.92) will
to AP' = 0.2857 PR (based on a 2.8:1 produce a maximum waterhammer pres safety factor) thereby allowing the re sure in an SDR 26 PVC pipe of
maining portion of the class rating, i.e.
Where: K
E
d t C2
= bulk modulus of water, 300,000 psi
= modulus of elasticity of pipe material, 425,000 psi Type I PVC
= pipe inside diameter, in. = pipe wall thickness, in. = a factor dependent on pipe-
end conditions and poisson ratio of the pipe material (anchored one end only for PVC Cx = 0.95; anchored
0.7143 PR to represent the maximum operating pressures.
/4000\ / 2 \
W W0.7143 FR= (SDR-1)
M.
(0.7143) (SDR-1)
AP = 15.67 x AV' = 15.67 x 2.92 =
45.5 psi
EFFECTS FROM AIR MOVEMENT A very important factor affecting waterhammer pressures is that due to movement of air pockets. The serious ness of entrapped air is not generally realized nor understood. When an air pocket becomes suddenly dislodged, as by a stream of flowing water, the extent of changes in "local" fluid velocities and
both ends but free at mid length for PVC Cj = 0.85)
TABLE 1. WAVE VELOCITY, WATERHAMMER, WATER VELOCITY CHANGE ~VS~ PVC SDR
d SDR-2 =
t
using C1 =0.91, for PVC type 1
J= 5892 SDR-0.443 and
SDR
OD/wail ratio
81 51 41 32.5 26 21
PR
Pressure rating. psi.
50 80 100 125 160 200
a
Surge velocity ft per sec
656 829 925 1040 1165 1300
P
Waterhammer, psi per AV
8.8 11.1 12.4 14.0 15.7 17.5
AV'
Instant velocity change max. ft per sec
1.6 2.1 2.3 2.6 2.9 3.3
AP = 79.22 A V J SDR-0.443
The pressure (class) rating of PVC Type I, Grade I is determined by
PR = 4000/(SDR-l) SDR = D/t = (d/t)+2
a = 5892/V SDR-0.443 P = 79.22 AV/V SDR-0.443
AV = 14.43V SDR-0.443/SDR-1 NOTE : The instantaneous velocity change produces P - 0.2857 x PR
CTD000842
C Ct "JOO "C* '<' '"C*
FIG. 5 PVC pipe, type I, grade I hoop stress regression (at 73.4 F).
the consequent waterhammer pressures are often much in excess of that accounted for by the general theory. Sometimes waterhammer pressures of several hundred psi or more are believed to develop. With PVC, as with any plas tic piping, the effect of air entrapment is suspected to be more pronounced be cause air bubbles appear to "stick" more to plastic surfaces, hence the quantity of air entrapped at a particular point would be greater than that at sur faces of more wettable material. If such is the case, the larger quantity of air when finally dislodged would have the more devastating effect. For this reason, it is most important to rid PVC piping of air and to prevent air from getting into the system. Avoiding or getting rid of air is particularly difficult for an irri gation system because of the many times throughout the irrigation season the system is started and stopped.
WATERHAMMER DAMAGE
Unless steps are taken to restrict waterhammer pressures, damage may occur to one or many of the irrigation system elements, such as pumps, valves, or piping. Depending upon the intensity of the waterhammer pressure will deter mine the severity of the damage. Piping may suffer a hydrostatic burst, confined to the area of the waterhammer origin. More often, however, the pressure wave will propagate with little loss of inten sity ahead of an ensuing burst propaga tion, thereby continuing to rend the pipe up to that point where it meets sufficient resistance to restrain its damaging force. Such a point of resistance may be at a joint, if the joint is of monolithic construction, i.e. one pipe length welded to the next or a pipe socket welded into an adjacent bell, the resistance to burst propagation is mini mal and too frequently the damaging force will continue on through one or more such joints. Discontinuous joints, represented by rubber-gasketed seals, usually offer adequate resistance to stop a burst propagation. While gasketed
joints do not remedy waterhammer damage, at least they generally reduce the extent of the damage considerably.
ADEQUATE DESIGN: PVC SAFETY FACTOR
A very misunderstood concept in PVC pipe design is its pressure (class) rating, and the safety factor attended thereto. The graph, Fig. 5, is a typical regression plot of PVC pipe, in which the ordinate is the log of pipe wall hoop stress in psi and the abscissa is the log of the time to failure, hour.
On this plot, when the stress is ele vated to 6400 psi (3.2 times the class rating), the pipe will burst hydrostati cally in 0.018 hr (65 sec) or longer. If pressured to a hoop stress of 4000 psi, burst will not occur before 100 000 hr. If, however, the pipe is stressed at 4000 psi for a period less than 100 000 hr, say 20 000 hr, it will still retain its origi nal strength, i.e. it will burst at 6400 psi at or in excess of 65 sec.
Hence, the hydrostatic design basis has been established as 4000 psi. Then, by applying a 2:1 safety factor, the hydrostatic design stress is 2000 psi. Based upon the hoop stress formula, the pressure (class) rating of the pipe is de termined from a hoop stress of 2000 psi.
4000
_2
PR = ----------- = (D-t)
2t
4000 ------------- (ISO Formula) (SDR-1)
Therefore after 10 years at the pres sure rating, it can be said with certainty, and even after 100 years at the pressure rating it is reasonable to expect that PVC Type I, Grade I pipe will still retain all of its original strength.
Many manufacturers of PVC pipe ad vocate the use of a 2:1 safety factor, which means that they promote the use of their pipe at a maximum operating pressure equal to the pressure (class) rating of the pipe. No provisions are thereby made to allow for waterhammer pressures within the pressure (class) rating of the pipe. However, we at Certain-teed believe strongly that the maximum operating pressure plus surge allowance should not exceed the pres sure (class) rating. Experience has taught that a 2:1 safety factor is not
TABLE 2. PVC MAXIMUM OPERATING PRESSURE FORMULA
____
HDB/S.F.
MOP = ---------------
<D-t)/2t
4000/2.8
(SDR-1 )/2
1430
(SDR-1J/2
2860
SDR-1
MOP HDB -
S.F. " D= t* SDR "
Max. operating pressure, psi. Hydrostatic design basis. psL
Safety factor Pipe outside die., in. Pipe wall thickness, in. Std. Dimensional Ratio
adequate. For irrigation pipe, we recom mend the maximum operating pressure not exceed 72 percent of the pressure (class) rating. This corresponds to a hoop stress of 1430 psi, or a safety fac tor of 2.8:1, see Table 2.
Hucks (1972) has shown that PVC exhibits also a cyclic stress regression curve, completely independent of the steady-state regression curve already discussed. Wilging(1972) in discussing Hucks' paper, graphically depicts the 2.8:1 safety factor, Fig. 6.
Using a 2.8:1 safety factor with a maximum hoop stress of 1430 psi plus a peak cyclic stress of 570 psi on top of that (a total of 2000 psi stress), the ex pected number of cycles to failure is
500 000. With an irrigation service life of 50 years, and a growing season of 80 days per year, this would allow 120 cycles per day, a factor probably 10 times that expected. Hence a 2.8:1 safety factor appears adequate.
In designing an irrigation system, it is important therefore to select pipe of an adequate pressure (class) rating. For ex ample, if the maximum operating pres sure is 90 psi, then a pipe of 125 psi rating (SDR 32.5) would be selected in order to provide a 2.8:1 safety factor.
FIG. 6 PVC pipe, type I, grade I hoop stress versus cycle to failure.
CTD000843
TABLE 3. PVC MAXIMUM OPERATING PRESSURE ~VS~ SDR
SDR
OD/wall ratio
PR
Pressure (class) rating
MOP
Max. operating pressure psi
81 51 41
32.5 26 21
50 80 100 125 160 200
35 55 70
90 115 145
SDR = D/t 4000
PR =
SDR-1
MOP = 0.71 x PR = 2840/(SDR-l)
3D Pipe outside diameter, in.
t = Pipe wall thickness, in. SDR = Standard dimensional ratio PR s Pressure (class) rating, psi.
MOP = Maximum operating pressure, psi.
The Table 3 of maximum operating pressures, comply with the 2.8:1 safety factor:
Low head (50-ft} irrigation pipe should be used only for gravity flow systems, and should not have a valve in the discharge end of the line. Where a head gate or an entrance valve is used to stop or throttle flow, a vacuum-breaker valve should be installed immediately downstream from the entrance valve.
ADEQUATE DESIGN: VELOCITY AND PRESSURE
Waterhammer pressure due to closing a valve: the time required upon closing a valve for the pressure wave to travel from the valve to the pressure source and reflect back to the valve is given by the equation:
2L Tc = --
a
Where Tc
L
= critical valve closure time, sec
= Length of Line, ft
a = "sonic" velocity of pressure
wave, ft per sec
The maximum waterhammer pres sure will occur at the closed valve pro vided the time to complete valve closure
is less than 2L
a
The amount of waterhammer pressure, the pressure increase, is constant and maximum for valve closure times equal to or less than the critical time:
Where: T = valve closure time, sec Since the maximum waterhammer
pressure possible at the closed valve occurs when valve closure time does not exceed
2L
a
the critical time of valve closure which produces a maximum waterhammer pressure rise becomes of interest. As the following summary for PVC pipe shows, this close-time period increases with in creasing length of pipe line.
The critical flow-stoppage time, Tc, in seconds yielding a maximum increase of waterhammer pressure at the valve is shown in Table 4 for various pipe SDR's and pipeline lengths:
By stopping flow at rates slower than critical time, waterhammer pressures will be reduced from their maximums. Charts and graphs are available to deter mine the time of flow-stoppage for vari ous valve types and flow conditions which will provide acceptable waterhammer pressures (Kephert and Davis
1961, Kerr 1958). However, some indi cation of valve closure time to obtain a percentage of the maximum waterhammer pressure (force) aV
g may be obtained by, first determining the pipe-line constant, Pc:
5892 fit Since a = ----=== for PVC
V SDR-0.443
Where: Pc = pipeline constant a = "sonic" velocity of pressure wave, ft per sec
TABLE 4. CRITICAL FLOW STOPPAGE TIMES ~VS~ SDR
SDR
OD/wall ratio
81 51 41 32.5 26 21
a
Surge velocity, ft per sec.
656 829 925 1040 1165 1300
Tc ** 2L/a, seconds
100 ft
0.31 0.24 0.22 0.19 0.17 0.15
Lr=1000 ft
3.05 2.41 2.16 1.92 1.72 1.54
L=10,000ft
30.5 24.1 21.6 19.2 17.2 15.4
a = 5892/V SDR-0.443
< 2L T = -----
a
SDR a Tc
L
= Std. dimensional ratio = Surge velocity, ft per sec = Critical flow-stoppage time, sec
= Pipeline length, ft
CTD000844
V = velocity of pipeline flow, ft
per sec
PQ = pipeline pressure before
valve closure, psi
g = acceleration of gravity, 32.2
ft per sec per sec
Generally when closing a valve, most
of the flow is stopped between one-
quarter and three-quarters of valve clo
sure. Hence, actual valve closing time is
twice that given by
2L
a
Therefore, the actual valve closing
time to produce critical flow-stoppage is
approximately
4L
T =-----
a
sec. But to reduce the surge by fourfifths the maximum (i.e. to 20 percent of maximum) the above mentioned charts show that valve closure times must be increased by multiplying the critical flow-stoppage time, T , by the following factors, N:
When Pc
1 10
N
6.4 11.6
Hence, valve closing times should be those shown in Table 5.
Not only is it important in design, but in actual operation as well, to insure that value closing times be of the order
of magnitude shown in Table 5. One means for ensuring safe waterhammer pressures is to limit the maximum vel ocity in the pipe line. Also shown in Table 5 (second column) are those vel ocities which will produce a maximum waterhammer pressure equal to 20 per cent of the pipe's pressure (class) rating. Hence, we recommend that the design water velocity when operating at system capacity does not exceed 5 ft per sec, unless additional measures or ancillary equipment are used to ensure waterhammer pressures not in excess of 20 percent pipe's pressure (class) rating and that in no case should the velocity exceed 10 ft per sec.
ADEQUATE DESIGN: AIR RELIEF
Air trapped in a water line can, and often does, spell trouble. If trapped at the top of a rise, it can seriously impede flow.
Air is compressible and, if carried along a pipeline can act like a spring, being compressed at the bottom of a draw and expanding at the top of a rise. Such alternate compression and expan-
TABLE 5. VALVE CLOSING TIMES ~VS~ SDR
SDR
OD/wall ratio
81 51 41 32.5 26 21
V'
Max. vel. change, ft per sec
5.7 7.2 S.O 9.0 10.2 11.4
Valve closing time. T, seconds
L= 1000 It Pc=l Pc* 10
_ L*1QJ>QQ ft Pc*l Pc* 10
19.5 15.4 14.0 12.3 11.3
9.9
35.4 28.0 26.0 22.3 20.5 17.9
195 354
154 280 140 260 123 223 113 205
99 179
1 6.4
10 11.6
T = N(2L/a>
Pc = <V/P0)<39.6/\/ SDR-0.443 ) V' = 50.5VSDR-0.443 /(SDR-1) Pc 11 Pipe line constant PQ * Pressure in pipeline (before valve closure) psi. V = Velocity in pipe line, ft per sec
V' - Max. velocity change producing waterhammer, P0.20 PR. as by valve closure times shown
sion produces velocity fluctuations and pressure variations which, if great enough, can produce serious waterhammer pressures.
Investigations of asbestos--cement pipelines have, for example, indicated that a sudden release of entrapped air can produce pressure increases which may be as much as 10 times the normal operating pressure of the lines. Similar magnitudes of pressure increase in PVC are believed also to occur--as witnessed when damaged pipelines were examined.
Water-column separation can also re sult in excessive waterhammer pressures when the separated column rejoins at high velocity. Furthermore, when the minimum pressure at any point in a line drops to the vapor pressure of water, the waterhammer solution is no longer valid. (Kephert and Davis 1961)
To prevent damage as a result of air entrapment during initial filling of a pipeline and to keep air from getting in to the line from operating pumps, provi sions should be made to remove air from the line at all high points. Com bined air-relief and vacuum-breaker valves should be located at high points, (A). (B), (D), and (E) indicated in the diagram. Fig. 7.
A pressure-relief valve at (F) will limit waterhammer pressure which might result from too rapidly closing the gate valve--at the right end of the diagram. A flush valve (C) will help re move possible debris from the line's low point.
Reasons for locating the several cornbin ed air-relief and vacuum-breaker valves are as follows:
1 Air has a tendency to accumu late at crests and along the downstream side of the crest. Hence, several air vents
should be located downstream of the crest and vented, through a manifold, into the air release valve located at the crest.
2 The valve at (A) is to eliminate air from a deep-well-pump column at startup and limits waterhammer at the check valve.
3 The valve at (B) is to eliminate air between the pump and (B) upon ini tial line-fill, to vent air accumulation with the system in operation under pres sure and to avoid column separation if the pressure should drop below atmo spheric.
4 The valve at (D) is to eliminate air between (C) and (D) and to avoid column separation.
6 The valve at (E) is to eliminate air between (D) and (E) and to avoid possible pipe collapse (in the case of
thinner wall pipe, such as SDR 32.5 or higher (SDR) due to high water velocity which may exist going through the gate valve at the downstream end of the line. (Sturm 1970, Lescovich 1972).
In many instances, manually oper ated globe and gate valves have been in stalled on pipelines to eliminate air at high points. While cheaper than com bined air-relief and vacuum-breaker valves, their use should be discouraged because they must be opened (and closed) manually. The automatic protec tion provided by the more sophisticated air-relief and vacuum-breaker valves is well worth their additional cost Per formance proves it.
If a line is laid in relatively flat terrain, provide at least three combined air-relief and vacuum-breaker valves. One should be in the pump discharge line ahead of the check and gate valves. A second should be near the middle of
CTD000845
the line and the third at the downstream end of the line. If several laterals take off from the main supply line, each one should have a combined air-relief and vacuum-breaker valve at its outermost end.
Everett (1967) points out that: "a popular misconception concerning waterhammer in a pumping system in volves the relative gradient and system pressure. It is assumed that a low flat gradient and a low pressure will mini mize the shock pressure. Conversely, a steep gradient and a high pressure on the system will produce an excessive shock pressure. This misconception should be reversed. Long flat lines with a small amount of gradient develop more shock pressure and are more sus ceptible to line failure than steep gradi ents at high pressure."
ADEQUATE DESIGN: PROTECTIVE EQUIPMENT
Many installations of PVC piping are supplied by motor-driven centrifugal pumps. These will be either horizontalshaft pumps or vertical-shaft deep well turbine pumps, both driven by constant speed squirrel cage induction motors. In general, lOHP and smaller will have full-voltage across-the-line starter units. Motors of greater horsepower will gener ally be provided with reduced-voltage starting. Hence, a pump-control of the flow in such cases is not possible. Flow control can be achieved by the opening or closing of a gate valve in the pump discharge, but must be done slowly ind with due caution to the operating char acteristics of the pump-drive system.
The designer of a PVC piping system supplied by the above mentioned pump
ing facilities, must consider the follow ing features to ensure satisfactory per
formance :
1 Remove air from the line as it is being Filled using automatic air-removal valves, properly sized'and located at:
(a) the pump discharge. (b) high points in the pipeline. (c) the downstream end of the pipeline.
2 Remove air from the riser pipe on deep well turbine pumps at start-up by a suitable air removal valve.
3 Provide pressure-relief valves at: (a) ahead of the gate valve in the pump discharge line. (b) at the downstream end of the pipe lines.
4 It may be necessary to install surge arrestors or automatic pressure re
ducing valves at: (a) flow regulators. (b) pump discharge.
5 It may be necessary to provide flow controllers so as to keep down the rate of Filling and to reduce the start-up surge in a filled lined at:
(a) pump discharge. (b) at downstream end of pipe
line. 6 Always use a non-slam and pre
ferably a controlled closing-rate checkvalve at the pump discharge.
7 Besides protecting the pipe at pump start-up, provisions should be considered for reducing waterhammer at pump shut-down or at emergency shut off as can occur from a power outage.
8 When shutting the system off, especially if it is to be started up again within several hours, the system should be designed, if possible, so as to keep out all air, then restart can begin with a completely, water-filled system.
9 Where the level of draw-down in the water supply can drop below that of the pump intake-line, air could be drawn in. This should be avoided and can be accomplished by the use of a pump-feed level-control.
10 The pump drive should operate at a relatively Constant speed and not capable of suddenly racing to excessive speeds. A drive provided with throttled speed control is an advantage at start-up and at shut-off.
Check valves are used to protect the pump and drive from damage by a flow
reversal and/or waterhammer. To protect
the pipe line, use a non-slam check valve at a centrifugal-pump discharge so as to limit waterhammer pressure to a mini mum. The check valve should close at the point of zero velocity, before the reflected surge wave returns from the downstream end. For even further pro tection, a surge-relief device (pressure-
relief valve, surge chamber, etc.) should be located just downstream of the check valve.
Each type of irrigation system has its peculiarities of operating pressures and potential for surge which must be taken into account. Every system must be analyzed in the light of its own perfor mance behavior and requirements, allowable water velocity, hydraulic gra dient and pipeline profile (especially that leaving the pump discharge), pipe diameter, pipe wall thickness, and the needs for protective equipment selected to provide a satisfactory, economic system.
Where waterhammer pressures could develop with sufficient magnitude to
damage PVC pipe, joining methods should be considered having one of the two following possibilities:
1 Use gasketed joints to confine the damage.
2 Where solvent-weld joints are used, install gasketed joints periodically to restrict the length of line damage should excessive waterhammer pressures develop.
While the use of air chambers can protect a line by limiting waterhammer pressures, they must be properly sized, correctly located and adequately main tained.
Pressure relief valves are actuated by a small increase in pressure above a pre set value. They open to discharge water, thereby relieving pressure somewhat and restraining its build-up to a degree.
Since there are many appurtenances for pipeline protection and because of the varied flow conditions associated with a pipeline system, calculations to determine and control waterhammer can be complex. Analysis and treatment of the problem must be tempered with judgment and experience. This paper is concerned essentially with elementary elastic wave theory to determine the magnitude of waterhammer pressures. It is limited in its application to single lines of constant cross-section, contain ing valves and gates. The determination
of waterhammer pressures and asso ciated variations in lines supplied by pumps or supplying turbines cannot be adequately treated in a paper as limited in scope as this one.
An excellent treatment of valves used for surge control has been given in an article by Weaver (1972). Additional references are also given (Ref: Com mercial Catalogues).
PROPER INSTALLATION
Properly installed pipe is a subject not to be ignored or overlooked, but will not be covered to any extent except to note that it should be done by accepted practices and in such a way as to permit safe operation. PVC pipe, like any piping material should be handled and treated with reasonable care. Rough handling, dropping the pipe, allowing it to strike or be struck by objects either before or after installation can seriously damage and weaken the pipe. Such im pact damage, unfortunately, is not always apparent. If the pipe line gradi ent is steep, laying the pipe closer to grade will help to reduce the accumula tion of air pockets. More detailed in struction in pipe line installation can be found in several references noted (SCS
CTD000846
/432-D. SCS 432-E, ASTM D 2321, ASTM D 2774).
RESPONSIBLE USE
A very important factor in the re sponsible use of an irrigation system is proper system start-up. With an empty pipe line, (ill as slowly as possible, ob serving the following cautions:
1 Never completely close the gate valve in the discharge of a deep well tur bine type pump, because of the exces sive shut-off head that develops.
2 Open all manual valves except in the pump discharge. Start filling the line slowly. It is suggested not to fill at a velocity in excess of 1 ft per sec. If it should be necessary to interrupt pump ing while in the process of filling a pipe line, upon restart slow down the input rate even more (a velocity of 1/2 ft per sec maximum is recommended). When restarting into a partly filled line, the appraching steep water front (i.e. the approaching wall of water) may slam in to the back of a stationary wall or into a more slowly moving water boundary with sufficient force to cause a rapid slow down of advancing water rate, par ticularly if air becomes entrapped be tween the fronts, and often results in damaging waterhammer pressures.
3 When water begins to discharge from the downstream end, there will most likely still be pockets of entrapped air. Continue to pump water through at a slow rate until no air is evident for at least a fifteen minute period. Then, if possible, shut off the pump while clos ing the system to keep air from getting in. Wait about 15 min before starting to pump again. Maintain the slow rate of flow until no air can be seen or heard at the discharge end for a least 15 min.
4 Close all manual valves slowly so as to increase the pressure slowly to the full operating line pressure, taking at least 10 min to do so. For larger diame ter pipe (6 in. or larger), for longer lines (more than 1000 ft) and for the higher operating pressures (in excess of 100 psi) proportionately more-than 10 min should be taken to bring the pressure up.
No valve should ever be closed in less than 10 sec (i.e. no less than 5 sec from one-quarter to three-quarters closed), preferably 30 sec or more would be a far safer valve-closure time.
Starting to pump into a filled line re quires that velocity buildup and its attendant pressure rise be done gradu ally. The water should be started into
the line slowly by either manual control
or by automatic control and once
assured that the line is free of air, the
flow should be increased at a rate slow
enough to limit waterhammer pressure.
Many times an irrigation system will
be interrupted momentarily (i.e. shut
off for a period of from 10 min to possi
bly several hours). It is just as important
then to slow down flow as when slowly
increasing flow at start-up. In so doing,
close all valves to keep water in and to
keep all air out. Then when restarting, it
will not be necessary to repurge the line
of air.
When stopping an irrigation system
at any time for any reason, it is just as
important that it be done with the same
due care and caution as that for start
up. However, provisions should be made
to assure protection from excessive
waterhammer pressures, automatically
at emergency shut-down (as by power
outages, etc.). While such automatic
means are protective, they generally do
not reduce waterhammer pressure
enough to be relied upon for repeated,
routine shut-offs. In such cases, addi
tional manual slow down or automatic
throttling should be employed.
References
1 Bennett, Richard. 1942. Waterhammer correctives. Waterworks & Sewerage (89):92-97.
2 Crocker, Sabin, ed. 1945. Piping Handbook, p. 291-300. McGraw-Hill. 1376 p.
3 Dawson, F. M. 1939. Waterhammer and its control. Waterworks Engineering, July 16..
4 DeVries, Dr. Richard M. 1973. Surge prevention in starting and stopping pumps. Presented at AWWA Annual Conference, Las Vegas, Nev. May 4.
5 Everett, Wm. S. 19.67. A (ail-safe method of waterhammer elimination. Irriga tion Engineering and Maintenance. March.
6 Hucks, Jr. Robert T. 1972. Design ing PVC pipe for water-distribution systems. Journal of AWWA 64<8):497-499, August.
7 Kephert, J. I. and Kenneth Davis. 1961. Pressure surges following water-column separation. Transactions of ASME, :456-460, Sept.
8 Kerr, S. Logan. 1948. Practical aspects of waterhammer. Journal of AWWA, June.
9 Kerr, S. Logan. 1950. Surge prob lems in pipe llnes-oil and water. Transactions of ASME. July.
10 Kerr, S. Logan, et al. 1950. New method for bulk-modulus determinations. Transactions of ASME, November.
11 Kerr, S- Logan. 1951. Waterhammer control. Journal of AWWA. Dec.
12 Kerr, S. Logan. 1952. Standard allowances for waterhammer. Journal of AWWA. November.
13 Kerr, S. Logan. 1958. Waterhammer--a problem in engineering design. Consulting Engineer. May.
14 Kerr, S. Logan. 1960. Effect of valve operation on waterhammer. Journal of AWWA. Jan.
15 Lescovich. Joseph E. 1972. Locating and sizing air-release valves. Journal of AWWA. 64(71:457-461. July.
16 Parkmakain. John. 1963. Waterhammer analysis. Dover Publications. 161 P.
17 Perkins, Philip H. 1958. Applica tions and Standards for Asbestos-cement Pipe. Journal of AWWA. Feb.
18 Richard. Richard T. 1939. Air bind ing in water pipe lines. Journal of AWWA. June.
19 Safawat, Hemmat H. and Jaap Van Den Polder. 1972. Experimental and analytic data correlation study of water column separation. ASME Paper No. 72-WA/FE-13. 7 p.
20 Spangler, M. G. 1954. Secondary stresses in buried high pressure pipe lines. The Petroleum Engineer. P. D6-D10. Nov.
21 Sturm. G. W. 1970. Air entrapment problems in automated irrigation systems. World Irrigation. June.
22 Weaver. Douglas L. 1972. Surge Con
trol. Journal of AWWA 64(7):462-466. July. 23 Wilging, Robert C. 1972. Discussion'.
Hucks 1972: Designing PVC pipe for waterdistribution systems. Journal of AWWA 64(8):497-499. August.
24 Wood. Don J. and S. E. Jones. 1973. Waterhammer charts for various types of valves. Proc: Journal of Hydraulics Division of ASCE. 99(HYI): 167-178. Jan.
25 Woodward, Guy O. 1969. Sprinkler irrigation, p. 240-241. Editors Press. 444 p.
26 Zahid. Zeke. 1973. Surge control in water systems. Water St Sewage Works. 120:2:47. Feb.
Commercial Bulletins
and Catalogues
Accumulators: Greer Olear Products (Div, of Greer Hydraulics). Los Angeles, Cal.
Surge Arrestors: Pulsco Controls Corp. Santa Paulo, Cal.
Surge Arrestors: Fluid Kinetics Corp. Ventura, Cal.
Surge Controls: Parco Engineering Corp. Needham Heights, Mass.
Surge Arrestors: Golden Anderson Valve Speciality Co. Pittsburgh. Pa.
Relief & Back Pressure Control Valves: Ross Valve Manufacturing Co., Troy, N.Y.
Apco Air Release Valves & Silent Check Valves: Valves & Primer Corp. Elk Grove Village, m.
Crispin Air Valves: Multiplex Manufac turing Co. Berwick, Pa.
Air Vent, Vacuum Relief & Pressure Relief Valves: Waterman Industries, Exeter, Cal.
Air Release, Vacuum, Pressure Relief & Silent Check Valves: Eddy-Iowa (Div. of Clow) Oskalousa, la.
Pressure, Vacuum, Relief Valves: Western Irrigation Valve Corp. Des Moines, la.
Valves: Pierce Valves. Eugene, Ore. Valves: Clary Valves. San Gabriel, Cal. Check Valves, Relief Valves: Chapman Products (Div. of Crane). Indian Orchard, Ma.
Specifications
AWWA Manual Mil. 1964. Steel pipe de sign and installation, p. 46-52, p. 60-70. 260 p.
AWWA Hl-67. 1967. Standard for thickness design of cast-iron pipe. Table 1-10 p. 63.
AWWA C301-58. 1958. Reinforced con crete water pipe-steel cylinder type, pre stressed. Section 3.2, par. 7.
AWWA C450-53T. 1953. Asbestos-cement water pipe. Section 3.5, section 8.
Soil Conservation Service. 1971. SCS 432-D. National Engineering Standard and Specification for Irrigation Pipelines (High Pressure Underground Plastic). April.
Soil Conservation Service. 1971. SCS
432-E. National Engineering Standard and
Specification for Irrigation Pipelines (Low Head Underground Plastic). April.
Soil Conservation Service. 1971. SCS 432-G. National Engineering Standard and Specification for Irrigation Pipeline (Rein forced Plastic Mortar).
ASTM D 2321-72. 1972. Underground In stallation of Flexible Thermoplastic Sewer Pipe.
ASTM D 2774-69T. 1969. Recommended practice for Underground Installation of Thermoplastic Pressure Piping.