ZONOLITE FIREPROOFING MONO - KOTE' _ Mono-Kote* cementitious 04502619 spray-applied fireproofing Mono-Kote is the trade name for a fire protection material developed by Construction Products Division, W. R. Grace & Co., specifically for fast application, high fire resistance, and low cost. The material is spray applied by any one of several plastering machines. Mono-Kote is a cementitious (plaster), mill-mixed material requiring only the addition of water at the job. It is applied directly to steel, concrete and other surfaces requiring fire protection. Machine-applied cementitious Mono-Kota withstands air erosion, prevent* "dusting'' in air-conditioning end ventilating systems. page 2 technical data FIRE RESISTANCE: Mono-Kote has been fire tested and rated by Underwriters' Laboratories, Inc., in accordance with test method ASTM E-119. Fire ratings up to 4 hours have been achieved. Each bag of material bears the UL label verifying compliance with UL's quality control inspection program and the appropriate fire resistance rating. The reports and details of these tests are available upon request IN 1970, A MAJOR REVISION TO TEST METHOD E-119 WAS ACCEPTED BY ASTM AND UL BASICALLY, THE REVISION (1) INTRODUCES A NEW SYSTEM FOR RATING THE HOURLY PERFORMANCE OF ASSEMBLIES AND STRUCTURAL MEMBERS AND (2) PROVIDES FOR TWO RATINGS FROM THE SAME FIRE TEST. THE UNDERWRITERS' LABORATORIES INDEX OF FIRE RESISTANCE RATINGS WILL IN GENERAL REFER TO TWO RATINGS --ONE BASED ON TIME-TEMPERATURE PERFORMANCE AND THE OTHER BASED ON A COMBINATION OF STRUCTURAL AND LESSER TIMETEMPERATURE PERFORMANCE CRITERIA. BECAUSE LOCAL BUILDING CODES MAY NOT YET HAVE ADOPTED THIS NEW UL CRITERIA. CONTACT THE JURISDICTIONAL MUNICIPAL AUTHORITY FOR VERIFICATION. Mono-Kote has been tested for other properties such as corrosion resistance, deflection, bond impact, surface hardness, etc. The test results comply with G.S.A. requirements and are available upon request. FIRE HAZARD: Tested and reported in accordance with ASTM E-84 by Underwriters' Laboratories, Inc. Flame Spread-10, Fuel Contributed-5, Smoke Deveioped-O. DRY DENSITY: Approximately 22 p.c.f. RESISTANCE TO AIR EROSION: Independent laboratory test subjected standard, machine-applied Mono-Kote surface to winds exceeding hurricane velocity . . . over 100 M.P.H. for 87 hours . . . with no erosion. Copies of test description available. SPECIFICATION (SHORT FORM): Sprayed fireproofing material shall be Mono-Kote as manufactured by Construction Products Division, W. R. Grace & Co., or its processing distributor, it shall be applied by machine to the thickness required by local codes and in the areas shown on the drawings. The method of mixing and application shall comply with the manufacturer's recommendations. specifications iCHACt i. score a) Work Included Provide all I--*?-;.. mater --1 r and eoui'm-int rccjired for complete installation of all sprayed fireDrccting and related work as shown on the drawings or specified herein, and in accordance with all applicable requirements of the Contract Documents. machine applied material similar to that which can be expected on the project. The air velocity shall be not less than feet per minute, and the J------- -- - - *hr -- -1-- U Note to Specifier: Recommended Quality Criteria: b) Work Not Included 1. Structural steel encased in conc.-;te. 2. Trowelled plaster fireproofing as specified under appropriate section. 3. The cleaning of the surfaces to receive sprayed fireproofing. c) Codes and Regulations This specification shall be supplemented by the applicable requirements of the Building Codes and all authorities having jurisdiction. Conflicts and/or discrepancies between Contract Documents, ordinances, etc., noted by the subcontractor shall be immediately brought to the architect's attention. 2. MATERIALS TESTS a) The architect will select and the owner will pay an independent testing laboratory to sample and verify the density of the direct-to>steei fireproofing as applied. b) Contractor shall control thickness, utilizing a workable depth gauge to meet minimum thickness as required. He shall cooperate with the owner's inspector in furnishing samples for tests. 4. SAMPLES Samples of sprayed fireproofing shall be submitted for approval in accordance with the applicable provisions of the Special Conditions. These samples shall be representative of the material as applied in accordance with Acceptance & Performance Criteria as stated below. a) The sprayed fireproofing shall be plaster cementitious setting-type, and shall be Mono-Kote as manufactured by Construction Products Division, W. R. Grace & Co., or its processing distributors. All manufactured materials shall be mill-mixed and shall be delivered in original, unopened packages bearing the manufacturer's name and the Underwriters' Laboratories, Inc. label. 5. INSTALLATION a) Application of sprayed fireproofing shall be in accordance with the printed instructions of V~ material manufacturer and the fire test report information. b) Upon request a qualified manufacturer's representative can be present for initial application to guide and assist applicator's personnel. The materials shall be stored off the ground, under cover, and away from damp surfaces. Materials shall be kept dry until ready for use. Materials that have been exposed to water before actual use shall be discarded. b) Water shall be clean, fresh and free from organic and mineral impurities which would be harmful to the sprayed fireproofing materials. c) All surfaces to which sprayed fireproofing will be applied shall be free of oil. grease, dirt, loose paint, mill scale or any other matter which would impair bond. d) All clips, hangers, supports, sleeves and other attachments to the fireproofing bases, as covered under other sections of the specifications, are to be placed by others prior to the application of the fireproofing material, where these attachments can be anticipated in advance. e) All patching and repairing of sprayed fireproofing, 3. ACCEPTANCE AND PERFORMANCE CRITERIA a) The sprayed fireproofing shall have been tested by due to cutting by other trades, shall be performed under this section and paid for by the trade(s) that performed the cutting. Underwriters' Laboratories, Inc. in accordance with the procedures of ASTM E-119. The structural steel members shall be protected with adequate fireproofing thicknesses 6. TEMPERATURE AND VENTILATION and densities to provide the following fire resistance ratings: When the prevailing outdoor temperature at the building site is less than 40*F, an interior temperature of 40* F Steel columns...................................................... -Hours shall be maintained for 24 hours before and 24 hours after application of Mono-Kote. Primary steel members (Girders) ................... -Hours The plastering contractor shall provide natural ventilation to properly dry the Mono-Kote during and subsequent to Secondary steel members (Beams) -Hours its application. In glazed buildings, this shall be b) The sprayed fireproofing beneath the deck assembly together with adequately proportioned concrete fill above the metal decking shall provide a hour fire resistant deck assembly as substantiated by a fire test in accordance with the procedures of ASTM E-119, and performed by Underwriters' Laboratories, Inc. accomplished by keeping windows open approximately 2" top and bottom (or side pivoted windows approximately 4") to provide air circulation; and in enclosed areas or buildings lacking openings for natural ventilation, by circulating exterior air and exhausting it to the outside by use of temporary circulators, exhaust fans or the air-conditioning system. c) The fire .-roofing material shall not be subject to losses from the fnished application by sifting, flaking or dusting. This performance shall be measured by the results of a test for erosion resistance when subjected to high velocity air flow across the surface of dried samples. The samples thus tested must be representative of 7. CLEAN UP After completion of fireproofing work, equipment shall be removed and all wall and floor areas cleaned of deposits of sprayed fireproofing materials. page 3 Zonolite plants and sales offices LISTED BELOW GEOGRAPHICALLY ARE THE MARKETS SERVED BY ZONOLITE: MCNO-KOTE? FIREPROOFING FACILITIES. ARIZONA Phoenix 85031. P. 0. Box 14279, (602) 272-6663 ARKANSAS North Little Rock 72114, P. 0. Box 294, (501) 945-1678 CALIFORNIA LOS ANGELES Los Angeles 90039. 5440 San Fernando Rd. West, (213) 245-6491 SAN FRANCISCO-OAKLAND Newark 94560. P. 0. Box 217, (415) 793-9111 COLORADO Denver 80223, 111 South Navajo Street, (303) 722-5707 FLORIDA Boca Raton 33432. P. O. Box 67, (305) 395-3103 Jacksonville 32202. 1530 East Adams St., (904) 355-8431 Tampa 33605, P. O. Box 5047 Ybor Station, (813) 248-1554 GEORGIA Atlanta 30340, 6300 Button Gwinnett Dr.. (404) 448-5880 HAWAII Honolulu 96819, 842-A Mapunapuna Street, (808) 895-105 ILLINOIS CHICAGO Chicago 60643. 12300 South Ashland Ave.. (312) 389-4900 Wilmette 60091, 3201 Old Glenview Rd. KANSAS Wichita 67214, 616 Pennsylvania, (316) 264-6251 KENTUCKY LOUISVILLE Wilders, Newport 41071. 112 North St.. (606) 291-3500 LOUISIANA New Orleans 70121, P. 0. Box 10262, (504) 834-5817 MARYLAND BALTIMORE/WASHINGTON, D.C. Beltsville 20705, P. 0. Box 347, (301) 953-2863 MASSACHUSETTS BOSTON Cambridge, 02140. 62 Whittemore Ave., (617) 876-1400 SPRINGFIELD/WORCESTER Easthampton 01027, P. 0. Box 112. (413) 527-1890 MICHIGAN DETROIT Dearborn 48121, 14300 Henn Avenue. (313) 846-1010 MINNESOTA Minneapolis 55413, 1720 Madison St.. N.E., (612) 789-2327 MISSOURI St. Louis 63110, 1705 Sulphur Avenue, (314) 645-8786 MONTANA Great Falls 49401, P. 0. Box 1419, (406) 453-1291 NEBRASKA Omaha 68107. 3520 "I" Street, (402) 731-3662 NEW JERSEY Trenton 08619. P.0. Box 2124, 15 Industrial Drive, (609) 587-2570; (609) 587-2571 NEW MEXICO Albuquerque 87107, P. 0. Box 6302. (505) 345-1633 i -A NEW YORK CITY New York City 10017. 51 East 42nd Street. (212) 661-3C85 ROCHESTER/SYRACUSE Weedsport 13166. P. 0. Box 310. (315) 834-7971 .'ORTH CAROLINA -,gh Fomt 27260, P. 0. Box 1308, (Sis; 683-E-72 NORTH DAKOTA Minot 58702. P. 0. Box 1782. (701) 838-1991 OHIO CLEVELAND C'eveland 44113, 1125 West 11th Street. (216) 621-3517 CINCINNATI Wilders. Newport, Kentucky. 41071, (606) 291-3500 OKLAHOMA Oklahoma City 73111. P. 0. Box 11402, (405) 232-2058 OREGON Portland 97227, 2303 North Harding Street, (503) 288-5195 PENNSYLVANIA PITTSBURGH New Castle 16102. 202 East Cherry Street. (412) 654-7723 PHILADELPHIA Trenton. N. J. 08619. P.O. Box 2124, 15 Industrial Drive. (609) 587-2570; (609) 587-2571 PUERTO RICO San Juan 00905, P. 0. Box 4007, (809) 782-3080 SOUTH CAROLINA GREENVILLE/SPARTANSBURG Travelers Rest 29690, P. O. Box 517, (803) 834-7272 TENNESSEE Nashville 37204, 4061 Powell Avenue. (615) 242-5496 TEXAS Dallas 75222. P. O. Box 6306. (214) 637-0900 Houston 77008. P. 0. Box 7327. (713) 869-6663 San Antonio 78204, P. 0. Box 9114, (512) 223-5781 UTAH Salt Lake City 34110, P. O. Box 2398, (801) 328-0117 WASHINGTON SEATTLE/TACOMA Auburn 98002, P. O. Box A, (206) 852-5725 SPOKANE Spokane 99201. North 1318 Maple Street (509) 325-2541 WISCONSIN Milwaukee 53208, 900 North 43rd Street. (414) 344-6667 CANADA ALBERTA Calgary 21. 701 Briggs Avenue. (403) 265-6622 Calgary. 1240 Tenth Avenue, S.W.. (403) 244-0811 BRITISH COLUMBIA Vancouver 15. 109 East 69th Avenue. (604) 327-0485 Vancouver. 460 Industrial Avenue, (604) 683-0534 MANITOBA Winnipeg 10. 760 Wall Street, (204) 786-5681 NOVA SCOTIA Truro, 1145 East Prince Street ONTARIO Toronto, 3349A Bloor Street. West. (416) 233-1271 QUEBEC Montreal 379, 140 Deslauriers. (514) 332-0520 SASKATCHEWAN Regina. 1035 Angus Street, (306) 569-3808 ZONOLITE PRODUCES OTHER PL^-'T3 AND FIREPROOFING PRODUCTS .'/RITE FOR THESE DATA SHEETS PA-97R Zonolite Vermiculite P'aster Aggregate PA-96R Zonohte Perlite Plaster Aggregate W. R. GRACE A CO. ZONOLITE PA 106 P' nted in USA Copvrignt 197i. 2oncii?e .s a registered trademark of Construction c.:ts C-v s-:n. w o 3<-:e & Co 62 Afjtt^mcre Ave. Cambridge. Mass. 02UO. We hooe the nfcrmation g.ven here a i; oe neipfui it is oased on ojr oest knowledge, and we believe it to be and accurate Please read an statements, recommendations, or suggestions herein m conjunc* on witn our conditions of saie which apply to a goods supplied by us. We assume no response " '< *ne use of these statements, recommendations or suggestions, nor do we intend them as a ;"nme?cat on for any jse which would infringe any patent or copyright. CONSTRUCTION PRODUCTS division 62 WHITTEMORE AVE., CAMBRIDGE, MASS. 02140 Phone: (617) 876-1400