Flammable and Combustible Liquids from flammable vapors, dismantled, and removed from the premises Tanks that are not to be removed should have all flammable liquid removed and be filled with a nonshnnking inert solid material They should have all inlets and outlets capped Tanks taken out of service for less than 90 days should have fill line, gauge opening, and pump suction line capped, and be secured against tampering The vent line should be left open Common Uses of Flammable Liquids Industrial use of flammable liquids in volves ail the general precautions outlined m this chapter pertaining to static, toxicity, storage, housekeeping, explosion-proof elec trical installation, segregation and isolation of operations, ventilation, enclosure of op erations, grounding sources of ignition, and fire and explosion All rooms or portions of plants, and equip ment in them, m which flammable liquids or vapors are used or generated should be con structed, installed, and operated as recom mended by the National Fire Protection Association in its Flammable b Combustible Liquids Code, and as required by local ordinances The following paragraphs discuss several of the more common processes and items of equipment which use flammable liquids, and the precautions applying to each Dip tanks Dip tanks containing flammable liquids subject to ignition at ordinary temperatures and giving off flammable vapors present a severe fire and explosion hazard (See NFPA Standard No 34, Dip Tanks Con taining Flammable or Combustible Liquids ) Dipping operations should be conducted above grade in a detached one-story build ing of noneombustible construction or m a cutoff one-story section m as large a room as possible, adequately ventilated, away from sources of ignition, and conspicuously marked as a flammable liquid area Handling of flammable liquids in open containers can be hazardous and should be avoided The openings should be as small as possible and a cover should be provided FiC 34-17 --Cover for medium-sized dip tank can be hinged and gravity closing or should slide on tracks and be held open by a fusible link or other heat-actuated device Courtesy National Fire Protection Association The cover should be hinged and gravity closing or should slide on tracks and be held open by a fusible link or other heatactuated device (See Fig 34-17) The NFPA states, "Mechanical ventila tion shall be provided and the ventilating system arranged to move air from all direc tions toward the vapor area origin and thence to a safe outside location The ventilating system shall be so arranged that the failure of any ventilating fan shall automatically stop any dipping conveyor system " Tanks with capacities over 500 gal should have bottom drains unless the viscosity of 1040