Document Y9JBJ5xq5reGoxBnYwkmQ1Qpy

Heating Ventilating Air Conditioning Guide 1939 If the published ratings are in terms of decibels per square foot cn rection must be made for area to secure to total sound level of outlets *1 more or less than one square foot area. This can be done by use 0{ following formula: e Decibel Addition = 10 logTM A where: A = core area, square feet. ) In practice the allowable total sound and the required air flow are usually known, and it is desired to determine the maximum allowable velocity. Since total loudness and air flow are both functions of velocity and area, the solution of the problem by use of the previous analysis implies a trial and error method. It has been found possible to present Chapter .28. Air Distribution ? . ,n Thus, if the absorption is 200 sabins, a correction of +1.3 db 08- te made and the permissible velocity becomes that corresponding to .a7 1 loudness level of 31.3 decibels or approximately 750 fpm. If the 3 * is highlyreflecting and has an absorption of less than 100, correction fm (_j1 more important. For instance, for 35 sabins a correction of -- 3 db these data with sufficient practical accuracy as a family of uniform curves as illustrated in Fig. 11. With this chart it is possible to find directly the velocity in feet per minute which\wil! give a predetermined total loudness at a predetermined rate of flow expressed in cubic feet per minute. The values used are arbitrarily chosen for the purpose of discussion and do not necessarily represent data referring to any particular make of grille, register or air outlet. It is assumed that Fig. 11 is based on a room having 100 sabins of sound absorption. In such a room the sound level due to other sources may be 35 db. As previously stated an outlet having a noise level of 30 db would be substantially inaudible in such a room. If 1000 cfm are required with a total noise due to outlet of 30 db, a velocity (Fig; 11) of about 675 fpm may be used. From this velocity and the rate of flow, the core area can be computed. This determination was oh the basis of a room absorption of TOO sabins. If the absorption is greater, the 675 fpm velocity is safe, since the loudness level will go down. However, correction can be made if desired by the use of the chart of 574 must be made and the maximum velocity corresponding to 27 db total loudness chosen; thatjs, approximately 550 fpm. Where more than one outlet must be considered, the problem is more complicated. If a similar outlet is added in a far corner of a highly absorbent room, the change in noise level at the 5 ft station at the first outlet is small; however, if the room is small, or highly reverberant or both, the intensity at the 5 ft station may be almost doubled and the noise level increased nearly 3 db thereby. The.simplest method of-hand- 575